AGENDA ITEM:Consideration of approval of a resolution approving and adopting 2025 City
of Waukee Standard Specifications for Public Improvements
FORMAT:Resolution
SYNOPSIS INCLUDING PRO & CON: The City of Waukee Standard Specifications for Public
Improvements was last updated in July 2024. Staff have determined an amendment to certain post
construction stormwater management requirements specific to treating the water quality volume
(WQv) for properties with existing on site or regional stormwater management facilities is warranted
after discussions with local developers regarding proposed state legislation (SF 595) that would limit
Cities and Counties on what they can require and enforce for WQv requirements. Staff suggest an
update to the Waukee Specifications for Public Improvements to amend subsection 13.5.3 New
Development or Redevelopment with Existing Regional Detention. From staff's perspective, we are
already taking these approaches specific to WQv in our development review process, however the
language adds more certainties for the developer on what will or will not be expected for WQv in a
situation as was discussed and agreed upon with their design representative.
FISCAL IMPACT INCLUDING COST/BENEFIT ANALYSIS:
COMMISSION/BOARD/COMMITTEE COMMENT:
STAFF REVIEW AND COMMENT:
RECOMMENDATION: Approve the resolution.
ATTACHMENTS: I. Resolution
II. 2025 Waukee Specifications for Public Improvements with Changes
Highlighted
PREPARED BY: Rudy Koester
REVIEWED BY: Rudy Koester RK
I1G
THE CITY OF WAUKEE, IOWA
RESOLUTION 2025-
APPROVING AND ADOPTING 2025 CITY OF WAUKEE
STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENTS
IN THE NAME AND BY THE AUTHORITY OF THE CITY OF WAUKEE, IOWA
WHEREAS, the City of Waukee, Dallas County, State of Iowa, is a duly organized Municipal
Organization; AND,
WHEREAS, the Waukee City Council has determined that certain minimum standards of construction
for public improvements are needed and desirable to ensure quality control; AND,
WHEREAS, City staff has provided an update to these standards specifications to include an amendment
to certain post construction stormwater management requirements specific to treating the water quality
volume (WQv) for properties with existing on site or regional stormwater management facility; AND,
WHEREAS, The standard specifications, with such specifications being in accordance with the standards
of the industry and complying with sound engineering principles.
NOW THEREFORE, BE IT RESOLVED THAT:
1.The document entitled Standard Specifications for Public Improvements, Waukee, Iowa, is
hereby adopted.
2.These Standard Specifications shall be followed and used by the City in considering, permitting,
inspecting, and otherwise dealing with the construction of public improvements within the City.
3.These Standard Specifications may, from time to time, be amended, changed, or altered by action
of the City Council.
4.These Standard Specifications shall be used for all projects submitted after the date of adoption of
this resolution.
Passed by the City Council of the City of Waukee, Iowa, and approved the 5th day of May, 2025.
___________________________________
Courtney Clarke, Mayor
Attest:
________________________________
Rebecca D. Schuett, City Clerk
RESULTS OF VOTE: AYE NAY ABSENT ABSTAIN
R. Charles Bottenberg
Chris Crone
Rob Grove
Anna Bergman Pierce
Ben Sinclair
VEENSTRA & KIMM, INC.
SPECIFICATIONS
FOR
PUBLIC IMPROVEMENTS
WAUKEE, IOWA
May 5, 2025
STANDARD SPECIFICATIONS
FOR
PUBLIC IMPROVEMENTS
WAUKEE, IOWA
I hereby certify that this engineering document was prepared by
me or under my direct personal supervision and that I am a duly
licensed Professional Engineer under the laws of the State of Iowa.
Signed: Date:
May 5, 2025
Jordan D. Kappos, P.E.
Iowa License No. 21146
My license renewal date is December 31, 2025
Detailed parts covered by this seal:
________________________________________________________
Prepared by
VEENSTRA & KIMM, INC.
West Des Moines,
Iowa
STANDARD SPECIFICATIONS
FOR
PUBLIC IMPROVEMENTS
WAUKEE, IOWA
INDEX
PART NO. PAGE
1 GENERAL CONDITIONS 1-1
2 DESIGN STANDARDS 2-1
3 EARTHWORK AND INCIDENTALS FOR PAVEMENT 3-1
4 PIPE EXCAVATION AND BACKFILL 4-1
5 STORM SEWERS AND STRUCTURES 5-1
6 SANITARY SEWERS AND APPURTENANCES 6-1
7 WATER MAINS AND APPURTENANCES 7-1
8 STRUCTURAL CONCRETE AND REINFORCING STEEL 8-1
9 SURFACE RESTORATION AND PAVEMENT REPLACEMENT 9-1
10 PORTLAND CEMENT CONCRETE PAVEMENT 10-1
11 KETTLESTONE STREET LIGHTS 11-1
12 TRAFFIC SIGNALS 12-1
13 EROSION AND SEDIMENT CONTROL 13-1
STANDARD DRAWINGS SD-1
1-1
PART 1 - GENERAL CONDITIONS
INDEX
1. FORM 8. CONSTRUCTION IN
2. INTENT HIGHWAY RIGHT-OF-WAY
3. DEFINITION OF TERMS 9. CONSTRUCTION IN PUBLIC
4. INTERPRETATION RIGHT-OF-WAY
5. CONTRACT AND BOND REQUIREMENTS 10. STANDARDS AND CODES
6. GENERAL REQUIREMENTS 11. MATERIALS TESTS
7. CONSTRUCTION IN RAILROAD 12. INSURANCE BY CONTRACTOR
RIGHT-OF-WAY 13. INSPECTION BY CITY
14. MATERIAL SUBSTITUTIONS
1. FORM
1.1 Standard specifications are in outline form and include incomplete sentences.
Omission of words or phrases is intentional. Supply omitted words or phrases by
inference.
2. INTENT
2.1 To set forth design standards and requirements of materials and construction for
installation of street pavement, sidewalks, trails, water mains, sanitary sewers,
storm sewers, sump pump drain lines, traffic signals and street lights in
subdivisions, site plans and other public improvements.
2.2 To assist in implementing the Subdivision Ordinance of the City of Waukee, Iowa.
2.3 To ensure that streets and utilities meet requirements of the City of Waukee, Iowa,
and the Iowa Department of Natural Resources (IDNR) and to ensure conformance
to the Comprehensive Development Plan of the City of Waukee.
2.4 To require construction of street pavement, sidewalks, trails, water mains, sanitary
sewers, storm sewers, sump pump drain lines, street lights and traffic signals in
subdivisions.
3. DEFINITION OF TERMS
3.1 "City" shall mean the City of Waukee, Iowa, acting through a person or persons
duly authorized by the City Council to act for said Council. City shall also mean the
area within the corporate limits of the City of Waukee and such area outside the
corporate limits over which the City has jurisdiction or control in accordance with
statutory provisions of the Code of Iowa.
General Conditions
1-2
3.2 "City Engineer" shall mean a person or persons designated by the City with authority
to perform official inspections, plan reviews and other functions designated by City
Council.
3.3 "City Engineering Department" shall mean person or persons hired by the City within
the department with authority to perform official inspections, plan reviews and
other functions designated by City Council.
3.4 "Comprehensive Development Plan" shall mean the current comprehensive
development plan approved by the City Council of the City of Waukee, Iowa.
3.5 "Contractor" shall mean the person, firm, partnership, association or corporation
constructing streets and utilities.
3.6 "Landscape and Open Space Ordinance" shall refer to the Waukee Municipal Code
and other governing ordinances or plans which provide regulation as to the
beautification, buffering, or improvement of property relating to plantings,
hardscape, streetscape, or similar treatments of property within the City of Waukee.
3.7 “Shared Use Path” shall mean a multi-use trail or other path, physically separated
from motorized vehicular traffic by an open space or barrier, either within a highway
right-of-way or within an independent right-of-way, and usable for transportation
purposes.
3.8 "Site Plan" shall mean an architectural plan, landscape plan, or detailed engineering
drawings of proposed improvements to a given lot or subdivision that can include
any or all of the following information: building footprint, streets and drives, grades,
parking, drainage facilities, storm water management, sanitary sewer mains and
services, water mains and services, storm sewer mains and services, sidewalks and
trails, lighting and landscaping elements.
3.9 "Site Plan Ordinance" shall refer to the Waukee Municipal Code along with other
governing ordinances or plans which provide regulation of sites within the City of
Waukee.
3.10 "Standard Drawings" shall mean drawings bound or referenced with these
specifications.
3.11 "Subdivider" shall mean any person, partnership, corporation, trustee, trust or other
legal entity dividing or proposing to divide or improve land so as to constitute a
subdivision or site plan.
General Conditions
1-3
3.12 "Subdivision" shall mean the division of land into two or more lots, parcels or other
divisions for the purpose of immediate or future sale or transfer of ownership or
building development. The term includes resubdivision and, when appropriate to
context, shall relate to the process of subdividing or to the land subdivided.
3.13 "Subdivision Ordinance" shall mean the current ordinance enacted by the City
Council of the City of Waukee, Iowa, establishing regulations for the subdivision and
platting of land, providing for the preparation of plats and providing for the
installation of utilities, streets and other improvements.
3.14 “SUDAS” shall mean the latest edition of the Statewide Urban Design and
Specifications including Design Manual and Standard Specifications.
4. INTERPRETATION
4.1 The City will answer questions regarding interpretation of intended meaning of
specifications; its interpretation shall be accepted as final.
5. CONTRACT AND BOND REQUIREMENTS
5.1 Contract between subdivider and his contractor shall be executed on forms provided
or approved by City prior to start of construction.
5.2 Subdivider's contractor shall provide maintenance bond to City, assuring faithful
performance of his contract and maintenance of the improvements for a period
after acceptance of the construction thereof by City; execute bond on forms
provided or approved by City for the following bond periods:
5.2.1 Water, sanitary sewer, storm sewer and subdrains including services to
property: 4 years.
5.2.2 Street pavement: 4 years.
5.2.3 Shared used paths:
5.2.3.1 Trails: 4 years.
5.2.3.2 Sidewalks: 4 years. Sidewalks by plat developer are limited to
lots with double frontage to pay for sidewalk along the frontage
without direct vehicular street access.
5.2.4 Site grading and subgrade preparation: 4 years.
General Conditions
1-4
5.3 Subdivider shall provide performance bond to City, assuring faithful performance of
his contract for conversion of any and all temporary erosion control sediment basins
to permanent stormwater control detention basins; execute bond on forms
provided or approved by City.
5.4 Maintenance bond shall list each item and quantity of each item covered by the
bond.
5.5 See Exhibit No. 1 following GENERAL CONDITIONS for acceptable forms of
of bonds.
6. GENERAL REQUIREMENTS
6.1 Submit plans of proposed construction for approval and acceptance by the City,
prior to construction and as set forth in the Municipal Code; all improvements to
extend to plat boundary unless directed otherwise by City.
6.1.1 Standard organization of construction drawings shall be as follows:
6.1.1.1 Cover Sheet
6.1.1.2 Quantities & General Information
6.1.1.3 Hydrant Coverage Map
6.1.1.4 Demolition Plan (if applicable)
6.1.1.5 Grading Plan
6.1.1.6 Erosion & Sediment Control Sheet
6.1.1.7 Paving and Storm Plan and Profile
6.1.1.8 Water and Sanitary Plan and Profile
6.1.1.9 Intersection and Pedestrian Ramp Details
6.1.1.10 General Details
6.1.1.11 Landscaping Plan
General Conditions
1-5
6.2 Submit plans for proposed construction of water mains and sanitary sewers and
stormwater General Permit No. 2 to the IDNR for review and approval in accordance
with the requirements of that agency.
6.2.1 Furnish City with 1 copy of plans approved by IDNR.
6.3 Begin no construction of water mains and sanitary sewers until plans are approved
by City and Iowa Department of Natural Resources.
6.4 Begin no construction without City issuance of Construction Site Erosion and
Sediment Control Ordinance (COSESCO) permit.
6.5 Materials and work are subject to inspection as deemed necessary by City; provide
access for inspectors.
6.6 Make no connection to existing water and sewer systems or work in public right-of-
way unless authorized by City.
6.7 Provide shop drawings for materials used in construction of public improvements.
6.8 Monthly project schedules are required to be submitted prior to processing of
partial pay estimates.
6.9 Upon completion of construction, furnish one certified reproducible paper copy of
as-built plans to City; plans shall be certified by Engineer licensed to practice in the
State of Iowa; furnish electronic files of as-built plans; electronic files in .dwg and
.pdf file extensions format approved by City and provided with information layers to
allow retrieval of lot layout, water, sanitary sewer and storm sewer alignment
information isolated from notes on background drawing information.
6.10 As-built plans are required for all development and shall contain the following
information:
6.10.1 Certified grading sheet shall provide point elevations for the low spot at
each location where an overland flowage easement crosses a property line,
at any change in grade across each lot, and at lot corners and sideyard lot
midpoints. The grade between shots should also be labeled.
General Conditions
1-6
6.10.2 As-built plans of all stormwater management facilities on site and a
certification statement signed by the design engineer indicating that
facilities were constructed as designed. Required information includes
inlet and outlet flow line elevations, normal pool surface water elevation (if
applicable), 100-year surface water elevation, overflow route and
elevation, orifice opening or weir information, storage volume provided,
and post-developed release rate. All corresponding design information
shall be provided on as-built plans for comparison. Survey information
shall be provided for bottom of retention ponds.
6.10.3 Provide as-built location for the ends of all lot services in relation to lot
property corners.
6.10.4 Point elevations at corners of all curb ramps and turning spaces within
right-of-way.
6.10.5 Size, flow lines, and locations of all storm sewer and sanitary sewer
including structures and appurtenances.
6.10.6 City staff will obtain elevations and locations of water main fittings prior to
fittings being backfilled. Contractor responsible for notifying City staff.
6.11 City will provide checklist for items remaining to be completed near the end of the
construction. Certificate of Completion will be issued after acceptance of work by
City Council and completion of all checklist items. Maintenance bond effective date
begins on date of acceptance by City Council.
6.12 Design all public improvements to survey and coordinate system State Plane Iowa
South Zone (1402) NAD 83. Note survey and coordinate system utilized on plans.
6.13 Design streets and utilities in accordance with Municipal Code, SUDAS
Design Manual and Standard Specifications of the City of Waukee. In the event of
conflicts between the documents, the Municipal Code shall govern, then the
Standard Specifications of the City of Waukee and finally SUDAS Design Manual. All
designs are subject to approval of City.
6.14 Locate utilities parallel to right-of-way lines as shown on Standard Drawings
Nos. 1A and 1B. Where strict compliance to these locations causes substantial
hardship, the City Council, upon recommendation of its staff, may modify these
requirements.
General Conditions
1-7
6.15 Streets: conform to Municipal Code for right-of-way requirements for streets;
provide street widths as specified hereinafter; construct streets to grades approved
by City.
6.15.1 Construct all street surfaces of reinforced portland cement concrete with
integral curb and gutter.
6.15.1.1 City will consider non-reinforced concrete pavement, if
requested.
6.15.2 Furnish and install all signs and barricades as specified herein.
6.16 Shared use paths: construct paths on both sides of street; locate as shown on
Standard Drawing; plat developer responsible for paths along double frontage lots
for frontage where lot does not have direct vehicular access; home builder
responsible for construction of all other paths.
6.17 Storm sewers:
6.17.1 Extend sewer line and grade to natural water course, to existing storm
sewer, or as directed by City.
6.17.2 Extend storm sewer upstream to plat or property boundary, or to within
500' of basin ridge, whichever is less, or as directed by City.
6.17.3 Provide minimum 8" dia. perforated subdrain or minimum 3’ wide
concrete flume along rear lot lines or side yards where surface flowage has
2% or less longitudinal slope; provide flat grate intakes in areas where
standing water is present after a 1" rainfall event after finished grading of
the site is completed; comply with material standards for subdrains.
6.17.4 Construct manhole on temporary ends of storm sewer; locate manhole
within 15' of plat boundary and install one segment of pipe upstream from
manhole or as directed by City.
6.17.5 Clean and televise storm sewer prior to or immediately following
constructing street paving as directed by the City; provide copy of video
and written report to City for review prior to or immediately following
constructing street paving as directed by the City; correct defect prior to
or immediately following paving as directed by the City.
General Conditions
1-8
6.18 Sanitary Sewers:
6.18.1 Clean and televise sanitary sewers prior to constructing street paving;
provide copy of video and written report to City for review prior to
constructing street paving; correct defects prior to paving.
6.18.2 Extend sewer line and grade to plat of property boundary, to next street
or sewer, or as directed by City; locate manhole within 15' of plat
boundary and install one segment of pipe upstream from manhole.
6.19 Sanitary sewer service connections:
6.19.1 Provide service connection for each platted lot or building; extend
service from sanitary sewer to 10’ inside property line, or as directed by
City.
6.19.2 Extension of sewer service pipe from property line to building or residence
responsibility of property owner.
6.19.3 Service connections include wye, fittings, riser pipe, if required, and pvc
service pipe.
6.20 Pumping stations and force mains: where a pumping station is required to lift
sewage to existing sewer system, submit complete design to City for approval;
include equipment drawings, design data and proposed plans.
6.21 Water Main:
6.21.1 Extend Water main line and grade to plat or property boundary, to next
street, or as directed by City; terminate dead end lines at plat boundary
with valve and 10’ section of water main and plug; to the extent possible,
City will require looping of water mains in lieu of dead end mains.
6.21.2 Furnish all water main and appurtenances including hydrants and valves.
6.22 Water services: provide service for each platted lot or building; include corporation
stop or other fitting, water service pipe and curb valve with box.
General Conditions
1-9
6.22.1 Extend service pipe from water main to property line or as directed by
City; locate top of curb valve box at finished grade; locate curb valve at
property line unless directed otherwise by City; do not locate service
under property approach driveway.
6.23 Sump pump drain lines: provide sump pump drain lines to receive discharge from
foundation drain sump pumps; extend to lot line.
6.24 Final adjustments of manhole covers, hydrants and valve boxes by Contractor
installing the utility after street pavement is in place.
6.25 All materials and accessories for construction of streets, sidewalks, trails, sewers
and water main, street lights and traffic signals furnished by subdivider except by
specific agreement with City.
6.26 Provide necessary easements to City for all City utilities located in or adjacent to
private property; minimum width: 10' either side of City utility or 2 times the utility
depth, whichever is greater, unless otherwise permitted or required by City.
7. CONSTRUCTION IN RAILROAD RIGHT-OF-WAY
7.1 Submit detailed plans of construction operations including sheeting, shoring and
bracing, for approval of Railroad and City.
7.2 Start no work on Railroad right-of-way until plans required above are approved
and license for construction is granted by Railroad; provide a copy of license to
City.
7.3 Notify Railroad Division Superintendent and City not less than one week in advance
of proposed time for performance of any construction work on Railroad right-of-way
or preparatory work thereto.
7.4 Confer with representative of Railroad relative to requirements for operation and
general safety regulations.
7.5 Conduct work in manner satisfactory to Railroad and exercise care not to damage
Railroad property or interfere with operations of Railroad.
7.6 The Railroad Division Superintendent or his representative will have jurisdiction over
safety for operations of Railroad. The decision of the representative of the Railroad
as to procedures which may affect safety of Railroad operation shall be final.
General Conditions
1-10
7.6.1 Provide insurance coverage requested by Railroad.
7.7 Do not stockpile or store excess material or debris on Railroad right-of-way.
7.8 Submit copy of the Railroad's certificate of acceptability to City after construction.
8. CONSTRUCTION IN HIGHWAY RIGHT-OF-WAY
8.1 Submit detailed plans of construction operations including sheeting, shoring and
bracing, for approval of Iowa Department of Transportation (IDOT).
8.2 Secure construction permit for proposed construction; start no work in highway
right-of-way until plans are approved and permit for construction is granted by
IDOT; provide a copy of permit to City. All construction within the State Rights of
Way shall comply with the appropriate approved permit and the agreements stated
within them.
8.3 Comply with applicable sections of current "Utilities Accommodation Policy" of
IDOT.
8.4 All traffic protection shall be in accordance with Part VI of the current Manual on
Uniform Traffic Control Devices for Streets and Highways.
8.5 Comply with all safety regulations of IDOT.
9. CONSTRUCTION IN PUBLIC RIGHT-OF-WAY
9.1 Submit detailed plans or construction operations for approval of City; obtained
permit for construction in public right-of-way from City.
9.2 Auger or directional bore water main, sewer, services and other utilities under all
existing streets; do not open cut except when authorized by City.
9.3 Start no work on public right-of-way until plans required above are approved and
permission is granted by City.
9.4 The placement of electronic message boards notifying the public of upcoming lane
or street closures may be required by the City. If required by the City, the message
boards are to be in place a minimum of two weeks prior to lane or street closure
unless approved otherwise by the City. Message boards are to be visible for each
direction of vehicle travel except for cul-de-sacs.
General Conditions
1-11
9.5 All utility lines, including electric and telecommunication lines, shall be installed
underground.
10. STANDARDS AND CODES
10.1 Do work in accordance with best present day construction practices.
10.2 Unless specifically noted to the contrary, conform with and test in accordance with
applicable section of latest revisions of following standards and codes:
10.2.1 American Association of State Highway and Transportation Officials
(AASHTO).
10.2.2 American Concrete Institute (ACI).
10.2.3 American Institute of Steel Construction (AISC).
10.2.4 American National Standards Institute (ANSI).
10.2.5 American Society for Testing and Materials (ASTM).
10.2.6 American Water Works Association (AWWA).
10.2.7 American Welding Society (AWS).
10.2.8 Federal Specifications (FS).
10.2.9 Iowa Department of Natural Resources (IDNR).
10.2.10 Iowa Department of Transportation, Standard Specifications For Highway
and Bridge Construction, latest edition (IDOT).
10.2.11 Manual of Accident Prevention in Construction by Associated General
Contractors of America, Inc. (AGC).
10.2.12 National Sanitation Foundation (NSF).
10.2.13 Occupational Safety and Health Act of 1970 (Public Law 91-596) (OSHA).
10.2.14 Iowa Occupational Safety and Health Act of 1972 (Chapter 88, Code of
Iowa,) (IOSHA).
General Conditions
1-12
10.2.15 Standards and Codes of the State of Iowa and ordinances of the City of
Waukee, Iowa.
10.2.16 Other standards and codes which may be applicable to acceptable
standards of the industry for equipment and materials and installation.
10.2.17 Standards and codes of Railroad.
10.2.18 Iowa Manual on Uniform Traffic Control Devices for Streets and Highways.
10.2.19 Statewide Urban Design and Specifications (SUDAS) including Design
Manual and Standard Specifications.
11. MATERIALS TESTS
11.1 Submit to City duplicate copies of reports by an independent testing laboratory
showing compliance of construction materials with specifications. Selection of
testing laboratory subject to approval by City.
11.2 Subdivider to pay cost of all laboratory and job site tests including transportation
charges on samples taken at job site.
11.3 Subdivider provide samples of materials and forms for preparing concrete
compression cylinders required for laboratory tests; sampling of materials at the site
and preparation of concrete compression cylinders performed by subdivider subject
to approval of method by City Engineer or City Engineering Department.
11.4 All materials subject to testing and inspection at the site by City.
11.5 Laboratory tests:
11.5.1 Portland cement: car, truck, or sealed bin samples for total requirements;
ASTM C150.
11.5.2 Fine aggregate for portland cement concrete: tests on each 100 tons for
deleterious substances, mortar strength and gradation.
11.5.3 Coarse aggregate for portland cement concrete: tests on each 500 tons for
abrasion loss, durability, deleterious substances and gradation.
11.5.4 Concrete pipe: certify that pipe conforms to ASTM C76 or ASTM C506,
for class of pipe specified.
General Conditions
1-13
11.5.5 Reinforcing steel: certify that steel conforms to ASTM A615, for grade
of steel specified.
11.5.6 Iron pipe: certify that ductile pipe conforms to ANSI/AWWA C150/
A21.50 and ANSI/AWWA C151/A21.51, special thickness class 52.
11.5.7 Polyvinylchloride pipe:
11.5.7.1 Sump pump drain lines and subdrains: certify that pipe
conforms to ASTM D1784 and ASTM D3034.
11.5.7.2 Water main and force main: certify that pipe conforms to
AWWA C900 or C905, DR18.
11.5.7.3 Truss pipe for gravity sewers: certify that pipe conforms to
ASTM D2680.
11.5.7.4 Corrugated pipe with smooth interior for gravity sewers:
certify that pipe conforms to ASTM D1784, ASTM F794 and
ASTM F949.
11.5.7.5 Sewer service pipe: certify that pipe conforms to ASTM D3034,
DR23.5.
11.5.8 Steel pipe: certify that pipe conforms to ASTM A139.
11.5.9 Copper tubing: certify that tubing conforms to ASTM B88, Type K.
11.5.10 High density polyethylene (HDPE) corrugated pipe: certify that pipe
conforms to ASTM F405 or F667.
11.5.11 Manholes: certify that precast sections conform to ASTM C478.
11.5.12 Welded wire fabric: certify that wire fabric conforms to ASTM A185.
11.5.13 Lining for reinforced concrete pipe:
11.5.13.1 Liner material: polyvinylchloride resin pigments and plasticizers;
compounded to remain flexible; polyvinylchloride resin not less
than 99% by weight of total resin used; copolymer resins not
permitted.
General Conditions
1-14
11.5.13.2 Physical properties of liner: tensile strength: 2,200 psi minimum
elongation at break: 200% minimum.
11.5.13.3 Following installation all surfaces covered with lining, including
welds shall be tested with an approved electrical holiday
detector with instruments set between 18,000 volts and 22,000
volts.
11.5.13.4 All welds shall be physically tested by a non-destructive probing
method.
11.5.14 Concrete compression cylinders: ASTM C39; cast three cylinders for each
days pour if pour is less than 100 CY; if pour is more than 100 CY, cast three
cylinders for each 100 CY poured with a minimum of two sets per day.
Contractor is responsible for hiring independent testing laboratory for
casting, protecting, pick-up, delivery, proper storage and testing of
cylinders. Submit written report and test results of 7-day and 28-day
cylinder breaks to City. At the discretion of contractor, additional cylinders
may be cast to allow testing for earlier access to pavement than 7 days.
11.5.15 Concrete air and slump: IDOT Instruction Manuals 317, 318 and 327; one
test for air and slump for each 200 CY poured with a minimum of one per
day. Contractor is responsible for hiring independent testing laboratory for
testing. Submit written report of test results to City.
11.5.16 Moisture-density tests on subgrade: ASTM D698; make 2 tests per 150 LF
feet of subgrade or where designated by City; make tests and submit
written report and test results to City.
11.5.17 Moisture-density tests on pipe trench backfill: ASTM D698; make series of
tests at 3' vertical intervals full depth of trench backfill at nominal 150 LF
horizontal spacing; City reserves the right to vary spacing between test
locations; make additional tests at all locations where trenches from storm
sewer, sanitary sewer, water main, sanitary sewer service, water service
and sump lines are located under proposed streets and trails and submit
written report and test results to City;
maintain moisture content of backfill material in range of optimum
moisture content to 4% above optimum moisture content.
General Conditions
1-15
12. INSURANCE BY CONTRACTOR
12.1 Provide and maintain insurance throughout construction period in the following
minimum amounts.
12.1.1 Workmen's compensation and occupational disease insurance in
accordance with laws of the State of Iowa covering all employees who
perform any obligations assumed under the contract.
12.1.2 Public liability (bodily injury and property damage) covering all operations
under this contract; limits for bodily injury or death and property damage
not less than $1,000,000 per occurrence and $2,000,000 aggregate.
12.1.3 Automobile liability insurance on all self-propelled vehicles used in
connection with the contract, whether owned, non-owned, or hired; public
liability limits of not less than $1,000,000 CSL (Combined Single Limit).
12.1.4 Insurance as required by Railroad.
12.1.5 Provide minimum $1,000,000 occurrence and $1,000,000 aggregate
umbrella insurance.
12.1.6 Certificates must reflect companies that are licensed and approved to do
business in the state of Iowa and have a BEST guide rating of A minus or
better.
12.1.7 Contractor must name the City as additional insured on a primary non
contributory basis. Contractor shall submit endorsements showing such
coverage with the certificate.
12.2 City shall have right at any time to require public liability insurance and property
damage liability insurance greater than required in above paragraphs.
12.3 Furnish certificates of insurance to City made in favor of City showing compliance
with foregoing requirements.
13. INSPECTION BY CITY
13.1 Construction will be inspected by the City's designee to insure compliance with
these specifications.
General Conditions
1-16
13.2 Subdivider shall notify and coordinate preconstruction meeting to be held
minimum one week prior to construction to be attended by subdivider, contractor,
subcontractor(s), subdivider's engineer and City Engineering Department.
Subdivider to notify City Engineering Department to schedule meeting.
13.3 Forward a construction schedule to City Engineering Department prior to start of
construction and notify City Engineering Department not less than 48 hours in
advance of readiness for required inspections.
13.3.1 City Engineering Department shall determine type and number of
inspections required based on construction proposed.
13.3.2 Notify City Engineering Department not less than 48 hours in advance of
performing any holiday or weekend work.
13.4 Subdivider shall reimburse City for costs of inspections and tests furnished and
conducted by or on behalf of City.
14. MATERIAL SUBSTITUTIONS
14.1 Wherever items of materials or equipment are specified by a manufacturer's name
and type, or equal, it is the intent that materials or equipment of other
manufacturers, equal in quality and performance, may be substituted. Such
substitution may be made only with written authorization of City.
14.2 Wherever items of materials or equipment are specified by a manufacturer's name
and type, or equal, and additional features of items are specifically required by
specifications, additional features specified shall be provided whether or not they
are normally included in standard manufacturer's items listed.
14.3 Wherever items of materials or equipment are specified by a manufacturer's name
and type, or equal, and specified items are or become obsolete and no longer
available, Subdivider shall provide City acceptable equal items which are currently
available.
14.4 When proposing "or equal" items or substitutions, Subdivider shall furnish general
arrangement drawings, full descriptive data, manufacturer's specifications and such
performance data as required to satisfy City that materials or equipment proposed
are equal to that specified. Burden of proof of equality shall be responsibility of
Subdivider.
General Conditions
1-17
14.5 Whenever items of materials or equipment are specified by a manufacturer's name
and type and "or equal" is not listed, Subdivider shall provide specified equipment
without substitution, unless prior approval of City is obtained for any substitution.
14.6 Subdivider shall abide by City’s decision when proposed substitutes of material or
equipment are deemed to be unacceptable by the City and in such an event
Subdivider shall furnish items of equipment or materials specified.
14.7 City reserves right to consider such factors as overall project arrangement, overall
operation and maintenance costs, and similar factors in determining whether
proposed substitutions will be acceptable.
EXHIBIT NO. 1
MAINTENANCE BOND
Bond Number ___________
Job Number ____________
KNOW ALL MEN BY THESE PRESENTS:
That ______________________________________________ of
_________________________ as Principal, and ___________________________________________
of _________________________ as Surety, are held and firmly bound unto the CITY OF WAUKEE,
230 Highway 6, Waukee, Iowa 50263, in the penal sum of _____________________________
($_______________________) Dollars, lawful money of the United States of America, for the
payment of which, well and truly to be made, the Principal and Surety bind themselves, their, and each
of their heirs, executors, administrators, successors and assigns, jointly and severally, firmly by these
presents.
WHEREAS, the said Principal entered into a certain contract, dated the ________ day of
_________________, 20___, with the _____________________________________________, to
furnish all the material and labor necessary for the construction of
__________________________________________________________________________________
__________________________________________________________________________________
_________________________________________________________________________________
in the County of Dallas, State of Iowa, in conformity with certain specifications according to the
subdivision ordinances of the City of Waukee, Iowa; and
WHEREAS, a further condition of said contract, and acceptance of the work by the City of
Waukee, Iowa, is that said Principal shall furnish a bond of indemnity, guaranteeing to remedy any
defects in workmanship or materials that may develop in the aforesaid work and improvements, and to
otherwise keep said improvements in good repair, for a period of four (4) years from the date of the
issuance of a Certificate of Completion by the City Council; and
WHEREAS, a request for a Certificate of Completion for the work has been submitted and is
being considered by the City Council, and this bond is being submitted in support of said request; and
WHEREAS, the said _____________________________________ of _______________,
Iowa, for a valuable consideration, has agreed to join with said Principal in such bond and/or
guarantee, indemnifying said City of Waukee, Iowa as aforesaid.
Now, the Principal and the Surety on this Bond hereby agree, at their own expense:
A. To remedy any and all defects that may develop in, or result from, said work by reason
of bad workmanship or poor material used in the construction of said work and
improvements, and shall otherwise keep all work in continuous good repair, and shall in
all other respects, comply with all the terms and conditions of the specifications and
ordinances of the City of Waukee, Iowa with respect to maintenance and repair of said
work and improvements for a period of four (4) year(s) from the date of issuance
of a Certificate of Completion for said work by the City Council; and
B. In addition, Principal and Surety shall pay the testing, expert evaluation, reports, and all
associated costs incurred by the City (collectively referred to generally as Testing)
related to the City’s ascertaining the nature and extent of any defect that appears in said
work for which Principal and/or Surety are responsible under Paragraph A above.
Prior to undertaking such Testing, the Parties shall attempt to reach agreement as to the
person or firm who shall undertake the Testing, however, if the parties cannot reach
agreement, the City shall select the person or firm to undertake the Testing and
associated work, in its discretion.
NOW THEREFORE, the condition of this obligation is such that if said Principal shall
faithfully perform all of the promises of the Principal, as set forth and provided in this Bond, then this
obligation shall be null and void, otherwise it shall remain in full force and effect.
IN WITNESS WHEREOF, we have hereunto set our hands and seal this ____day of
________________, 20____.
_________________________________________,
Principal
By: ______________________________________
Name and Title
__________________________________________,
Surety
By: _______________________________________
Name and Title
PERFORMANCE BOND
Bond Number ___________
Job Number _____________
KNOW ALL MEN BY THESE PRESENTS:
That ______________________________________________ of
_________________________ as Principal, and ___________________________________________
of _________________________ as Surety, are held and firmly bound unto the CITY OF WAUKEE,
230 Highway 6, Waukee, Iowa 50263, in the penal sum of _____________________________
($_______________________) Dollars, lawful money of the United States of America, for the
payment of which, well and truly to be made, the Principal and Surety bind themselves, their, and each
of their heirs, executors, administrators, successors and assigns, jointly and severally, firmly by these
presents.
WHEREAS, the said Principal entered into a certain contract, dated the ________ day of
_________________, 20___, with the _____________________________________________, to
furnish all the material and labor necessary for the construction of
__________________________________________________________________________________
__________________________________________________________________________________
_________________________________________________________________________________
in the County of Dallas, State of Iowa, in conformity with certain specifications according to the
subdivision ordinances of the City of Waukee, Iowa; and
WHEREAS, a further condition of said contract, and acceptance of the work by the City of
Waukee, Iowa, is that said Principal shall furnish a performance bond guaranteeing the conversion of
any and all temporary erosion control sediment basins to permanent stormwater control detention
basins.
WHEREAS, a request for a Certificate of Completion for the work has been submitted and is
being considered by the City Council, and this bond is being submitted in support of said request; and
WHEREAS, the said _____________________________________ of _______________,
Iowa, for a valuable consideration, has agreed to join with said Principal in such bond and/or
guarantee, indemnifying said City of Waukee, Iowa as aforesaid.
Now, the Principal and the Surety on this Bond hereby agree, at their own expense:
A. The conversion of any and all erosion control sediment basins to permanent
stormwater control detention basins including silt removal and disposal, earthwork,
grading, piping, stormwater control structures, rip-rap, as-builts and surface
restoration.
NOW THEREFORE, the condition of this obligation is such that if said Principal shall
faithfully perform all of the promises of the Principal, as set forth and provided in this Bond, then this
obligation shall be null and void, otherwise it shall remain in full force and effect.
IN WITNESS WHEREOF, we have hereunto set our hands and seal this ____day of
________________, 20____.
_________________________________________,
Principal
By: ______________________________________
Name and Title
__________________________________________,
Surety
By: _______________________________________
Name and Title
2-1
PART 2 – DESIGN STANDARDS
INDEX
1.GENERAL 8.SUMP PUMP DRAIN LINES
2.STREETS 9.SUBDIVISION LOT GRADING
3.SHARED USE PATHS AND MAINTENANCE
4.STORM SEWERS 10.STREET LIGHTS
5.SANITARY SEWERS 11. TRAFFIC SIGNALS
6.PUMPING STATIONS 12. FIBER OPTIC LINES
AND FORCE MAINS 13. STORMWATER MANAGEMENT
7.WATER MAINS
1. GENERAL
1.1 This section sets forth minimum design standards to be used for design of
streets, sidewalks, trails, sewers, water mains, sump pump drain lines, traffic
signals and street lights in subdivisions in the City of Waukee, Iowa.
1.2 The design standards specified hereinafter are minimum standards; all plans are
subject to review and approval by the City.
1.3 Provide all lots in subdivision with water, sanitary sewer and sump pump drain
service lines; stub sanitary sewer service 10' inside lot line; stub water and
sump pump drain services to lot line; omit Pipe Bedding Material on the last 5’
of sanitary service pipe at stub end; install curb stop valve and box on lot lines.
1.4 Provide geotechnical exploration and report for all proposed street, sanitary and
storm sewer and water main projects in accordance with the SUDAS Design
Manual; submit written report and test results to City for review.
2. STREETS
2.1 Design streets in accordance with SUDAS Design Manual, Subdivision Ordinance
of the City of Waukee, Iowa, and the following standards:
Design Standards
2-2
2.2 Culs-de-sac are subject to approval by City on project-by-project basis; provide
areas designated for snow removal storage from cul-de-sac.
2.2.1 Provide temporary 40' radius, granular surfaced turn around at temporary
ends of portland cement concrete pavement where temporary pavement
end is more than 150' from a street intersection. Other temporary turn
around configurations may be acceptable as approved by the City
Engineering Department. Granular surfacing to be a total of 8” thick with 4”
thick of 3” gradation rock base and with 4” thick of 1” road stone on top.
2.3 Minimum pavement thickness:
2.3.1 Local service and loop streets: 7" non-reinforced portland cement
concrete over 12” thick compacted natural subgrade.
2.3.2 Minor collector streets: 7” non-reinforced portland cement concrete
over 6” thick granular modified subbase with 12” thick compacted
natural subgrade.
2.3.3 Major collector streets: 8” non-reinforced portland cement concrete
over 6” thick granular modified subbase with 12” thick compacted
natural subgrade.
2.3.4 Minor arterial streets: 9" non-reinforced portland cement concrete
over 6” thick granular modified subbase with 12” thick compacted
natural subgrade.
2.3.5 Major arterial streets: 10” non-reinforced portland cement concrete
over 6” thick granular modified subbase with 12” thick compacted
natural subgrade.
2.3.6 Construction requirements for reinforced and non-reinforced portland
cement concrete pavement are set out in PORTLAND CEMENT
CONCRETE PAVEMENT.
Design Standards
2-3
2.4 Minimum pavement width:
Collector ArterialDesign Elements Local Cul-de-
sac Minor Major Minor Major
General
Lane width (single lane) (ft)11 11 11 12 12 12
Two-Way Left-Turn Lanes (TWLTL) (ft)N/A N/A 12 14 14 N/A
Object setback (ft)1.5 1.5 3.0 3.0 3.0 3.0
Urban (2-lane undivided roadway)
Roadway width with parking (one-side) (ft)29 26 31 N/A N/A N/A
Roadway width without parking (ft)26 26 26 29 31 N/A
Boulevard (2 or 4-lane divided roadway)
Roadway width without parking (one side) (ft)N/A N/A N/A 181 262 412
Raised median with left-turn lane (ft)N/A N/A N/A 18 20 30
1Based on one lane each direction
2Based on three lanes each direction
2.5 Minimum pavement radius at intersections: meet requirements of SUDAS Design
Manual.
2.6 Pavement gutter grades: minimum 0.60% and maximum 5.0% unless
otherwise approved by City.
2.7 Construct streets in accordance with details shown on Standard Drawings;
center pavement on right-of-way, unless otherwise permitted by City.
2.8 Minimum pavement diameter for culs-de-sac when approved by City: 80';
maximum length of street to serve culs-de-sac: 600' from end or radius of
intersecting perpendicular street to beginning of radius for cul-de-sac.
2.9 Provide depressed curb where sidewalks intersect streets and at driveways
constructed prior to pavement; construct 6" integral curb at other locations; mill
or saw cut and remove 6" curb at sidewalks and driveways constructed after
pavement. Sidewalks and crosswalks to meet requirements of Americans with
Disabilities Act (ADA) and Public Right of Way Access Guidelines (PROWAG).
2.10 Construct driveway approaches as shown on Standard Drawings; single driveway
approach width 10'; double driveway approach width 18'; triple driveway approach
width 22’ unless otherwise approved by City.
Design Standards
2-4
2.10.1 Construct commercial driveway and private street approaches in
accordance with SUDAS Standard Specifications Figure 7030.101 for
Concrete Driveway, Type A except minimum thickness is 8 inches.
2.11 Provide red nine dot object markers (OM4-2), 2 in each lane and one at centerline,
at dead ends of streets.
2.12 City to provide street name signs, speed limit signs, stop signs and no parking signs
as specified hereinafter; use symbol signs where appropriate. Subdivider to
reimburse City for cost of materials and installation of signs.
2.13 Surface and pavement replacement of existing streets:
2.13.1 Asphalt and seal coat streets: replace with asphalt or concrete as
specified.
2.13.2 Granular surfacing: replace with granular surfacing as specified.
2.13.3 Concrete curb and gutter: minimum pavement thickness as
specified.
2.14 Provide subdrain on all public street improvements unless specifically stated in
geotechnical report that subdrain is not needed. Provide storm sewer, sump pump
drain line, or subdrain on each side of street. Subdrain shall be 6” minimum
diameter.
2.15 Provide appropriate street network enhancements based upon projected traffic
volumes warranting additional travel lanes, turning lanes, or signalization.
2.15.1 Projected traffic volumes to be based upon development anticipated
within a 20 year planning period or as directed by the City. Traffic studies
to provide a 5 year and 20 year projection.
2.15.2 Costs associated with the street network enhancements and design will
be distributed between Subdivider and City based upon the Subdivider’s
contribution to the traffic volumes necessitating the enhancements.
2.16 Provide commercial drives with thickened approach between sidewalk and
edge of street pavement; minimum 8" thick; install expansion joint.
2.17 Subdivider responsible for installing pavement markings at improved street
intersections that include turning lanes as directed by City.
Design Standards
2-5
2.17.1 For purposes of these requirements the intersection will include all
areas within 250 feet of the intersection covering the required
improvements.
2.17.2 Subdivider to create a plan identifying all required markings at
intersection for City’s review.
2.17.3 Markings to be provided include centerline (2 solid or dashed yellow),
turn lane(s) (1 solid white), lane separation(s) (1 dashed white),
pedestrian crossings, (solid white longitudinal lines or bars parallel to
vehicle traffic flow), and directional arrows (solid white).
2.17.4 Markings to be comprised of Durable Paint.
3. SHARED USE PATHS
3.1 Design shared use paths including sidewalks and trails in accordance with
Americans with Disabilities Act (ADA) and Public Right of Way Access Guidelines
(PROWAG).
3.2 Curb ramps are required to be constructed with public improvements.
3.3 Provide minimum 1’ clear zone from edge of shared use paths to edge of hydrants,
poles, street signs, street lights and other obstacles.
3.4 Sidewalks:
3.4.1 Construct 5' wide sidewalks on both sides of street; or as directed by
City; place inside edge of sidewalk 1' outside property line or as directed
by City; conform to details shown on Standard Drawing Nos. 46 through
52 unless otherwise approved by the City.
3.4.2 Provide 1.5% +/- 0.5% cross slope.
3.5 Multi use trails:
3.5.1 Applicable to bike trails and multi-use trails including locations where
trail replaces standard sidewalks.
3.5.2 Construct on prepared subgrade as specified for driveway approaches
and sidewalks in EARTHWORK AND INCIDENTALS FOR PAVEMENT.
Design Standards
2-6
3.5.3 Construct 10’ wide portland cement concrete surfacing, 6” minimum
thickness with maximum 10’ transverse joint spacing; thicken trail to 7”
at driveways and street crossings. Provide 1.5% +/- 0.5% cross slope.
Construct as specified for driveway approach and sidewalk construction
in PORTLAND CEMENT CONCRETE PAVEMENT.
3.5.4 Provide 2’ wide graded shoulder each side; sod shoulders.
4. STORM SEWERS
4.1 Provide adequately sized storm sewers and sump pump drain lines. Design
storm sewers in accordance with SUDAS Design Manual, Subdivision
Ordinance of the City of Waukee, Iowa and the following standards.
4.2 Determine runoff using the Rational Formula, Q=CIA, where:
Q = maximum rate of runoff in cubic feet per second.
C = runoff coefficient; use coefficients consistent with type of surfaces in
drainage area.
I = average rainfall intensity in inches per hour for the period of rainfall of a given
frequency having a duration equal to the time of concentration.
A = drainage area in acres.
4.3 Use 10-year storm frequency and the Mean Frequency Distribution for Storm
Periods referenced under Paragraph 4.6 to determine intensity for storm sewer
system including intakes, structures, and pipes except as follows:
4.3.1 Use 100-year storm frequency for future development without regard for
stormwater detention flow reduction for culvert design under roadways
where roadway embankment blocks drainageway.
4.3.2 Use 100-year storm frequency for future development storm sewers
draining sump area in roadways and private lands unless drainage
easements are provided for all areas inundated during 100-year storm.
Design Standards
2-7
4.4 City will consider open channel storm water drainage with a 15" dia. double wall
polyethylene or reinforced concrete pipe subdrain when required pipe diameter is
greater than 48".
4.5 Storm sewers, intakes and other structures located within the street right-of-way
shall not discharge storm water during a less than or equal to 10-year storm
frequency storm event into normally dry drainage swales located on private
property unless otherwise permitted by City.
4.6 Mean Frequency Distribution for Storm Periods per the Iowa Stormwater
Management Manual (ISWMM).
4.7 Use minimum of 15-minute time of concentration for single family residential
area storm sewers; time of concentration for all other developments will be
reviewed by City.
4.8 Minimum pipe size: 15" except for intake cross-runs which shall be 12" minimum
diameter.
4.9 No bends or pipe deflections permitted on storm sewers unless otherwise
permitted by City.
4.10 Storm sewers that cross a street shall cross the street at no more than
15 degrees from perpendicular. Intent is to locate storm sewer and the intakes
on each side of the street within the same pavement panel.
4.11 Maximum velocity within pipe (1/2 full): 15’ per second. Pipe slopes that exceed
the following chart are not allowed:
Pipe Diameter Maximum Slope
(in.)(%)
12 10.9
15 8.1
18 6.3
21 5.1
24 4.3
30 3.2
36 2.5
42 2.0
48 1.7
54 1.4
Design Standards
2-8
4.12 Curb intakes:
4.12.1 Single, SUDAS Standard Specifications Type SW-501, SW-502, SW-503 or
SW-504.
4.12.2 Double, SUDAS Standard Specifications Type SW-505 or SW-506.
4.12.3 Provide SUDAS Standard Specifications Types SW-501 through SW-506
Curb Intakes when street grade is less than 5.00%; provide special intakes
when street grade is 5.00% or greater; consult with City Engineering
Department.
4.12.4 Location: up grade from intersections, sidewalk ramps and other
locations to meet specific topographic conditions; locate outside of
intersection radius.
4.12.4.1 Install at least one intake at the low point of the street grade.
4.12.4.2 Install intake no further than 500 feet from the street high
point.
4.12.4.3 Maximum spacing 400 feet regardless of gutter flow capacity.
4.12.5 Connecting pipes: size to accommodate flow into intake without
surcharging intake.
4.13 Area intakes:
4.13.1 Rectangular area intake: SW-511.
4.13.2 Circular area intakes: SW-512 with Type 4 flat grate.
4.13.3 Open sided area intake: SW-513.
4.13.4 Connecting pipes: size to accommodate flow into intake without
surcharging intake.
4.14 Manholes: SUDAS Standard Specifications Types SW-301, SW-401, SW-402, SW-
403, SW-404 or SW-405 modified as specified in STORM SEWERS AND
STRUCTURES or Standard Drawings Types Special Manhole or Shallow Manhole.
4.15 Cleanouts: SUDAS Standard Specifications Figure 4040.232 Types A-1 or B.
Design Standards
2-9
4.16 Manholes, intakes and structures required that are larger or deeper than those
shown in SUDAS Standard Specifications shall be designed and certified by a
licensed professional engineer in the State of Iowa.
4.17 Provide minimum 8” dia. perforated subdrain surrounded by pea gravel or
minimum 3’ wide concrete flume along rear lot lines or side yards where surface
flowage has 2% or less longitudinal slope; provide flat grate intakes in areas
where standing water is present after a 1” rainfall event after finished grading of
the site is completed; comply with material standards for subdrains.
4.17.1 Minimum slope of flume is 0.5% with ponding depth less than or equal
to 1”.
4.17.2 Subdrain to be tied into the public storm sewer system or outletted into
a detention facility designed to handle the 100 year storm event.
4.17.3 Cleanouts or intakes to be provided a maximum of every 150 feet from
the point of outlet and at deadends or as directed by the City.
Use cleanouts as specified hereinbefore except use slotted casting.
5. SANITARY SEWERS
5.1 Comply with design standards contained in the SUDAS Design Manual and in
CHAPTER 12 - IOWA STANDARDS FOR SEWER SYSTEMS from IOWA WASTEWATER
FACILITIES DESIGN STANDARDS published by the IDNR.
5.1.1 Size lateral sewers for residential areas to accommodate flow of
500 gallons per capita per day; volume of flow from areas other than
residential subject to approval by City. Size trunk sewers as directed by
the City.
5.2 Sanitary sewer service connections:
5.2.1 Minimum service pipe size for single family dwellings: 4" at minimum
slope of 1% or as specified in the adopted Plumbing
Code.
5.2.2 Minimum service pipe size for all other types of buildings: 6" at
minimum slope of 1% or as specified in the adopted Plumbing Code.
5.2.3 Shared sewer services from multiple buildings that are located on
separately owned lots are not allowed.
Design Standards
2-10
5.2.4 Cleanouts to be provided a maximum of every 150 feet or as directed
by the City. Use cleanouts as specified hereinbefore.
5.2.5 Label invert elevations at ends of sewer service stubs on construction
drawings.
5.3 Manholes: SUDAS Standard Specifications Types SW-301, SW-302,
SW-303, SW304, SW-305 or Standard Drawings Types Special Manhole or Shallow
Manhole. High point manholes are not allowed.
6. PUMPING STATIONS AND FORCE MAINS
6.1 Comply with design standards contained in the SUDAS Design Manual,
SANITARY SEWERS AND APPURTENANCES and in CHAPTER 13 - SEWAGE
PUMPING STATIONS from IOWA WASTEWATER FACILITIES DESIGN STANDARDS
published by the IDNR.
6.1.1 Pumping station capacity: size for maximum rate of flow from connected
sewers.
6.1.2 Provide at least 2 pumps of equal capacity, each capable of pumping
maximum flow; if more than 2 pumps, size pumps so that with largest
pump out of service remaining units have capacity for maximum sewage
flow.
6.1.3 Provide in-place standby power system; provide for automatic and
manual start-up, automatic load transfer and exercising of system under
load.
6.1.4 Size force main to maintain velocity of 2' per second at design
average flow and pass 3" solids.
6.1.5 Provide fence around pumping station site.
6.1.6 House major pump controls in heated above ground structure; provide
disconnect switches for pumps and all other electrical equipment; blend
pumping station superstructure with surrounding development
including landscaping.
6.1.7 Provide automatic pump alternators on multiple pump installation.
Design Standards
2-11
6.1.8 Provide stainless steel guide rails, cable holders, chain, bolts and
appurtenances inside wet well.
6.1.9 Provide magnetic flow meter on pump discharge pipe.
6.1.10 Provide water supply with yard hydrant.
7. WATER MAINS
7.1 Comply with design standards contained in the SUDAS Design Manual and in
RECOMMENDED STANDARDS FOR WATER WORKS (Ten States Standards) as
adopted by the IDNR.
7.1.1 Minimum water main size: Residential R-1 and Residential R-2 zoning: 8".
Water main size other than in residentially zoned areas subject to
approval by City.
7.1.2 Size major water mains as directed by the City.
7.1.3 Maximum dead end water main length: 300’.
7.2 Isolating valve spacing:
7.2.1 Residential R-1 and Residential R-2 zoning: 800' maximum and at street
intersections.
7.2.2 Other zoning: 400' maximum and at street intersections.
7.2.3 On all private lines at the connection with the City main.
7.3 Provide fire hydrant within 25 feet of each street intersection, measured from
an end of a street paving return. Equally space hydrants between
intersections, maximum hydrant spacing: 300', unless otherwise directed by
City.
7.3.1 Provide hydrant at entrance and at end of culs-de-sac when approved by
City; maximum spacing as specified hereinbefore.
7.4 Minimum water service size: 1".
Design Standards
2-12
7.4.1 Materials: use copper tubing for services 2" and smaller between main
and curb stop box and optional for services 2” and smaller between curb
stop box and building; use crosslinked polyethylene (PEXa) or
polyethylene (PE) pipe for services larger than 2" and optional for all
service sizes between curb stop box and building.
8. SUMP PUMP DRAIN LINES
8.1 Design sump drain lines in accordance with SUDAS Design Manual, Ordinances of
the City of Waukee, Iowa and the following standards:
8.2 Provide sump pump drain line for each building requiring foundation drainage.
8.2.1 Drain line standards herein are based on proper installation of a suitable,
commercially available automatic, thermal overload protected sump
pump capable of discharging 20 gpm at 20' TDH.
8.3 Outlet drain line in public collector pipe or storm sewer.
8.4 Collector pipes, receiving discharge of two or more sump pumps, may be used
upon written approval of installation details by City; minimum pipe size: 8".
8.5 Arrange sump pump drain lines and collector pipes to prevent freezing;
minimum depth of cover over buried pipe: 3'-6" or as approved by City.
8.6 Provide 4" pvc pipe with positive drainage for drain lines. Extend 4" drain line
from public storm sewer or collector pipe to minimum 1’ inside property line.
9. SUBDIVISION LOT GRADING AND MAINTENANCE
9.1 Construction sites covered by General Permit No. 2, issued by IDNR, are
required to fulfill the topsoil preservation requirement by either:
9.1.1 Stating that the requirements for on-site topsoil in SUDAS Standard
Specifications Section 2010 will be met OR using the General Permit
No. 2 language which states “The permittee shall minimize soil
compaction and, unless infeasible, preserve topsoil”.
9.2 Subdivider responsible for obtaining required borrow excavation and for disposal
of surplus excavated material.
9.3 Scarify slopes to a minimum depth of 3" prior to placement of topsoil.
Design Standards
2-13
9.4 Compact fill in areas intended to support utilities to not less than 95%
maximum density with moisture content between optimum moisture content
percentage and 4% above optimum unless otherwise directed by geotechnical
report; compact in horizontal layers not more than 8" in loose thickness.
9.5 Provide minimum 2% slope for buildable areas of residential lots and minimum
1.5% slope for buildable areas of commercial and industrial lots; no slope limit for
areas not disturbed by construction having slopes stabilized by existing vegetation
or rock outcropping.
9.6 Provide unobstructed 100-year flood flow paths through platted areas subject to
development to convey runoff from upstream areas of the watershed.
9.6.1 Compute runoff in accordance with Paragraph 4. STORM SEWERS.
9.6.2 Preserve or improve natural drainageways for use as flood flow paths.
9.6.3 Grade lots for drainage as shown on Standard Drawings or in accordance
with an agreed-upon plan with City.
9.6.4 All 100-year flood flow paths in rear and side yards shall be within a
surface water flowage easement. Provide subdrains, storm sewers and
flumes for low flow storm events in accordance with Paragraph 4.
STORM SEWERS.
9.7 Stabilize disturbed areas by sodding or seeding and mulching; maintain
undeveloped lots free of weeds.
9.8 Provide sediment and erosion control in areas subject to development in
accordance with IDNR General Permit No. 2.
9.8.1 Deposition of eroded soil on public rights-of-way, adjacent properties not
owned by subdivider and established streams, drainage ditches and
sewers is prohibited.
9.8.2 Remove sediment deposited by erosion, vehicle tire or otherwise on
public rights-of-way or adjacent properties by end of work day and
prior to a storm event.
Design Standards
2-14
10. STREET LIGHTS
10.1 All lighting within the Kettlestone corridor shown in Exhibit No. 2 following PART 11 –
KETTLESTONE STREET LIGHTS shall conform to the standards in the Kettlestone Design
Guidelines and PART 11 – KETTLESTONE STREET LIGHTS.
10.2 All lighting on private property including lighting for buildings, parking lots and private
streets shall conform to the City of Waukee Site Plan Ordinance.
10.3 All lighting on public streets shall conform to the design standards contained in the
SUDAS Design Manual and the following standards:
10.4 Poles:
10.4.1 All new street light poles and appurtenances installed within the clear zone
of any public street right-of-way shall be of a design to break-away when hit
by a vehicle. The break-away design shall conform to the definitions of the
U.S. Department of Transportation.
10.4.2 Street light poles shall be placed near all intersections, outside the sight
triangle, for proper lumination of the intersection.
10.4.3 Street light poles along minor collectors and local streets shall be spaced at a
maximum of 250 feet. Street light poles along major collectors and arterial
streets shall be spaced as approved by the City.
10.4.4 Locate poles in a straight line 3-feet to 6-feet behind the back of curb. Install
poles plumb.
10.5 Fixtures:
10.5.1 All fixtures shall be full cut-off (no sag lenz).
10.5.2 All fixtures shall be supported by MidAmerican Energy unless otherwise
approved by the City as a part of a development agreement related to
special development characteristics of a subdivision.
10.5.3 Mounting height shall be a minimum of 24.5 feet along minor collector and
local streets and a minimum of 30.5 feet along major collector and minor
and major arterial streets.
Design Standards
2-15
10.6 Provide photometric plan identifying all pole locations and project lighting levels with
foot-candle measurements at 10’ increments.
10.7 In cases where a homeowners association is created for a particular subdivision and
includes the responsibility of on-going maintenance of street light poles and fixtures, a
street lighting design utilizing unique poles and fixtures may be approved at the
discretion of the City.
11. TRAFFIC SIGNALS
11.1 All traffic signal installations must meet the criteria as set forth in the MUTCD for
minimum warrants to be met or be approved by the City following an engineering
study.
11.2 Meet SUDAS Specifications for traffic signals except as modified in PART 12 - TRAFFIC
SIGNALS.
11.3 Pedestrian crossings and ramp areas associated with a new traffic signal installation
shall comply with Americans with Disabilities Act (ADA) and Public Right of Way Access
Guidelines (PROWAG).
11.4 Traffic signal interconnection must be considered for any installation deemed
appropriate by the City. Interconnection methodologies and technologies must be
compatible with adjacent signal systems.
11.5 Placement of signal poles, cabinetry and pedestrian push buttons shall comply with
appropriate clear zone requirements for design speeds of the adjacent roadway as set
forth by AASHTO.
11.6 Traffic signal pole locations, traffic head placement and pedestrian crossings shall be
located to accommodate design vehicle turning movements throughout the
intersection.
11.7 All poles, footings and mast arms are to be designed to accommodate appropriate
structural loadings that are expected for this installation. Additional loadings shall be
considered for signage, aesthetic amenities, etc.
11.8 All components and appurtenances shall be made from materials to withstand the
elements and be protected by low maintenance coatings. These coatings shall meet
the standard colors for such installations as approved by the City.
Design Standards
2-16
11.9 All footings, cabinetry and handholes shall be placed to minimize the exposure to
drainage paths or conflict with other utility providers.
11.10 For any combination signal and street light installations, street light components shall
be as specified hereinbefore.
12. FIBER OPTIC LINES
12.1 Provide fiber optic lines on all minor collector streets and larger unless otherwise
directed.
12.2 Design fiber optic lines in accordance with the following standards:
12.2.1 Conduit: Comply with Iowa Department of Transportation Standard
Specifications Section 4189. 2” diameter, 30” depth.
12.2.2 Handholes: 30” x 48” x 24” precast polymer rated for 20,000 lb. load
(Tier 15). Handholes shall be installed at splicing, building access, and future
signal locations; 800’ maximum spacing.
13. STORMWATER MANAGEMENT
13.1 In 2024, the Iowa Legislature passed new regulations that limit how cities and counties
can enforce local stormwater post construction requirements. The City hereby
acknowledges the new Section 364.3(18) of the Code of Iowa relating to the
regulation of topsoil and storm water at construction sites and incorporates limits into
the Waukee Standard Specifications for Public Improvements for management of
stormwater.
13.2 The City hereby adopts the Iowa Stormwater Management Manual (ISWMM) and the
Waukee Standard Specifications for Public Improvements for management of
stormwater. The ISWMM is written as a guideline recommending certain techniques
and advising against others in order to accomplish goals related to managing water
volume and quality. Therefore, where the ISWMM states a design element or
technique is “essential” it is required by the City. Where ISWMM states a design
element or technique is “target” such design element or technique is desired by the
City and every effort shall be made to accomplish. Where ISWMM states a given
design element or technique is “advisory” this design element or technique shall not
be used within the City.
Design Standards
2-17
13.3 In cases where ISWMM does not speak to a stormwater issue, such as sizing or
installation of pipes, the City follows the Iowa Statewide Urban Design and
Specifications (SUDAS), the Waukee Standard Specifications for Public Improvements
or the Iowa River Restoration Toolbox streambank stabilization guides as applicable.
13.4 All development and redevelopment projects shall meet the requirements described
in Section 364.3(18) of the Code of Iowa and/or the requirements of the Unified
Sizing Criteria, as described within the Iowa Stormwater Management Manual
(ISWMM), as noted below, unless stormwater management has been designated for
an alternative off-site location or an existing downstream conveyance capacity
requires additional management to ensure no adverse impacts to existing facilities.
13.4.1 Water Quality Volume Standard: Practices or techniques shall be employed
that capture and treat runoff from a 1.25” rainfall event, as further defined
within the ISWMM and as required per the current City MS4 permit.
13.4.2 Channel Protection Standard: Practices or techniques shall be employed
that provide extended detention of the 1-year, 24-hour storm event – with
release rates established as per methods defined within the ISWMM to
provide a minimum drawdown period of 24 hours.
13.4.3 Detention Standard: Practices and techniques shall be employed that limit
the allowable peak release rates that are anticipated to occur post-
development during the 5-, 10-, 25-, 50-, and 100-year, 24-hour storm events
to a level no greater than those expected to occur from the pre-developed
(existing condition) 5-year storm event. (e.g. the post-development release
rate from a 5-year storm event will be no greater than the existing condition
release rate from a 5-year storm event as well as the post-development
release rate from a 100-year storm event will be no greater than the existing
condition release rate from a 5-year storm event).
13.4.3.1 Alternative Detention Standard: Practices and techniques shall
be employed that limit allowable peak release rates that are
anticipated to occur post-development during the 2-, 5-, 10-,
25-, 50-, and 100-year, 24-hour storm events to levels no
greater than those expected to occur from natural conditions
a given site from a similar storm event (e.g. the post-
development release rate from a 5-year storm event will be
no greater than the natural release rate from a 5-year storm
event).
Design Standards
2-18
13.4.3.1.1 Natural conditions are defined as meadow in good condition,
with times of concentrations calculated and Curve Numbers
selected based on those natural surface conditions and
drainage patterns. Curve Numbers shall be selected based on
the Hydrologic Soil Group for site soils, but the weighted
Curve Number used to determine allowable release rates for
the site to be served by the detention practice shall not
exceed a Curve Number of 58 unless demonstrated by a
geotechnical report that a higher curve number is warranted,
however, in no case shall the curve number exceed 71.
13.4.4 Detention of events larger than the 100-year storm event are not required,
however, the design of auxiliary spillways should safely convey flows from
the 500-year, 24-hour storm event.
13.4.5 Detention of off-site stormwater runoff is not required, however, the design
of the outlet structure and auxiliary spillways shall safely convey off-site
flows through the proposed development with no adverse impacts to
adjacent properties.
13.4.6 Surface water flowage easements shall be provided as needed to reserve a
safe and clear path for the width of expected concentrated flows for the
100-year storm event. Detention events larger than the 100-year can occur
and surface water conveyance for those events should be considered.
13.4.7 Detention basins shall be sized using the TR-55 Method or approved
equivalent.
13.4.8 Soil Group information shall be determined from current County Soil maps
as available through the NRCS. If a Soil Group type has not been identified
for a given location, the natural condition shall be assumed to be
Hydrologic Soil Group B and the post-developed condition shall be assumed
to be Hydrologic Soil Group C, unless geotechnical studies are provided for
City review that provide evidence for use of another Soil Group for analysis.
13.4.9 Restrict discharge rate from detention basins using a correctly sized
aluminum or stainless-steel weir plate or orifice plate securely fastened with
stainless steel hardware. Fasten orifice plate inside downstream pipe or
structure. Pipe downstream from weir plate or orifice plate to have
adequate capacity to accommodate a minimum of a 10-year storm
frequency event. The minimum orifice size to be used is 3” diameter
regardless of the calculated allowable release rate for a given storm event.
Design Standards
2-19
13.4.10 Meet ISWMM requirements for the design of best management practices;
including, but not limited to: sizing, slopes, embankment widths, freeboard,
high water depths and auxiliary spillway.
13.5 Applicability:
13.5.1 New Development: Any new development of land adding more than
10,000 square feet of new impervious surface shall provide stormwater
management as outlined above. This threshold is a cumulative amount of
new square footage and may be reached over time in increments. At such
time that a development site exceeds 10,000 cumulative square feet of
new impervious surface the site will be required to come into compliance
with this chapter. This includes linear roadway projects that are a part of a
new development.
13.5.2 Redevelopment: Any redevelopment of land adding more than 10,000
square feet of new impervious surface but disturbing less than 50% of the
site shall provide stormwater management at the Water Quality Volume
standard and shall be asked to also meet the Channel Protection standard
or demonstrate why doing so is infeasible. This standard is in addition to
remaining in compliance with detention proposed for larger storm events
in any previously approved stormwater management plan. This threshold
is a cumulative amount of new square footage and disturbance and may be
reached over time in increments. At such time that a site exceeds 10,000
cumulative square feet of new impervious surface, the entire site will be
required to come into compliance with this section. Any redevelopment
disturbing 50% or more of a site shall be required to meet the same
stormwater management standards as a new development per section
13.5.1. At such time that 50% or more of a site is cumulatively disturbed,
the entire site will be required to come into compliance with section
13.5.1.
Design Standards
2-20
13.5.3 New Development or Redevelopment with Existing Regional or Onsite
Detention: Any new development or redevelopment adding more than
10,000 square feet of new impervious surface or any redevelopment
disturbing 50% or more of a site with existing regional or onsite detention
shall provide stormwater management at the Water Quality Volume
standard and shall be asked to also meet the Channel Protection standard
in addition to the regional or onsite detention provided or demonstrate
why doing so is infeasible. Existing detention facilities will not be required
to be increased in size and additional detention facilities will not be
required to be constructed to meet these standards. These standards are
in addition to remaining in compliance with the regional or onsite
detention proposed for larger storm events in the previously approved
regional detention stormwater management plan. This threshold is a
cumulative amount of new square footage and disturbance and may be
reached over time in increments. At such time that a development site
exceeds 10,000 cumulative square feet of new impervious surface or 50%
or more of a site is cumulatively disturbed, the entire site will be required
to come into compliance with this section.
13.5.4 City Projects: Stormwater management standards shall apply to all City
projects including new City parks and buildings.
13.5.5 Exemptions: The following activities shall be exempted from meeting the
stormwater management standards of this ordinance:
13.5.5.1 New development adding less than 10,000 square feet of new
impervious surface.
13.5.5.2 Redevelopment adding less than 10,000 square feet of new
impervious surface and less than 50% site disturbance and if in
compliance with a previously approved stormwater
management plan.
13.5.5.3 Removal and replacement of impervious surface exactly
matching location and area.
13.5.5.4 Logging or agricultural activity that is consistent with an
approved soil conservation plan or timber management plan
prepared or approved by the appropriate agency, as
applicable.
13.5.5.5 Additions or modifications to single family structures.
Design Standards
2-21
13.5.5.6 Repairs to any stormwater management BMP deemed
necessary by the city.
13.5.5.7 Linear road construction projects where stormwater detention
is impractical. This does not include linear roadway projects
that are a part of a new development.
13.6 All development or redevelopment projects shall begin with a pre-application
meeting with the City Development Services and Public Works staff. At said
meeting, City staff will discuss the proposed project with the developer or developer
representatives and will review preliminary information regarding stormwater
management as indicated on the City’s Stormwater Management Plan Review
Checklist.
13.7 The City will maintain a checklist of required plans and studies and timing for
submittal which may include, but not be limited to:
13.7.1 Post-Construction Stormwater Management Plan consistent with City
requirements outlined in the City Post-Construction Stormwater
Management Plan Review Checklist in section 13.12 to follow.
13.7.2 Natural Resources Inventory as outlined in section 13.12.2.1.8 to follow.
13.7.3 Soil Management Plan as outlined in section 13.12.2.2 to follow.
13.8 The site shall be designed using Better Site Design principals. Better Site Design
involves techniques applied early in the process to preserve natural areas, reduce
impervious cover, distribute runoff and use pervious areas to more effectively treat
stormwater runoff. Site design should address open space protection, impervious
cover minimization, and runoff distribution and minimization, and runoff utilization
through considerations such as:
13.8.1 Open space protection and restoration:
13.8.1.1 Conservation of existing natural areas (upland and wetland).
13.8.1.2 Reforestation.
13.8.1.3 Re-establishment of prairies.
13.8.1.4 Restoration of wetlands.
Design Standards
2-22
13.8.1.5 Establishment or protection of stream, shoreline and wetland
buffers.
13.8.1.6 Re-establishment of native vegetation into the landscape.
13.8.2 Reduction of impervious cover:
13.8.2.1 Reduce new impervious through redevelopment of existing
sites and use of existing roadways, trails etc.
13.8.2.2 Minimize street width, parking space size, driveway length,
sidewalk width.
13.8.2.3 Reduce impervious surface footprint (e.g. two-story buildings,
parking ramp).
13.8.3 Distribution and minimization of runoff:
13.8.3.1 Utilize vegetated areas for stormwater treatment (e.g. parking
lot islands, vegetated areas along property boundaries, front
and rear yards, building landscaping).
13.8.3.2 Direct impervious surface runoff to vegetated areas or to
designed treatment areas (roofs, parking, driveways drain to
pervious areas, not directly to storm sewer or other
conveyances).
13.8.3.3 Encourage infiltration and soil storage of runoff through grass
channels, soil compost amendment, vegetated swales,
raingardens, etc.
13.8.3.4 Plant vegetation that does not require irrigation beyond
natural rainfall and runoff from the site.
13.8.4 Runoff utilization:
13.8.4.1 Capture and store runoff for irrigation in areas where
irrigation is necessary.
Design Standards
2-23
13.9 It is intended that this section is construed to be consistent with City Ordinance
Chapters 165-169 Zoning Regulations, Chapters 175-179 Subdivision Regulations,
Chapter 102 Construction Site Erosion and Sediment Control (COSESCO), Chapter
103 Post Construction Storm Water Management, Chapter 101 Illicit Discharge to
Storm Sewer System, Chapter 170 Floodplain Management, as well as any other
applicable local, state or federal regulations.
13.10 The requirements of this chapter should be considered minimum requirements, and
where any provision of this chapter imposes restrictions different from those
imposed by any other chapter, rule or regulation, or other provision of law,
whichever provisions are more restrictive shall take precedence.
13.11 The purpose of a Stormwater Management Plan is to identify in detail how
stormwater runoff will be managed from a site including specifications on what
stormwater management techniques and facilities will be used and where they will
be located. It is the policy of the City that stormwater management is planned and
designed early in the development process so that developments are built in
harmony with nature versus forcing stormwater management to fit a development
site design. Therefore, certain items will be discussed at the time of a pre-
application meeting with City staff so that they can be considered before detailed
engineering site design has occurred.
13.11.1 The following are items to be discussed or submitted at the pre-application
phase. Items in the pre-application phase need not be final reports or
engineering studies nor is that the intent. A designer should consider these
items at the start of the design process and should discuss them with City
staff. Examples of the items in this section are as follows:
13.11.1.1 Natural Resources Inventory – written and/or maps.
13.11.1.2 Soil Management Plan.
13.11.1.3 Map(s) showing existing and proposed conditions.
13.11.1.4 Be prepared to discuss Better Site Design Principles being
incorporated into the site plan.
13.11.2 Items to be submitted with site plan/plat/grading plan submittals:
13.11.2.1 Report and Narrative Information.
Design Standards
2-24
13.11.2.2 Cover sheet including project name, location, engineer and
developer contact information.
13.11.2.3 Table of contents indicating sections and page numbers.
13.11.2.4 Professional certification from Iowa Licensed Engineer.
13.11.2.5 Summary of any previous studies or master plans.
13.11.2.6 Natural Conditions and runoff analysis summary.
13.11.2.7 Description and explanation of storm water analysis (e.g.
computer-generated hydrographs).
13.11.2.8 Summary of stormwater management plan detailing
compliance with design standards.
13.11.2.9 Natural Resources Inventory:
13.11.2.9.1 Soil conditions (karst, hydric, etc.).
13.11.2.9.2 Forest cover.
13.11.2.9.3 Topography.
13.11.2.9.4 Wetlands/Prairie Potholes.
13.11.2.9.5 Streams and floodplains.
13.11.2.9.6 Review of FEMA FIRM maps.
13.11.2.9.7 Other Native Vegetative Areas.
13.11.2.9.8 Environmentally Sensitive Areas.
13.11.2.9.9 Archeological and/or cultural resources.
13.11.2.9.10 Wildlife areas
13.11.2.9.11 Wellhead protection and drinking water supply
management areas.
Design Standards
2-25
13.11.2.9.12 Areas of existing stormwater storage.
13.11.2.10 Soil Management Plan. The intent of a Soil Management Plan
is simply to demonstrate what is to be done with soil on site.
Where will it be stockpiled and eventually spread and used on
site. Depending on intended use of soil to meet stormwater
requirements, the following items may be applicable:
13.11.2.10.1 Review NRCS or USGS soils maps or geotechnical
reports.
13.11.2.10.2 Avoid disturbance of higher quality soils to
maximum extent possible.
13.11.2.10.3 Avoid disturbance activities under the drip line
of any trees intended to be preserved.
13.11.2.10.4 Identify where topsoil is to be stripped,
stockpiled and replaced.
13.11.2.10.5 Identify locations where Soil Quality Restoration
techniques are proposed to be used to manage
water quality treatment requirements.
13.11.2.11 Summary of how Better Site Design Principles, if applicable,
have been incorporated into site design.
13.11.2.12 Geotechnical report.
13.11.2.13 US Army Corps of Engineers Section 404 Permit, if applicable.
13.11.2.14 Local or DNR Floodplain Development Permit, if applicable.
13.11.3 Calculations – for each calculation, provide exhibits demonstrating how
calculated and assumptions made:
13.11.3.1 Runoff coefficient and/or curve number calculations
(allowable release rates).
13.11.3.2 Time of concentration calculations.
13.11.3.3 Water volume infiltrated.
Design Standards
2-26
13.11.3.4 Water Quality Volume calculations required and proposed.
13.11.3.5 Channel Protection Volume calculations required and
proposed (if applicable).
13.11.3.6 Large storm (100 year) calculations detention volume required
and proposed.
13.11.3.7 Storm system capacity calculations (outlet control, pipe
capacity, swale/ditch capacity, erosion control and emergency
dissipation measures, downstream capacity calculations).
13.11.3.8 Runoff and routing hydrographs.
13.11.3.9 Floodplain modeling if applicable and base flood elevations.
13.12 Project Summary:
13.12.1 Identify method(s) and location of proposed post-construction
stormwater management BMPs.
13.12.2 Map indicating drainage area of each post-construction BMP.
13.12.3 Discuss how proposed management methods comply with requirements.
13.12.4 Post-construction BMP maintenance plan.
13.12.5 Operation and maintenance of post-construction BMPs.
13.12.6 Identify post development stormwater impacts to adjacent properties and
mitigation measures for any potential impacts.
13.12.7 Offsite / downstream conditions and runoff analysis if applicable.
13.13 Maps:
13.13.1 Existing drainage contour map illustrating and labeling pre-development
drainage patterns, basins, swales/ditches, creeks, river, streams, etc. and
any other relevant on-site or off-site information.
Design Standards
2-27
13.13.2 Proposed drainage contour map illustrating and labeling post
development drainage patterns, areas for which storm water
management will be provided, conveyance methods (pipes, swales, etc.)
and any other relevant on-site or off-site information.
13.13.3 Location of existing and proposed buildings, roads, parking areas, utilities
and stormwater management facilities and erosion/sediment control,
easements, ROWs.
13.13.4 Preliminary stormwater storage estimation.
13.13.5 Proposed land use.
13.13.6 Existing and proposed drainage patterns.
13.13.7 Limits of clearing and grading.
13.13.8 Map(s) identifying where stormwater runoff enters and leaves the project
limits.
13.13.9 Watershed area delineations.
13.13.10 Floodplain delineations.
13.13.11 Natural Resources Inventory Map.
3-1
PART 3 – EARTHWORK AND INCIDENTALS FOR PAVEMENT
INDEX
1. GENERAL 4. SUBGRADE PREPARATION 2. EXCAVATION 5. SUBGRADE TREATMENTS 3. EMBANKMENT 6. FINISH GRADING 7. STREET SIGNS
1. GENERAL
1.1 This part of the specifications includes earthwork and incidentals to complete
grading for portland cement concrete pavement, driveway approaches and shared
use paths.
1.2 Reference to percent maximum density shall mean a soil density not less than the
stated percent of maximum density of optimum moisture content for soils as
determined by ASTM D698 Moisture-Density Relations of Soils using 5.5 lb.
Rammer and 12" Drop. (Standard Proctor Method).
1.3 Do work in accordance with best present-day installation and construction
practices.
2. EXCAVATION
2.1 Excavate to grade required for street construction.
2.2 Provide suitable approaches from intersecting streets and driveways.
2.3 Subdivider responsible for obtaining required borrow excavation.
2.4 Subdivider responsible for disposal of surplus excavated material.
2.5 Provide temporary drainage facilities to prevent damage to public or private
interests when necessary to interrupt natural drainage or flow of artificial drains.
2.6 Restore original drains as soon as work will permit.
2.7 Subdivider liable for damage resulting from neglect to provide for interrupted
natural or artificial drainage.
2.8 Do not damage pavement or disturb subgrade beneath existing pavement.
Earthwork and Incidentals for Pavement
3-2
3. EMBANKMENT
3.1 Remove all ground cover and topsoil from area.
3.2 Construct embankment in horizontal layers not more than 8" in loose thickness.
3.3 Deposit each layer over full width of embankment as separate operation.
3.4 After layer is deposited, smooth to uniform depth by means of suitable
grader or bulldozer.
3.5 Compact layer by rolling with tamping type roller filled with water until full weight
of roller is supported by tamping feet, but with not less than one pass per inch of
loose thickness of layer.
3.5.1 Roller will be considered to be supported entirely on its tamping feet
when feet do not penetrate more than 3" into material being
compacted.
3.6 If soil is wet so that it will not sufficiently compact by one passage of roller per inch
of loose thickness, provide one discing per 2" of loose thickness.
3.6.1 Cut and stir full depth of layer.
3.6.2 Allow interval of not longer than 2 hrs. between successive discings.
3.6.3 After discing is completed, compact layer by rolling, as specified.
3.7 If soil is dry so that it will not satisfactorily compact by rolling, moisten material
before compaction; manipulate material to secure proper distribution of moisture
before compaction.
3.8 Whenever operations are suspended during period when rain is likely to occur,
smooth and compact surface to shed water readily.
3.9 Other compacting equipment and construction methods may be used provided
results obtained produce compacted lifts of soil having not less than 95% maximum
density and moisture content between optimum moisture content percentage and
4% above optimum.
3.9.1 Test for density and moisture content; one test per lift per 150 feet or as
directed by City Engineering Department.
Earthwork and Incidentals for Pavement
3-3
4. SUBGRADE PREPARATION
4.1 Provide uniform composition at least 12" below top of subgrade for full width of
subgrade of pavement plus 2' on each side; roll and scarify materials, mix and re-
compact, or otherwise treat to produce a uniform condition; remove top 6" and
scarify, mix and re-compact the next 6” of subgrade; replace, mix and compact the
top 6” of subgrade; proof roll finished subgrade with fully loaded tandem axle
dump truck with maximum tandem axle gross weight of 34,000 pounds
immediately prior to paving; correct soft areas visible during proof rolling. Provide
additional proof rolling after a rainfall event prior to paving.
4.2 Remove and dispose of stones over 4" in size from loosened portion of subgrade.
4.3 Construct subgrade with uniform density for a width equal to that of proposed
pavement plus 2' on each side; density is to be not less than 95% maximum density
and moisture content between optimum moisture content percentage and 4%
above optimum.
4.4 In areas where roller cannot compact; place 6" of Class B crushed limestone,
IDOT 4120.05; compact to 95% maximum density with vibrator tamper.
4.5 Construct subgrade such that after rolling, surface will be at required grade
and cross section.
4.5.1 Shape edges of subgrade to keep flowing water away from
pavement.
4.6 Fill depressions that develop during rolling with suitable material; continue
rolling until subgrade is uniformly firm, properly shaped and true to grade
and cross section.
4.6.1 Maintain until pavement is placed.
4.6.2 Remove materials other than sand which will not compact readily
under roller; replace with materials which will compact readily;
again roll that portion of subgrade.
4.7 If ruts or other objectionable irregularities form in subgrade during construction,
reshape and re-roll subgrade before placing pavement or subbase; fill ruts or
other depressions with material similar to other subgrade material.
Earthwork and Incidentals for Pavement
3-4
4.8 Draw steel shod template, over subgrade prior to depositing concrete; check and
trim subgrade to required grade and cross section.
4.8.1 Use of template may be waived if subgrade has been shaped satisfactorily
by suitable electronically controlled subgrade trimming machine.
4.8.2 In irregular sections where use of template or subgrade trimming
machine is impractical, check subgrade by most accurate practical
method.
4.9 Subgrade preparation for driveway approaches and shared use paths:
4.9.1 Excavate to provide finish grade approved by City.
4.9.2 Excavate subgrade to a point 2" below proposed grade of bottom of slab;
backfill with 2" of compacted crushed stone, depending on condition of
subgrade.
4.9.3 For driveway approaches and shared use paths constructed in fill: backfill
with selected material; compact in not more than 6" lifts to a density of
95%; fill top 2" with compacted crushed stone, depending on condition of
subgrade.
4.10 Test subgrade for density and moisture content; one test per lift per 150 feet of
street to be paved or as directed by City Engineering Department.
5. SUBGRADE TREATMENTS
5.1 Use only to correct subgrade condition where specified density cannot be
obtained by other methods.
5.2 Granular subbase for concrete pavement: use uniform mixture of granular
material, uniformly moistened, placed on prepared subgrade; use also as
suitable material to fill depressions in subgrade.
5.2.1 Use crusher run limestone, crusher run sandstone, limestone
screenings, soil-aggregate, pit run gravel, or a mixture of sand or pit run
gravel with crushed limestone or limestone screenings.
5.2.2 Use mixture uniform in composition with no visible
segregation of constituent materials.
Earthwork and Incidentals for Pavement
3-5
5.2.3 If soil is added to material, pulverize soil particles so no particles are
retained on 3/4" sieve.
5.2.4 If constituent materials are proportioned, blend to homogeneous mixture
before placing on subgrade.
5.2.5 Not more than 5% of finished mixture retained on sieve having square
openings equal to one-third nominal thickness of subbase and not more
than 25% pass No. 200 sieve.
5.2.6 Material containing soil added in process of producing aggregate or
added separately: solid volume ratio not less than 0.80; material
without added soil: solid volume ratio not less than 0.75.
5.3 Equipment requirements for placing granular subbase:
5.3.1 Compaction equipment: IDOT 2001.05.
5.3.2 Prewetting equipment: IDOT 2001.08A.
5.3.3 Equipment for applying water: IDOT 2001.09.
5.3.4 Weighing equipment: IDOT 2001.07.
5.4 Lime subgrade treatment for concrete pavement:
5.4.1 Provide lime, 20 lbs. per SY, in top 6" of subgrade.
5.4.2 Mix until uniform consistency is obtained; add water as required for
optimum moisture content and compact to specified density.
5.4.3 Lime: use hydrated lime: ASTM C207, Type N.
5.5 Geogrid material: biaxial material of 98% minimum polypropylene and regular grid
structure conforming to ASTM D4101 Group 1, Class 1, Grade 2 with .05%
minimum carbon black per ASTM 4218; Tensar Geogrid BX1100, or equal.
5.5.1 Aperture size suitable for mechanical interlock of base and geogrid;
minimum of 70% open area; maximum openings: 1” (longitudinally along
roll) and 1.3” (across roll).
5.5.2 Tensile modulus of 14,000 lbs./ft.; flexural rigidity of 250,000 mg-cm.
Earthwork and Incidentals for Pavement
3-6
5.5.3 Nominal rib thickness of 0.03”; nominal junction thickness of 0.11” per
ASTM D1777.
5.5.4 Resistant to damage by all forms of biological and chemical degradation
caused by subgrade or subbase environment.
5.5.5 Avoid damage to subgrade; roll geogrid material over prepared subgrade;
extend geogrid material minimum 1; beyond back of curb line; cut to
conform to fixtures; pin overlaps to provide anchorage.
5.5.6 Overlap geogrid material joints minimum 2’ both transverse and
longitudinal; overlap on 31’ wide street pavement may be reduced to 1.5’
to accommodate manufacturer’s standard geogrid material widths in
longitudinal lap joints only.
5.5.7 Overlap geogrid material in direction granular base will be spread.
5.5.8 Anchor geogrid material to subgrade as recommended by manufacturer.
5.6 Cement and fly ash subgrade treatment for concrete pavement:
5.6.1 Geotechnical engineer to evaluate the soil moisture and select a
percentage of cement or fly ash to be incorporated. Provide City with letter
of recommendation identifying the specific characteristics outlined in this
section and signed by a licensed geotechnical engineer in Iowa.
5.6.2 Treat the upper 12” of soil subgrade in 1 lift utilizing a reclaimer for uniform
incorporation of cement or fly ash.
5.6.3 Place subgrade treatment the width of the pavement, plus 2 feet on each
side. Use spreader for uniform spreading of cement or fly ash.
5.6.4 Compact treated soil with sheepsfoot-type roller and vibratory roller to
percent compaction as recommended by geotechnical engineer.
5.6.5 Proof roll treated areas with fully loaded tandem axle dump truck with
maximum axle gross weight of 34,000 pounds prior to paving. Correct any
soft areas visible during proof rolling prior to paving.
5.7 Other subgrade treatments may be used provided they are approved by a
geotechnical engineer licensed in Iowa.
Earthwork and Incidentals for Pavement
3-7
6. FINISH GRADING
6.1 Finish grade and shape area from property line to back of curb to prevent water
from entering subgrade.
6.2 Compact backfill behind curb to 95% maximum density.
6.3 Grade to drain to street; slope from property line to sidewalk or trail 4%; sidewalk
and trail slope: 1.5% +/- 0.5%; slope from sidewalk or trail to back of curb 4%.
6.3.1 Maximum slope at driveways: meet requirements of the Driveway Design
Criteria of the SUDAS Design Manual.
6.3.2 Use above slope limitation unless exceptions are allowed by City.
6.4 Remove an adequate amount of topsoil from the upper 12” of existing on-site
topsoil to allow finish grading with a finished grade of 8” of salvaged or amended
topsoil. The topsoil may be moved directly to an area where it is to be used, or
may be stockpiled for future use.
6.4.1 On-site topsoil material is material excavated from the top 12” of the site.
Use of on-site topsoil material is subject to the Engineer’s approval.
6.5 Degree of finish for grading slopes: that ordinarily obtainable through use of
suitable power equipment operated by skilled workmen on favorable ground
conditions.
6.6 Keep equipment off parkings after finishing.
7. STREET SIGNS
7.1 Furnish and install street name and traffic control signs and accessories in
accordance with Iowa Manual on Uniform Traffic Control Devices and as directed
by City; use symbol signs where appropriate; install signs prior to opening street
for public use.
7.1.1 Manufacturer: Iowa State Industries, Lyle Signs, Inc., Newman
Signs, or approved equal.
7.2 Street name signs and accessories:
7.2.1 Provide 1 street sign assembly at each intersection; locate where
directed by City.
Earthwork and Incidentals for Pavement
3-8
7.2.2 Street nameplates: high intensity reflective sheeting with white
letters on green background; white border.
7.2.3 Provide two-way, four-way or six-way brackets, as required.
7.3 Furnish and install NO PARKING signs and accessories; Lyle Signs, Inc., or
approved equal.
7.3.1 Provide signs to prohibit parking on sides of streets as directed by City;
place signs in parking, facing on-coming traffic; locate first sign in block
approximately 100' from intersection; 200' maximum spacing on signs in
remainder of block.
7.3.2 Sign plate: Lyle Signs, Inc., or approved equal, high intensity
reflective sheeting; urban: 12"x12" size; rural: 24"x24" size;
legend: "P" in black letters, symbol in red, on white
background; black border.
7.3.3 Install sign on post with bottom of sign approximately 7'-0" above
ground; use 5/16" cadmium plated bolts and lock washers.
7.4 Furnish and install DEAD END signs and accessories on streets which terminate in
dead end or cul-de-sac; Lyle Signs, Inc., or approved equal.
7.4.1 Locate sign where directed by City.
7.4.2 Sign plate: Lyle Signs, Inc., or approved equal, high intensity
reflective sheeting; 30" x 30" size; legend: "DEAD END" in black
letters on yellow background; black border.
7.4.3 Install sign on post with bottom of sign approximately 7'-0" above
grade; use 5/16" cadmium plated bolts and lock washers.
7.5 Furnish and install speed limit signs and accessories: Lyle Signs, Inc., or approved
equal.
7.5.1 Provide signs of speed limits as directed by City; place signs in parking,
facing on-coming traffic; locate signs as directed by City.
Earthwork and Incidentals for Pavement
3-9
7.5.2 Sign plate: Lyle Signs, Inc., or approved equal, high intensity reflective
sheeting; 24" x 30" size; typical legend: SPEED LIMIT 25 in black
letters and numerals on white background; black border; speed limit
designation as determined by City.
7.5.3 Install sign on post with bottom of sign approximately 7'-0" above
grade; use 5/16" cadmium plated bolts and lock washers.
7.6 Furnish and install STOP signs and accessories; Lyle Signs, Inc., or approved equal.
7.6.1 Locate signs at intersections where directed by City.
7.6.2 Sign plate: Lyle Signs, Inc., or approved equal, high intensity reflective
sheeting; 24" octagon on local service streets and 30" octagon on
arterial streets; legend: white letters and borders on red background.
7.6.3 Install sign on post with bottom of sign approximately 7'-0" above grade;
use 5/16" cadmium plated bolt and lock washers.
7.7 Furnish and install post mounted object markers on streets that dead end at
platted subdivision boundaries and are intended for extension in future.
7.7.1 Sign: red nine dot object marker meeting requirements of the Manual
on Uniform Traffic Control Devices (MUTCD) for Type 4 object marker
OM4-2.
7.7.2 Provide five object markers at each dead end; two in each lane and one at
centerline.
7.7.3 Install object marker on post with bottom of marker a minimum of
4’-0” above grade; use 5/16” cadmium plated bolts and lock washers.
7.8 Posts:
7.8.1 2” square galvanized steel; minimum 12 gauge; galvanized inside and
outside; conform to ASTM A653, G90, structural quality Grade 50, Class 1;
Telespar, or equal.
7.8.2 Provide with holes 7/16 inch diameter at one inch centers on all four
sides down the entire length of the post. Holes shall be on centerline of
each side in true alignment and opposite each other directly and
diagonally.
Earthwork and Incidentals for Pavement
3-10
7.8.3 Set in 3’ x 2.25” square galvanized base post; minimum 12 gauge; anchor
base post 3’ below finished grade, or as directed by City.
7.9 Furnish and install other traffic control signs as determined by City.
4-1
PART 4 – PIPE EXCAVATION AND BACKFILL
INDEX
1.
GENERAL 6. TUNNELING
2. EXCAVATION FOR STRUCTURES 7. DEWATERING
3. TRENCH EXCAVATION 8. BACKFILL FOR STRUCTURES
4. ROCK AND RUBBLE EXCAVATION 9. TRENCH BACKFILL
5. SHEETING, SHORING AND BRACING 10. CONCRETE ENCASEMENT
1. GENERAL
1.1 This part of the specifications includes excavation and backfill for storm sewers,
sanitary sewers, water mains, subdrains, sump pump drain lines and structures.
1.1.1 Excludes excavation for streets, driveway approaches and shared use
paths.
1.2 Excavate in open cut except when tunneling is required or allowed by City; tunnel
under railroads, highways, shared use paths, driveways, concrete pavement and
curb and gutter except where permission to open cut is granted by City.
1.3 Protect all existing concrete pavement, shared use paths, driveways and curb and
gutter in public right-of-way from damage during construction; if damage occurs,
restore at no expense to City or private property owners. Restore in accordance
with SURFACE RESTORATION AND PAVEMENT REPLACEMENT.
1.4 Reference to percent maximum density shall mean a soil density not less than the
stated percent of maximum density for soil as determined by ASTM D698
Moisture-Density Relations of Soils using 5.5-lb. Rammer and 12" Drop. (Standard
Proctor Method).
2. EXCAVATION FOR STRUCTURES
2.1 Includes excavation for manholes, intakes and other appurtenances.
2.2 Excavate as required to firm, undisturbed soil; if excavation is carried below
bottom of foundation, fill with stabilizing material or Class B concrete.
2.3 Provide sheeting, shoring and bracing where required to hold walls of excavation,
to protect existing structures or utilities or to provide safety for workmen.
Pipe Excavation and Backfill
4-2
3. TRENCH EXCAVATION
3.1 Keep width of trench as narrow as possible and still provide adequate
room for backfill and jointing.
3.2 Keep sides of trench as nearly vertical as practicable; maintain vertical walls of
excavation below top of pipe.
3.3 Maximum width of trench at top of pipe: as shown on Standard Drawings;
water main and sanitary force main trench: outside diameter of pipe plus 12"
on each side.
3.4 Bottom of trench for gravity sanitary sewers and services:
3.4.1 Bedding for iron gravity sewer in open cut: use Class C - Granular
Type I. See Standard Drawings.
3.4.2 Bedding for pvc, pvc truss and pvc corrugated
sanitary sewer pipe: lay pipe on 6” deep pipe bedding material;
fill around and over pipe to a minimum depth of 12” above the
top of pipe bell with pipe bedding material; compact all bedding
material by vibration. See Standard Drawings for Standard PVC
Pipe Bedding – Granular Encasements.
3.4.3 Excavate full depth by machine; place pipe bedding in bottom of trench.
3.4.4 Pipe bedding: sharp, 1” clean crushed stone; comply with
following gradation, dependent upon pipe diameter:
Sieve Size % Passing
1” 100
3/4" 80-95
1/2" 50-60
3/8" 20-40
No. 4 0-5
3.4.4.1 City may authorize change in gradation subject to materials
available locally at time of construction.
3.4.5 Compact pipe bedding by rodding or slicing with shovel.
Pipe Excavation and Backfill
4-3
3.4.6 Hand shape bell holes at each pipe joint in pipe bedding; provide access
around circumference of pipe for proper jointing.
3.4.7 Trench excavated below required grade: backfill to proper elevation
with pipe bedding, as specified.
3.5 Bottom of trench for sump pump drain lines larger than 3": lay pipe on 6" deep
pipe bedding material; fill around and over pipe to minimum depth of 6" above top
of pipe bell with pipe bedding material; compact all bedding material by vibration.
See Standard Drawings for Sump Pump Drain Lines.
3.6 Bottom of trench for sump pump drain lines 3” and smaller, storm sewer, water
main, or force main.
3.6.1 Hand shape to provide uniform bearing and support for full length of pipe
barrel against undisturbed earth for at least 1/4 circumference as shown
on Standard Drawings for Hand Shaped Trench Bottom.
3.6.2 Provide suitable bell holes at each pipe joint after bottom of trench has
been graded.
3.6.3 Alternate to hand shaping trench bottom: at Contractor's option,
excavate to full depth by machine; place 6" depth of pit run gravel or
crushed rock on trench bottom to provide firm bearing 1/4 circumference
of pipe.
3.6.4 Remove large clods, stones, and other foreign material from bottom
of trench.
3.7 Bottom of trench for subdrain: backfill with pea gravel. See Standard Drawings for
Subdrains.
3.8 When unstable material is encountered which may not provide a suitable
foundation for pipe, remove and replace with stabilizing material.
Pipe Excavation and Backfill
4-4
3.8.1 Stabilizing material: sharp, clean crushed stone; comply with following
gradation:
Sieve Size % Passing
2-1/2” 100
2" 90-100
1-1/2" 35-70
1" 0-15
1/2" 0-5
3.8.2 Place pipe bedding on top of stabilizing material in sewer trenches;
place excavated material on top of stabilizing material in other trenches.
4. ROCK AND RUBBLE EXCAVATION
4.1 If trench bottom is extremely hard or is in rock or rubble where there is
possibility of pipe being subjected to point contact:
4.1.1 Overexcavate trench bottom 6" minimum below grade.
4.1.2 Backfill overexcavation with pipe bedding material; place pipe bedding
material as shown on Standard Drawing.
4.2 Use of explosives: submit detailed plans to City Engineering Department outlining
all proposed blasting operations, locations, methods and use of mats and other
safety measures.
4.2.1 Obtain written approval from City before using explosives.
4.2.2 Use thoroughly experienced demolition personnel.
4.3 Dispose of excavated rock and rubble not suitable for backfill.
5. SHEETING, SHORING AND BRACING
5.1 Construct sheeting, shoring and bracing where required to hold walls of
excavation, to provide safety for workers, to protect existing utilities or
structures or to permit construction in the dry.
5.2 Leave in place all sheeting below a level 2' over top of pipe.
Pipe Excavation and Backfill
4-5
5.3 Leave sheeting and shoring in place 2' over top of pipe when removal might
damage new pipe.
6. TUNNELING
6.1 Tunneling will be required under railroads, highways, shared use paths,
driveways, concrete pavement and curb and gutter except when stipulated
otherwise in writing by City.
6.1.1 Water main, sanitary sewer and sanitary sewer force main must be
installed in casing pipe under railroads and highways.
6.2 Obtain approval of City and IDOT or railroad on method before starting;
auger or jack pipe in place.
6.3 If pipe is augered, clean out pipe upon completion of operation.
6.4 If pipe is jacked, clean out pipe as work progresses; use dry bore method.
6.5 If pipe is directionally bored, properly dispose of boring mud; do not deposit
on ground or dispose of mud in any storm sewer or sanitary sewer.
6.6 If voids occur above pipe or casing pipe, blow full with sand or flowable fill.
6.7 Maintain correct vertical and horizontal alignment; tolerance for sanitary sewers:
6.7.1 Vertical: 0.2' up to 100’ with an additional 0.1’ per 100’
thereafter or as to permit gravity flow in proper direction.
Backfall and sags in pipe are not allowed.
6.7.2 Horizontal: 1.0' per 100’.
6.8 Maintain street, highway or railroad for full use by traffic at all times.
6.9 Tunneling below or adjacent to structures or pavement: do work in manner to
prevent settlement of structures or pavement.
6.10 Casing spacers: stainless steel construction with polyethylene runners. Install
within one foot of each side of the carrier pipe joint and at maximum spacing of 6-
feet. Do not allow pipe to be supported by joint bells. Follow manufacturers
recommendations.
Pipe Excavation and Backfill
4-6
6.11 Casing end seals: minimum 1/8 inch thick manufactured synthetic rubber with
stainless steel bands and fasteners. Install at both ends of casing pipe around
carrier pipe.
7. DEWATERING
7.1 Do all work in dry; provide for handling of water encountered during
construction.
7.2 Lay no pipe in or pour no concrete on excessively wet soil.
7.3 Prevent surface water from flowing into excavation; remove water as it
accumulates.
7.4 Divert stream flow away from areas of construction.
7.5 Do not discharge water into sanitary sewers.
7.6 Protect discharge points from erosion. Provide sediment control for sediment
contaminated water. Discharges from dewatering activities, including discharges
from dewatering of trenches and excavations, are prohibited unless managed by
appropriate controls.
7.7 Remove all dewatering equipment and wells at end of construction; wells not
allowed to be abandoned in place.
8. BACKFILL FOR STRUCTURES
8.1 Backfill after concrete or masonry has cured.
8.2 Backfill with suitable material removed from excavation except where other
backfill is specified; use no debris, frozen earth, large clods or stones.
8.3 Backfill simultaneously on all sides of structure; save structure from damage at all
times.
8.4 Compact backfill at structures to density not less than specified for adjacent
trench.
8.5 Terminate at original grade or at elevation shown on plans; dispose of excess
excavation unless otherwise directed by City Engineering Department.
8.6 Prepare backfill for surface restoration as specified for adjacent trench.
Pipe Excavation and Backfill
4-7
8.7 If settlement occurs within period of guarantee and bond, refill, compact and
level off, and provide surface restoration in accordance with SURFACE
RESTORATION AND PAVEMENT REPLACEMENT.
9. TRENCH BACKFILL
9.1 Backfill trench immediately after locations of connections and appurtenances
have been recorded and testing has been completed.
9.1.1 Provide compacted backfill at all locations unless ordinary backfill is
specifically permitted by City Engineering Department.
9.1.2 Maintain compacted backfill moisture content between optimum moisture
content percentage and 4% above optimum.
9.2 Allow no more than 200' of trench to be open at one time; construct manholes and
appurtenances and backfill as work progresses.
9.3 Use no large stones, large clods, organic matter, rubbish, frozen or unsuitable
materials in backfill.
9.4 Backfill simultaneously on both sides of pipe to prevent displacement.
9.5 Trenches where "compacted backfill" is required:
9.5.1 Hand place and carefully compact backfill to 1' over top of pipe.
9.5.2 Backfill above 1' over top of pipe with excavated material in layers not
to exceed 6", moisten if required; compact to 95% maximum density.
9.5.3 Fill upper portion of trench with topsoil where construction area is to be
seeded or sodded; replace street surfacing material where trench is in
or at edge of traveled way.
9.6 Trenches where "ordinary backfill" is allowed:
9.6.1 Hand place and carefully compact backfill to 1' over top of pipe.
9.6.2 Backfill above 1' over top of pipe with excavated material in layers not
to exceed 6" up to 12"; moisten if required; compact to 90% maximum
density.
Pipe Excavation and Backfill
4-8
9.6.3 Fill upper portion of trench with topsoil; prepare for surface
restoration.
9.6.4 Mound up or level off to original surface.
9.7 Backfill above pvc truss pipe, PE pipe, solid wall pvc and pvc profile wall pipe.
9.7.1 Backfill with pipe bedding material to minimum 12” above top of pipe; do
not drop pipe bedding material from equipment bucket more than 2’
above pipe.
9.7.2 Above pipe bedding material, except at creek crossings, backfill with
excavated material, except frozen material, shale, and other non-suitable
material; do not drop backfill material from equipment bucket more than
2’ above bottom of trench until backfill material is in place 4’ above pipe
bedding backfill material.
9.7.3 Consolidate bottom 4’ of trench backfill with hand tools, tampers and
vibratory plates; do not use drop type compactor until above bottom 4’ of
trench backfill.
9.8 Pipe bedding for backfill to top of pipe may be required if mechanical compaction
of backfill around pipe does not eliminate voids.
9.9 New pipes below existing water, sewer, or other mains: backfill under existing
water, sewer or other main with pipe bedding; compact to 95% maximum density;
length of pipe bedding backfill at elevation of existing utility: equal to depth of
excavation below utility.
9.10 If removal of sheeting disturbs compacted backfill, recompact backfill to comply
with specifications.
10. CONCRETE ENCASEMENT
10.1 Place concrete encasement at creek crossings or where directed by City
Engineering Department.
10.1.1 Make pipe joint in same manner specified for pipe not encased.
10.1.2 Pour concrete beneath and around pipe after jointing is complete.
10.1.3 Use two temporary pipe supports per pipe length: one near bell and
one near spigot.
Pipe Excavation and Backfill
4-9
10.1.4 Provide ties and braces to prevent displacement or flotation during
encasement.
10.2 Use concrete encasement as shown on Standard Drawing.
5-1
PART 5 - STORM SEWERS AND STRUCTURES
INDEX
1. GENERAL 6. CONNECTIONS BETWEEN DISSIMILAR
2. PIPE MATERIALS PIPE
3. JOINTS FOR REINFORCED CONCRETE PIPE 7. STORM SEWER INSTALLATION
PIPE (RCP AND RCAP) 8. SUMP PUMP DRAIN LINES
4. MANHOLES 9. SUBDRAINS
5. INTAKES 10. TESTS
1. GENERAL
1.1 This part of the specifications includes materials and installation procedures for
storm sewers and appurtenances, subdrains and sump pump drain and collector
lines.
2. PIPE MATERIALS
2.1 Reinforced concrete pipe (RCP): ASTM C76, Class III, Wall B, tongue and groove,
machined ends; provide reinforcement as set forth in Table 3 of ASTM C76; use for
storm sewer except for pipe jacked or augered in place.
2.1.1 Use ASTM C76, Class IV, Wall B, tongue and groove pipe for jacking or
augering; provide reinforcement as set forth in Table 4 of ASTM C76.
2.2 Reinforced concrete arch pipe (RCAP): ASTM C506, Class A-III, tongue and
groove, machined ends. Use where clearance requirements preclude use of RCP.
2.3 For water main conflicts use RCP or RCAP; provide flexible joint rubber gasket;
ASTM C443.
2.4 Corrugated metal pipe (CMP): AASHTO M36, galvanized 2-2/3" x 1/2" corrugations;
14 gauge; use for roadway culverts only; minimum pipe size: 12" dia.; size roadway
culvert to convey carrying capacity of ditch.
2.5 Sump pump collector lines, sump pump drain lines and subdrains:
2.5.1 Polyvinylchloride pipe (pvc): ASTM D3034, SDR 23.5, manufactured in
accordance with ASTM D1784; cell classification 12454-B; size equal to or
larger than 4”; joints according to manufacturer's recommendations; use for
sump pump drain line in right-of-way.
Storm Sewers and Structures
5-2
2.5.2 Polyvinylchloride pipe (pvc): ASTM D3034, SDR 35, manufactured in
accordance with ASTM D1784, cell classification 12454-B; joints according to
manufacturer's recommendation; use for perforated and non-perforated
subdrain lines equal to or larger than 6".
2.5.3 Polyvinylchloride (pvc) corrugated pipe with smooth interior: Contech A2000,
or equal; ASTM F949; manufactured in accordance with ASTM D1784, cell
classification 12454-B; joints according to manufacturer's recommendation;
use for sump pump collector lines and for perforated and non-perforated
subdrain lines equal to or larger than 6".
2.5.4 High density polyethylene (HDPE) corrugated pipe with smooth interior: ADS
N12, or equal; ASTM F2648; manufactured in accordance with ASTM D3350,
cell classification 424420C; use for sump pump collector lines and for
perforated and non-perforated subdrain lines equal to or larger than 6".
2.5.5 Use manufacturer's recommended tees or wyes at all sump pump collector
lines for services.
2.5.6 Use manufacturer's recommended tees or wyes at all connections
between non-perforated subdrains or sump pump collector lines with
perforated subdrains.
3. JOINTS FOR REINFORCED CONCRETE PIPE (RCP AND RCAP)
3.1 Pipe joints wrapped with engineering fabric; engineering fabric minimum 2' wide
centered on pipe joint; engineering fabric shall conform to IDOT 4196.01 B.
3.2 Where required by City Engineer, in lieu of engineering fabric, provide cold-applied
rubber asphalt pipe joint material; quality standard: FS-SS-S-00210.
3.2.1 Apply cold joint compound to bottom 1/2 of groove and top 1/2 of
matching tongue and force adjoining pipe together; wipe joint clean to
provide smooth invert.
3.2.2 Use plywood spacers as recommended by manufacturer to maintain
structural integrity of pipe being jacked or augered in place.
3.3 Use flexible joint rubber gasket at locations specified hereinbefore.
Storm Sewers and Structures
5-3
4. MANHOLES
4.1 Manholes and end of line cleanouts:
4.1.1 Conform to details shown on Standard Drawings and to
SUDAS Standard Specifications Figures. See DESIGN
STANDARDS for types permitted.
4.1.1.1 Type SW-301: Chimney seal not required. Joint
sealant not required, joint material as specified for
Shallow Manholes. Use SUDAS Standard
Specifications Type SW-601 castings.
4.1.1.2 Types SW-401 and SW-405: offset top slab
opening toward steps.
4.1.1.3 For all types: Concrete and reinforcing as
specified in STRUCTURAL CONCRETE AND
REINFORCEING STEEL; precast reinforced concrete
pipe manhole sections with minimum wall
thickness 5” meeting ASTM C478.
4.1.2 Diameter and thickness of base may be increased by City Engineering
Department due to poor foundation conditions.
4.1.3 Use shallow manhole only where required clearances above top of
pipe preclude the use of any other manhole types; use end of line
cleanouts for sump pump and subdrain lines only.
4.1.4 Shallow manholes:
4.1.4.1 Conform to details shown on Standard Drawings.
4.1.4.2 Poured in place, 48"x48" square manhole, concrete bottom
slab, walls and top slab.
4.1.4.3 Concrete as specified in STRUCTURAL CONCRETE AND
REINFORCING STEEL. Bottom slab and walls minimum 8" thick.
Top slab 6" thick in non-traffic areas. Top slab 10" thick in traffic
areas. Maintain temperature of work at 40°F. for at least 24
hours after placing.
Storm Sewers and Structures
5-4
4.1.4.4 Reinforcing as specified in STRUCTURAL CONCRETE AND
REINFORCING STEEL. Bottom slab use #5 at 12" each way. Walls
use #5 at 12" horizontal and vertical; provide continuous steel
through corners; top slab use #4 at 6".
4.1.4.5 Alternative wall material: 48" dia. reinforced concrete pipe;
ASTM C478, minimum wall thickness: 5". Minimum wall height
required above top of storm sewer pipe: 12".
4.1.4.6 Joints: cold-applied rubber asphalt pipe joint material: quality
standard: FS-SS-S-00210.
4.2 Special manholes:
4.2.1 Conform to details shown on Standard Drawings.
4.2.2 Diameter and thickness of base may be increased by City
Engineering Department due to poor foundation conditions.
4.2.3 Construct bottom section of precast reinforced concrete pipe;
ASTM C478.
4.2.4 Construct upper section with precast reinforced concrete pipe; place
eccentric to lower section.
4.2.5 Bottom section top slab: reinforced concrete as shown on Standard
Drawing; provide keyway seat for mortaring in manhole top section,
pour non-shrinking concrete fillet around outside of joint with
manhole top section.
4.2.6 Use special manholes where any connecting pipe is 30" or larger in
diameter or span.
4.2.7 Use manhole diameters shown on Standard Drawing.
4.2.8 Omit upper section if depth of manhole is less than 6'.
Storm Sewers and Structures
5-5
4.3 Manhole bottoms:
4.3.1 If precast or poured without manhole section being embedded: place
primed manhole section in bed of mortar or cold-applied rubber asphalt
pipe joint material; quality standard: FS-SS-S-00210; pour non-shrinking
concrete fillet around outside of manhole section.
4.3.2 If poured with manhole section embedded: embed 2" minimum.
4.3.3 Use non-shrinking concrete between pipe and manhole blockout as
specified in STRUCTURAL CONCRETE AND REINFORCING STEEL.
4.4 Accessories:
4.4.1 Steps: M. A. Industries, Inc., PS1-PF, or approved equal; #4 steel bar in
copolymer polypropylene plastic; provide on upstream side in all
manholes; space 16" o.c.; top step 10" below top of cone section.
4.4.2 Type E frame and cover for all manholes except shallow manholes: SUDAS
Standard Specifications Figure SW-602; machined bearing surfaces;
concealed pickholes; use unless specified otherwise.
4.4.3 Type F frame and cover for all manholes except shallow manholes: SUDAS
Standard Specifications Figure SW-602; machined bearing surfaces;
concealed pickhole; use where manhole is located in concrete pavement.
4.4.4 Type G frame and cover for shallow manholes: SUDAS Standard
Specifications Figure SW-602; machined bearing surfaces, concealed
pickhole.
4.4.5 Frame and cover for cleanouts: SUDAS Standard Specifications Figure
4040.232; set top of frame and cover flush with finished ground.
4.4.6 Drill two 1" dia. holes in manhole frame flange to accommodate anchor
bolts specified hereinafter.
4.4.7 Secure frame and adjusting rings to upper manhole section with two
stainless steel 1/2" dia. anchor bolts, equally spaced on 2'-5" dia. circle to
prevent movement of frame or entry of water; seal frame in place.
Storm Sewers and Structures
5-6
4.4.8 Provide reinforced concrete or high density polyethylene adjusting rings
on manholes as necessary to place cover at grade or to required
elevation; provide one adjusting ring minimum; maximum height of
manhole adjustment using adjusting rings: 12"; secure to upper manhole
section; make joints with bituminous jointing material to prevent entry of
water.
4.4.8.1 Secure adjusting rings to manhole with stainless steel tie rods.
4.4.8.2 Concrete adjusting rings: comply with ASTM C478.
4.4.8.3 High density polyethylene adjusting rings: comply with ASTM
D1248.
4.4.8.4 Do not use polyethylene adjusting rings where exposed to
HMA pavement.
5. INTAKES
5.1 Conform to SUDAS Standard Specifications Figures: See DESIGN STANDARDS for
types permitted.
5.2 Construct top and bottom sections of reinforced concrete as specified in
STRUCTURAL CONCRETE AND REINFORCING STEEL.
5.3 Construct intake walls of precast manhole sections or poured in place concrete;
poured in place intakes: use reinforced concrete as specified in STRUCTURAL
CONCRETE AND REINFORCING STEEL.
5.3.1 In freezing weather, heat materials and protect work from cold;
maintain temperature of work at 40° for at least 24 hours after placing.
5.4 Accessories:
5.4.1 Frame and Cover for Curb Intakes; Type E, F or G.
5.4.2 Curb Intakes: Type Q or R.
5.4.3 Rectangular Area Intakes: Type 6.
5.4.4 Circular Area Intakes: Type 4; provide Type 5 where directed or allowed
by City.
Storm Sewers and Structures
5-7
5.4.5 Open Sided Area Intakes: Type G.
5.4.6 Provide cast-in-place concrete or high density polyethylene adjusting
rings as necessary to place cover at grade or to required elevation;
maximum height of adjustment using adjusting rings: 12" below bottom
of proposed pavement.
5.4.6.1 Concrete adjusting rings not allowed.
5.4.6.2 High density polyethylene adjusting rings: Comply with ASTM
D1248.
5.4.6.3 Do not use polyethylene adjusting rings where exposed to HMA
pavement.
5.4.7 Stamp intake castings with message “DUMP NO WASTE, DRAINS TO
RIVER”.
6. CONNECTIONS BETWEEN DISSIMILAR PIPE
6.1 Provide concrete collar 6" thick and 12" each way from joint in accordance with
SUDAS Standard Specifications Figure 4020.211 (SW-211).
6.2 For connections between pvc sump pump drain lines and RCP storm sewer core
drill RCP pipe and install Inserta Tee, or equal.
6.3 Provide Fernco Strong Back RC couplers, or equal, for subdrains, sump pump
collector lines and sump pump drain line connections to existing pipe.
6.4 Modify above requirements as directed by City Engineering Department.
7. STORM SEWER INSTALLATION
7.1 Before laying pipe, verify all measurements at site; make necessary field
measurements to accurately determine sewer make-up lengths or closures.
7.2 Begin at lowest point in line; lay bell or groove ends pointing upstream.
7.3 Place pipe such that joint openings on the outside or inside of the pipe do not
exceed 1/8” at the bottom and 5/8” at the top.
7.4 Lower pipe carefully into trench; lay true to line and grade.
Storm Sewers and Structures
5-8
7.5 Provide a smooth and uniform hand shaped invert as shown on Standard Drawing;
bear spigots against bell shoulders.
7.6 Conflict with water main: conform with requirements set forth in WATER MAINS
AND APPURTENANCES.
7.7 Where new water main or sanitary sewer crosses under existing field drain tile,
replace with 20' lengths of pipe; match size of existing drain line; use
non-perforated pipe.
7.7.1 Use corrugated pvc with smooth interior subdrain pipe for sanitary sewer
crossings.
7.7.2 Use water main pipe for water main crossings.
7.7.3 Extend pipe minimum 4' beyond trench excavation for new pipe.
7.8 Line and grade:
7.8.1 Lay pipe to design line and grade by use of laser equipment or other
approved method.
7.8.2 Check line and grade of each pipe length.
7.8.3 Keep pipe free of all dirt and foreign material.
7.8.4 Use no defective pipe; check each length for defects and hairline
cracks at ends prior to lowering into trench.
7.8.5 Do not allow horizontal and vertical alignment to vary from design
line and grade at any structure by more than 1% of the inside
diameter of the pipe or 1/4 inch, whichever is larger.
7.8.6 Do not allow the horizontal alignment of the pipe to vary from
design line at any point along the pipe by more than 1% of the
inside diameter of the pipe.
7.8.7 Continuously check alignment of pipe by flashing light between
manholes or between last piece of pipe laid and opening at
downstream manhole.
7.9 Correct misalignment, displacement or otherwise defective pipe.
Storm Sewers and Structures
5-9
7.10 Place concrete headwall at outlet of storm sewer as shown on Standard Drawing
unless flared end section is permitted by City Engineering Department; provide
minimum of 10 tons of rip-rap at downstream end of headwall; place rip-rap over
engineering fabric, IDOT 4196.01B.3.
7.10.1 Rip-rap: IDOT 4130.02 minimum Class D size revetment stone.
7.11 With approval of City Engineering Department, flared end sections may be used at
outlet of storm sewers.
7.11.1 Use rip-rap, as specified, at downstream end; provide minimum 10 tons of
rip-rap or as permitted by City; place rip-rap over engineering fabric, IDOT
4196.01B.3. Construct concrete footing under downstream end of sewer
flared end pipe section; footing full width of flared end.
7.11.1.1 Footing may be deleted on culverts provided written request
is made by the contractor to the City, and City Engineering
Department provides written approval to delete footing.
7.11.2 Flared end section: Forterra, complying with ASTM C76 or ASTM 506, or
approved equal; flat bottom; provide tie holes for securing flared end
section to upstream pipe section.
7.11.3 Provide two pipe joint ties on outside of last three pipe joints at each
flared end section; order upstream pipe section and flared end section
with holes provided; Forterra pipe joint ties, or approved equal.
7.11.4 Install minimum 3’ wide clay waterstop at all storm sewer outlets per
SUDAS Standard Specifications Figure SW-105.
7.12 Clean and televise sewers and submit copy of video and written report to City
Engineering Department as specified under GENERAL CONDITIONS.
8. SUMP PUMP DRAIN LINES
8.1 Materials: as specified hereinbefore.
8.1.1 Sump pump collector lines in public right-of-way minimum size 8”.
8.2 Installation: as specified in DESIGN STANDARDS and PIPE EXCAVATION AND
BACKFILL.
Storm Sewers and Structures
5-10
8.3 Mark location of sump pump drain line with steel post painted green; set top of
post 3', minimum, above ground.
8.3.1 City will mark location of sump pump drain line with the symbol "S"
lying on its side stamped in front face of fresh concrete during
pavement construction.
9. SUBDRAINS
9.1 Construct perforated or non-perforated subdrains as shown on plans or as directed
by City Engineering Department.
9.2 Arrange subdrains and collector pipes to prevent freezing; minimum depth of cover
over buried pipe: 3'-6" or as approved by City.
9.3 Slope subdrains to drain.
9.4 Backfill perforated subdrain with washed, round, durable, porous backfill
material meeting IDOT Aggregate Gradation No. 29. Use pea gravel for 6” back
of curb subdrains and all back and side yard subdrains.
9.5 Connect subdrains to storm sewer, sump pump collector lines or daylight in
drainageway.
9.6 Provide pipe, manholes, intakes or end of line cleanouts as specified
hereinbefore.
9.7 Storm sewers may be used for subdrain provided edge of storm sewer is
located within 3’ of the back of the curb. Backfill storm sewer used for
subdrain with pea gravel per Std. Dwg. No. 37.
10. TESTS
10.1 Comply with applicable sections of ASTM and other applicable industry
standards and codes.
10.2 Clean and televise all storm sewers including subdrains and sump pump
collector lines. Subdrains 6” in diameter and smaller only need to be
cleaned and not televised.
10.2.1 Camera:
10.2.1.1 High-resolution color with adjustable iris focus.
Storm Sewers and Structures
5-11
10.2.1.2 Pan and tilt capabilities.
10.2.1.3 Integral lighting suitable to provide proper illumination
and a clear video image of the entire periphery of the
pipe.
10.2.1.4 Capable of operating in 100% humidity conditions.
10.2.1.5 Produce a high quality video image.
10.2.1.6 Provide with depth gauge to measure dips and sags in
pipe.
10.2.2 Provide closed-circuit video inspection equipment capable of
displaying on-screen footage of distance measured to within 1% of
actual distance.
10.2.3 Record the inspection in color in the recording media specified by
the City Engineering Department. Forward the recording and
inspection report to the City Engineering Department.
10.2.4 Clean all storm sewers and pipe culverts prior to testing by flushing
with high pressure water and removing debris by vacuum
extraction, and by removing sheeting, bracing, shoring, forms, soil
sediment, concrete, or other debris.
10.2.5 Do not discharge soil sediment or debris to drainage channels,
existing storm sewers, or existing sanitary sewers.
10.2.6 Prior to video inspection, run sufficient water through the pipe to saturate
potential low spots so they may be detected during inspection.
10.2.7 Inspect each pipe segment between manholes or access points in a single,
continuous run. Progress through the entire project in a uniform
direction.
10.2.8 Inspect all lateral connections and other observations at right angles
utilizing the pan and tilt capabilities of the camera.
10.2.9 Center the video camera in the pipe during the inspection.
10.2.10 Do not exceed 30 feet of inspection per minute.
Storm Sewers and Structures
5-12
10.2.11 Provide a copy of the video inspection including on-screen continuous
footage, pipe diameter, direction of viewing, and manhole and street
location references in the recording. Affix labels to the recording media to
include the name of the project, the date, and the location of the
inspection.
10.2.12 Provide a written report of the inspection. In the report, include true-to-
scale drawings of all sewer defects and observation locations. Reference
the time stamp on each line item entry on the written report.
10.3 Low spots holding water exceeding the following depths for each pipe size will be
considered unacceptable and must be removed and reinstalled to proper grade.
Pipe Diameter
Maximum Low Spot Depth
Per Occurrence
Maximum Total Low Spot Depths
For All Occurrences Between
Two Adjacent Manholes
8” 1/2" 1"
10” 1/2" 1"
12” 3/4" 1-1/2"
15” 3/4" 1-1/2"
18" and Larger 5% of Pipe Diameter
Measured to the nearest 1/2”
10% of Pipe Diameter
Measuredto the nearest 1/2”
10.4 Repair or replace any defective, broken, damaged or fractured pipe.
6-1
PART 6 - SANITARY SEWERS AND APPURTENANCES
INDEX
1. GENERAL
2. PIPE MATERIALS
3. PIPE JOINTS
4. MANHOLES
5. SERVICE CONNECTIONS
6. PUMPING STATIONS
7. LATERAL SEWER AND SERVICE
PIPE INSTALLATION
8. FORCE MAIN INSTALLATION
9. RAILROAD AND HIGHWAY CROSSINGS
10. STREET CROSSINGS
11. TESTS
1. GENERAL
1.1 This part of the specifications includes materials and installation procedures for
sanitary sewers and appurtenances.
1.2 Isolate sanitary sewer from downstream sewers and pumping stations with ball plug
during construction; do not remove ball plug until completion of pavement
construction; dewater manholes as required to maintain maximum 2' of standing
water at ball plug; intent is to keep construction debris and ground water from
washing into downstream system.
2. PIPE MATERIALS
2.1 Vitrified clay pipe (VCP): ASTM C700, extra strength; use only to repair or replace
existing vitrified clay pipe for 12" or smaller diameter sanitary sewer pipe and
sanitary sewer connections.
2.2 Polyvinylchloride truss pipe (pvc truss): ASTM D2680 pvc composite pipe; use for
15" or smaller diameter sanitary sewer pipe.
2.3 Polyvinyl chloride service pipe (pvc): 4" or 6"; ASTM D3034, SDR 23.5; cell
classification 12454-B. Use for service pipe for sanitary sewer.
2.4 Polyvinylchloride (pvc) corrugated pipe with smooth interior: Contech A2000, JM
Eagle Ultra Corr or equal; ASTM F949; manufactured in accordance with ASTM
D1784; cell classification 12454-B; pipe stiffness of 46 psi; use for 18" or larger
diameter sanitary sewer pipe.
2.5 Ductile iron pipe (DI): ANSI A21.50 manufactured in accordance with ANSI A21.51;
minimum thickness Class 52; cement lined; standard outside asphalt coating.
2.5.1 Use for force main at subdivider's option and use for underground
gravity sewer at conflicts with water mains.
Sanitary Sewers and Appurtenances
6-2
2.5.2 Fittings: mechanical joint, meeting ANSI/AWWA C153/A21.53 compact
design with joint meeting ANSI/AWWA C111/A21.11, 350 psi pressure
rating.
2.5.3 Wrap all buried pipe and fittings; minimum 8 mils thickness polyethylene
encasement; AWWA C105.
2.6 Polyvinylchloride pipe (pvc): AWWA C900; outside diameter conforming to ductile
iron pipe; dimensional ratio (DR) equal to 18 for 150 psi working pressure rating.
2.6.1 Use for buried force main at subdivider's option.
2.7 Steel casing pipe: smooth wall welded steel pipe, ASTM A139; 3/8" wall thickness,
unless directed otherwise by IDOT or railroad; use for railroad and highway
crossings or where directed by City.
2.7.1 Coat outside of pipe with asphalt liquid, Iowa Paint Mfg. Co., or
approved equal.
2.8 Other pipe materials may be acceptable with City approval.
3. PIPE JOINTS
3.1 Vitrified clay pipe (VCP): factory fabricated, 0-ring, flexible compression joints;
ASTM C425 or compression couplings: ASTM C594, Type B.
3.2 Polyvinylchloride truss pipe and corrugated pipe with smooth interior:
elastomeric gasket, ASTM D3212; gasket materials, ASTM F477.
3.3 Polyvinylchloride pipe service pipe (pvc): flexible elastomeric gasket joint;
ASTM F477 and ASTM D3212.
3.4 Polyvinylchloride (pvc) force main: push-on joint, AWWA C900;
compatible with mechanical joint fittings specified hereinbefore.
3.5 Ductile iron pipe: mechanical or push-on joints; ANSI A21.11.
3.6 Steel casing pipe: welded joints: comply with American Welding Society (AWS)
Code of Arc and Gas Welding in Building Construction.
3.6.1 Bevel or space ends of pipe to insure penetration of weld for full thickness
of pipe.
Sanitary Sewers and Appurtenances
6-3
3.7 All sanitary sewer repairs made with water strength couplings, Hymax 2000
coupling, or equal.
3.8 Pipe joint protection and inspection:
3.8.1 Carefully protect joints from injury while handling and storing pipe.
3.8.2 Use no deformed, gouged or otherwise impaired joints.
3.8.3 Clean joint surfaces of dirt and foreign matter before jointing pipe.
3.8.4 Make joints in strict accordance with manufacturer's recommendations.
4. MANHOLES
4.1 Standard, special, or shallow manholes:
4.1.1 Conform to details shown on Standard Drawings and to SUDAS Standard
Specifications Figures. See DESIGN STANDARDS for types permitted.
4.1.2 Use shallow manhole only where required clearances above top of
pipe preclude the use of any other manhole types.
4.1.3 Diameter and thickness of base may be increased by City
Engineering Department due to poor foundation conditions.
4.1.4 Reinforced concrete pipe; ASTM C478, minimum wall thickness: 5"; one
cage reinforcing: minimum reinforcement: 0.18 sq.in. per linear foot of
pipe wall.
4.1.5 Joints: rubber ring gasket type, flexible joint, 0-ring gasket, or
approved equal; conform to ASTM C443.
4.1.6 Apply 6" wide heavy bitumastic coating on outside of manhole at joints
around entire perimeter.
4.1.7 Pipe openings: flexible watertight connection integral with bottom barrel
section of manhole; lockjoint flexible manhole sleeve, or approved equal.
Sanitary Sewers and Appurtenances
6-4
4.2 Manhole bottoms:
4.2.1 If precast or poured without manhole section being embedded: place
primed manhole section in bed of mortar or cold-applied rubber asphalt
pipe joint material; quality standard: FS-SS-S-00210; pour non-shrinking
concrete fillet around outside of manhole section.
4.2.2 If poured with manhole section embedded: embed 2" minimum.
4.3 Use non-shrink concrete between pipe and manhole blockout as specified in
STRUCTURAL CONCRETE AND REINFORCING STEEL.
4.4 Drop connections: use for manholes where difference in elevation of connecting
pipe is greater than 2'-0"; conform to details shown on Standard Drawings.
4.4.1 Use external drop connections on all manholes 48” in diameter as shown
on Standard Drawings.
4.4.2 Internal drop connection may be used for sewers 12” in diameter or less
provided manhole diameter is increased 12” for each internal drop
connections.
4.4.3 External drop connection pipe and fittings and 20’ length of sewer pipe
adjacent to manhole constructed with ductile iron.
4.4.4 Internal drop connection pipe and fitting constructed with ductile iron or
pvc with stainless steel hardware and fasteners.
4.5 Accessories:
4.5.1 Steps: M. A. Industries, Inc., PS1-PF, or approved equal; #4 steel bar in
copolymer polypropylene plastic; provide in all manholes; space 16" oc;
top step 10" below top of cone section; place steps on straight side of
manhole; locate 90o from direction of flow.
4.5.2 Frame and cover for standard and special manholes:
4.5.2.1 Type A frame and cover: SUDAS Standard Specifications
Figure SW-601; machined bearing surfaces, gasket seal,
concealed pickhole; use unless specified otherwise.
Sanitary Sewers and Appurtenances
6-5
4.5.2.2 Watertight frame and cover: Type C; SUDAS Standard
Specifications Figure SW-601; use where watertight covers are
required.
4.5.3 Frame and cover for shallow manholes: Type C: SUDAS Standard
Specifications Figure SW-601; machined bearing surfaces, gasketed
seal, concealed pickhole.
4.5.4 Drill two 1" dia. holes in manhole frame flange to accommodate anchor
bolts specified hereinafter.
4.5.5 Secure frame and adjusting rings to upper manhole section with two
stainless steel 1/2" dia. anchor bolts, equally spaced on 2'-5" dia. circle to
prevent movement of frame or entry of water; seal frame in place.
4.5.6 Provide reinforced concrete adjusting rings on manholes outside of
pavement at contractor’s option as necessary to place cover at grade or
to required elevation; provide one adjusting ring minimum; maximum
height of manhole adjustment using adjusting rings: 12"; grout in and
make joints with bituminous jointing material to prevent entry of water.
4.5.6.1 Secure adjusting rings to manhole with stainless steel tie
rods.
4.5.6.2 Comply with ASTM C478.
4.5.7 Provide expanded polypropylene adjusting rings on manholes outside of
pavement at contractor’s option and manholes within pavement as
necessary to place cover at grade or to required elevation; provide one
adjusting ring minimum; maximum height of manhole adjustment using
adjusting rings: 12”.
4.5.7.1 Use adhesive meeting ASTM C920, Type S, Grade N5, Class 25.
4.5.7.2 Comply with ASTM D4819.
4.5.8 Provide external chimney seals on all sanitary manholes with reinforced
concrete adjusting rings; do not install chimney seals on manholes with
expanded polypropylene adjusting rings.
4.5.8.1 Seals to extend from the manhole frame flange to 3"
below the adjusting rings.
Sanitary Sewers and Appurtenances
6-6
4.5.8.2 Rubber sleeve with stainless steel top and bottom bands:
minimum rubber thickness 3/16", ASTM C923; allow for
minimum vertical expansion of 2"; locking mechanism of studs
and nuts conforming to ASTM F923 and 594,
Type 304.
5. SERVICE CONNECTIONS
5.1 Conform to details shown on Standard Drawing; use 4" or 6" branch diameter
wyes; if sewer invert is more than 12' below finished grade of street, use tee and
riser; encase tee and riser in Pipe Bedding Material as shown on Standard
Drawing.
5.2 pvc Services:
5.2.1 For 8" main line and 4" or 6" services: use molded wye with all bell
configuration; solvent weld factory-attached couplings.
5.2.2 For larger than 8" main line: use reducing saddles with 4" or 6" stubs bell
end ready for solvent welding to service.
5.3 Place stopper in end of service pipe:
5.3.1 Provide watertight joint on stopper to match that on pipe spigot; block
plug with 2”x4” vertical strut to 2’ above ground.
5.3.2 Mark end location of sewer service connection with steel post painted
red; set top of post 3', minimum, above ground.
5.3.2.1 City will mark location of sewer service with the symbol "S"
stamped in front face of fresh concrete during pavement
construction.
5.3.3 Omit Pipe Bedding Material on the last 5’ of sanitary service pipe at
stub end.
5.4 Backfill trench after recording exact location of service connection.
Sanitary Sewers and Appurtenances
6-7
6. PUMPING STATIONS
6.1 Submit complete design to City for approval; include equipment drawings,
design data and proposed plans.
6.2 Chain link fence: construct 6' high vinyl coated chain link fence including two 10'
wide gates, and all posts, braces, clips, and miscellaneous materials for complete
installation; provide and install privacy slats in fabric.
6.2.1 Embed posts in concrete as recommended by manufacturer.
6.2.2 Provide padlock for each gate with two keys, Master Size 1, or
approved equal.
6.3 Non-clog submersible pumps; Flygt, or equal.
6.3.1 Explosion proof motors suitable for NEC Class I, Division I.
6.3.2 Stainless steel guide rails, hardware, cables, chains and fasteners.
6.3.3 Provide thermal and seal failure protection for pump and motor.
6.3.4 Provide safety chain for each pump attached to pump and just under
hatch.
6.4 Trash basket: Fiberglass with vertical rods and drop bottom.
6.5 Piping: painted ductile iron for all interior piping; ductile iron as specified
herein before for all buried piping between structures.
6.6 Shut off valves: rectangular port plug valve.
6.7 Check valve: swing type with external weight and lever and air cushion
cylinder assembly suitable for wastewater.
6.8 Provide on site standby generator, magnetic flow meter and pre-
manufactured control building. Connect all alarms and data outputs to City’s
data acquisition system.
6.9 Provide minimum 2” water service with yard hydrant near pump station wet
well.
Sanitary Sewers and Appurtenances
6-8
7. LATERAL SEWER AND SERVICE PIPE INSTALLATION
7.1 Before laying pipe, verify all measurements at site; make necessary field
measurements to accurately determine sewer make-up lengths or closures.
7.2 Begin at lowest point in line; lay bell or groove ends pointing upstream.
7.3 Lower pipe carefully into trench; lay true to line and grade.
7.4 Provide smooth and uniform invert; bear spigots against bell shoulders.
7.5 Make joints with equipment recommended by pipe manufacturer; do not
use backhoe to push joints together.
7.6 Line and grade:
7.6.1 Lay pipe to design line and grade by use of laser equipment or other
approved method.
7.6.2 Check line and grade of each pipe length.
7.6.3 Keep pipe free of all dirt and foreign material.
7.6.4 Use no defective pipe; carefully check each length of pipe for defects and
hairline cracks at ends prior to lowering into trench; remove and replace
cracked pipe; check each length of pvc pipe for punctures of outer ring;
do not use punctured pipe; scratches and dents acceptable for use.
7.6.5 Place in trench in sound, undamaged condition; do not damage pipe; use
web slings to install or move pipe; use of end hooks, dropping or rolling
pipe not permitted.
7.6.6 Check alignment and grade of sewer at minimum 50’ intervals off of
construction stakes between manholes.
7.7 Correct misalignment, displacement or otherwise defective sewer.
7.8 Clean and televise sewers and submit copy of video and written report to City
Engineering Department as specified under GENERAL CONDITIONS.
7.9 Conflicts with water main: conform to requirements set forth in WATER MAINS
AND APPURTENANCES.
Sanitary Sewers and Appurtenances
6-9
7.10 Connection to existing manhole:
7.10.1 Insert flexible watertight connector into new opening.
7.10.2 Install and tighten internal expansion sleeve to hold flexible connector
in place.
7.10.3 Insert pipe through flexible connector and tighten external
compression ring.
7.10.4 Do not install grout or concrete collar for cored opening with flexible
connector.
8. FORCE MAIN INSTALLATION
8.1 Lay pipe in the dry; minimum earth cover: 5'.
8.2 Clean pipe interior of foreign materials before lowering into trench; keep clean at
all times by closing open ends of pipe and fittings; use minimum amount of
gasket lubricant; apply to gasket only; do not apply to inside of bell.
8.3 Before installation, examine pipe carefully; defective, damaged or unsound pipe
will be rejected.
8.4 Place in trench in sound, undamaged condition; do not injure pipe coating or
lining; do not use end hooks to install or move pipe; do not drag or scratch pvc
pipe.
8.5 Cut pipe in neat and workmanlike manner without damage to pipe.
8.5.1 Mechanical pipe cutters subject to approval of Engineering Department.
8.5.2 Cut pvc pipe with fine tooth saw or tubing cutter; square cut; file
jagged edges.
8.5.3 Bevel cut ends of push-on type iron pipe.
8.5.4 Completely coat damaged ends of cut iron pipe with bituminous sealer;
use spray-on type sealer which will adhere to liner at any temperature;
pipe and fittings showing blisters or holes will be rejected by Engineer on
site.
8.5.5 Seal ends of cut truss pipe with solvent cement or lubricant.
Sanitary Sewers and Appurtenances
6-10
8.6 Use suitable fittings where grade or alignment requires offsets of more than 1" per
foot.
8.7 Provide continuous tracer wire along all new pvc force main; tracer wire as
specified in WATER MAINS AND APPURTENANCES ; start wire at meter manhole
and end at discharge manhole; terminate tracer wire in tracer wire receptacle box
with top flush with ground near meter manhole, discharge manhole and any
intermediate structures.
9. RAILROAD AND HIGHWAY CROSSINGS
9.1 Tunnel casing pipe in place; length and method of installation as required by
Railroad or IDOT.
9.2 Encase all sewers and force mains under railroads and highways.
9.3 Do not stockpile or store excess material or debris in right-of-way.
10. STREET CROSSINGS
10.1 Tunnel sewers under paved streets, driveways and sidewalks unless written
permission to open cut is granted by City; use casing pipe if directed by City.
11. TESTS
11.1 Allowable leakage:
11.1.1 Maximum allowable infiltration or exfiltration for any new sanitary sewer
section between manholes, including all manholes is 200 gallons per inch
of diameter per mile of pipe per day; manholes may be tested separately.
11.2 Leakage test:
11.2.1 Conduct all infiltration and exfiltration tests after backfill for sewer line
and manholes is complete; test sewer lines by low pressure air testing.
11.2.1.1 Isolate and test all sections of pipe between
manholes.
11.2.1.2 Install plugs in accordance with manufacturer's
recommendations; allow no one in manholes during
testing.
11.2.1.3 Wet line by flushing to produce consistent results.
Sanitary Sewers and Appurtenances
6-11
11.2.1.4 Plug and brace all stoppers to resist test pressure.
11.2.1.5 Determine test duration for section under test from
Table No. 1; table ignores pipe length and uses factor
0.472 d, with d being in inches.
Table No. 1
Pipe Diameter
(Inches)
Test Period
Duration
(min.)
8 4.0
10 5.0
12 6.0
15 7.0
18 8.5
21 10.0
24 11.5
27 13.0
30 14.0
36 17.0
Pressure holding time based on average holding pressure
of 3 psi gauge or drop from 3.5 psi to 2.5 psi gauge.
11.2.1.6 Add air to line segment being tested until internal air pressure
of sewer line is raised to approximately 4.0 psi gauge greater
than average back pressure of any groundwater that may be
over top of the pipe; allow at least 2 min. for air pressure to
stabilize.
11.2.1.7 When pressure has stabilized and is at or above starting test
pressure of 3.5 psi gauge, commence test; record drop in
pressure for test period; if pressure has dropped more than
1.0 psi gauge during test period as set forth in Table No. 1,
line is presumed to have failed; test may be discontinued
when prescribed test time has been completed, even though
1.0 psi gauge drop has not occurred.
Sanitary Sewers and Appurtenances
6-12
11.2.1.8 In areas of known groundwater above section being
tested, divide total height of water in feet above pipe by
2.31 to establish pounds in pressure (psi gauge) that will
be added to all readings; for example, if height of water is
7' then added pressure will be 3.0 psi gauge; this increases
3.5 psi gauge to 6.5 psi gauge and 2.5 psi gauge to 5.5 psi
gauge; allowable drop of 1.0 psi and timing remain same.
11.2.2 City may require water testing of sewers if results of air testing are
unsatisfactory or indefinite.
11.2.2.1 Test sewers at infiltration test manholes designated by City
Engineering Department.
11.2.2.2 Line infiltration test using weir: cover crown of pipe with
minimum 2' of water at highest point in section being tested;
maintain test head for not less than 24 hrs. before weir
measurement is made; measure infiltration with V-notch weir
located in downstream manhole; cap or plug all service
connections and stubs to prevent entrance of groundwater
into line at connections.
11.2.2.3 Line exfiltration test: close inlet of upstream and downstream
manholes with watertight bulkheads; fill sewer and upstream
manhole with water until elevation of water in upstream
manhole is 2' higher than top of pipe in line being tested, or 2'
above existing groundwater in trench, whichever is higher
elevation; measure exfiltration by determining amount of
water required to maintain initial water elevation for 1 hour
from start of test; if average head above section being tested
exceeds 2', allowable leakage can be increased by 5% for each
additional foot of head; test is preferable for dry areas where
groundwater head over pipe does not exist at time of test.
11.3 Manhole tests: test using water exfiltration test or vacuum test.
11.3.1 Manhole exfiltration test:
11.3.1.1 Plug inlet and outlet of manhole and fill manhole to top of
casting; allow water to stand 1 hour and refill to original
elevation; after specific time, usually 15 min. to 1 hour, record
difference in elevation and convert into gallons per hour lost
through manhole leakage.
Sanitary Sewers and Appurtenances
6-13
11.3.1.2 To obtain actual line exfiltration subtract manhole loss from
loss determined during line exfiltration test.
11.3.2 Manhole vacuum test:
11.3.2.1 Test all manholes in accordance with ASTM - C1244.
11.3.2.2 Plug all lift holes with non-shrink grout.
11.3.2.3 Temporarily plug all pipes entering manhole.
11.3.2.4 Place test head at top of manhole in accordance with the
recommendations of the testing equipment manufacturer.
11.3.2.5 A vacuum of 10” of mercury shall be drawn from manhole;
turn off testing equipment and close testing equipment valves;
measure and record time for vacuum to top to 9” mercury.
11.3.2.6 A passing test is indicate when duration recorded for vacuum
to drop from 10” of mercury to 9” mercury is equal to or
longer than that shown in the following table for 48” and 60”
dia. manholes.
Manhole
Depth (ft.)
48” Dia.
Minimum
Duration
(sec.)
60” Dia.
Minimum
Duration
(sec.)
8 20 26
10 25 33
12 30 39
14 35 46
16 40 52
18 45 59
20 50 65
22 55 72
24 59 78
26 64 85
28 69 91
30 74 98
Sanitary Sewers and Appurtenances
6-14
11.3.2.7 Complete necessary repairs to manholes that fail test; repeat
test until manhole passes test.
11.4 Deflection test - sewer:
11.4.1 If pvc truss or profile wall pipe is used, provide deflection test 30 days
after backfill of trench is completed; maximum allowable deflection: 5%
of average inside diameter.
11.4.2 Run rigid ball or mandrel without mechanical pulling device through
sewer; diameter of ball or mandrel equal to 95% of average inside pipe
diameter.
11.5 Alignment test: Check sewers for alignment by using laser beam or lamping; full
barrel must be visible through section of pipe lamped.
11.6 Force mains:
11.6.1 Evaluated at a test pressure of 150 lbs. per square inch for 2 hours,
leakage shall not exceed 10 gallons per inch diameter per mile per day (24
hours); should a test of any section of pipe line disclose leakage per mile
greater than specified, Contractor shall locate leaking joints and repair
leaks until minimum leakage requirement has been satisfied in a 24 hour
test.
11.6.2 In cases where pipe line cannot be pressure tested at 150 psi, maximum
leakage must be decreased proportionally to the decrease in test
pressure.
11.6.3 All pressure testing shall be performed to satisfaction of City
Engineering Department.
11.7 Clean and televise all sanitary sewers not including services.
11.7.1 Camera:
11.7.1.1 High-resolution color with adjustable iris focus.
11.7.1.2 Pan and tilt capabilities.
11.7.1.3 Integral lighting suitable to provide proper illumination and
a clear video image of the entire periphery of the pipe.
Sanitary Sewers and Appurtenances
6-15
11.7.1.4 Capable of operating in 100% humidity conditions.
11.7.1.5 Produce a high quality video image.
11.7.1.6 Provide with depth gauge to measure dips and sags in pipe.
11.7.2 Provide closed-circuit video inspection equipment capable of displaying
on-screen footage of distance measured to within 1% of actual distance.
11.7.3 Record the inspection in color in the recording media specified by the
City Engineering Department. Forward the recording and inspection
report to the City Engineering Department.
11.7.4 Clean all sanitary sewers prior to testing by flushing with high pressure
water and removing debris by vacuum extraction, and by removing
sheeting, bracing, shoring, forms, soil sediment, concrete, or other
debris.
11.7.5 Do not discharge soil sediment or debris to drainage channels, existing
storm sewers, or existing sanitary sewers.
11.7.6 Prior to video inspection, run sufficient water containing colored dye
through the pipe to saturate potential low spots so they may be
detected during inspection.
11.7.7 Inspect each pipe segment between manholes or access points in a
single, continuous run. Progress through the entire project in a uniform
direction.
11.7.8 Inspect all lateral connections and other observations at right angles
utilizing the pan and tilt capabilities of the camera.
11.7.9 Center the video camera in the pipe during the inspection.
11.7.10 Do not exceed 30 feet of inspection per minute.
11.7.11 Provide a copy of the video inspection including on-screen continuous
footage, pipe diameter, direction of viewing, and manhole and street
location references in the recording. Affix labels to the recording media
to include the name of the project, the date, and the location of the
inspection.
Sanitary Sewers and Appurtenances
6-16
11.7.12 Provide a written report of the inspection. In the report, include true-to-
scale drawings of all sewer defects and observation locations. Reference
the time stamp on each line item entry on the written report.
11.8 Low spots holding water exceeding the following depths for each pipe size will be
considered unacceptable and must be removed and reinstalled to proper grade.
Pipe Diameter
Maximum Low Spot Depth
Per Occurrence
Maximum Total Low Spot Depths
For All Occurrences Between
Two Adjacent Manholes
8" 1/2" 1"
10" 1/2" 1"
12" 3/4" 1-1/2"
15" 3/4" 1-1/2"
18" and Larger 5% of Pipe Diameter 10 % of Pipe Diameter Measured
Measured to the nearest 1/2" to the nearest 1/2"
11.9 Repair or replace any defective, broken, damaged or fractured pipe.
7-1
PART 7 - WATER MAINS AND APPURTENANCES
INDEX
1. GENERAL 11. CONCRETE AND REINFORCING STEEL
2. PIPE 12. PIPE INSTALLATION
3. FITTINGS 13. VALVE INSTALLATION
4. VALVES 14. HYDRANT INSTALLATION
5. SERVICE CONNECTIONS 15. RAILROAD AND HIGHWAY CROSSINGS
6. VALVE MANHOLES AND METER
16. STREET CROSSINGS
PITS 17. CREEK CROSSINGS
7. VALVE BOXES 18. TESTS
8. BLOWOFFS 19. DISINFECTION
9. HYDRANTS
10. THRUST BLOCKS
1. GENERAL
1.1 This part of the specifications includes materials and installation procedures for
water mains and appurtenances.
2. PIPE
2.1 Ductile iron pipe (DI): ANSI A21.50, manufactured in accordance with ANSI
A21.51; minimum thickness Class 52; mechanical or push-on joint, ANSI A21.11;
use restrained or locked joints on fittings and pipe adjacent to downward,
vertical bends and for pipe augered or bored in place.
2.1.1 Standard thickness cement lining, ANSI A21.4 (AWWA C104), with
bituminous seal coat sprayed on lining surface which will adhere to
lining at all temperatures; provide coating free of blisters or visible
holes.
2.1.2 Coat outside of pipe with bituminous compound, ANSI A21.51 (AWWA
C151).
2.1.3 Wrap all buried pipe and fittings, minimum 8 mils thickness
polyethylene encasement; AWWA C105.
2.1.4 Do not telescope small pipe inside larger pipe for shipment or storage.
2.1.5 Pipe with damaged cement lining will be rejected; field patching
not permitted except on cut pipe.
Water Mains and Appurtenances
7-2
2.1.6 Use for water main at subdivider's option.
2.1.7 Use in soils contaminated with gasoline or volatile organic compounds.
Install with viton gaskets.
2.2 Polyvinylchloride pipe (pvc): AWWA C900, DR18, Class 150; push-on, rubber
gasketed joint; ductile iron pipe size.
2.2.1 Use restrained joints with coupling, gaskets and splines for augered and
bored pipe. Certainteed Certa-Lok, or equal.
2.2.2 Use for water main at subdivider's option.
2.2.3 Do not use in soils contaminated with gasoline or volatile organic
compounds.
2.3 Steel casing pipe: smooth wall welded steel pipe, ASTM A139; 3/8" wall thickness,
unless directed otherwise by IDOT or railroad; use for railroad and highway
crossings or where directed by City.
2.3.1 Welded joints: comply with American Welding Society Code of Arc and
Gas Welding in Building Construction.
2.3.2 Bevel or space ends of pipe to insure penetration of weld for full
thickness of pipe wall.
2.3.3 Coat outside of pipe with asphalt liquid, Iowa Paint Mfg. Co., or
approved equal.
3. FITTINGS
3.1 Mechanical joint, ANSI/AWWA C153/A21.53 compact design with joint meeting
ANSI/AWWA C111/A21.11; 350 psi pressure rating; provide restrained or locked
joints on all fittings; Megalug, or approved equal.
3.2 At all 90º bend locations use 2 compact design 45º bends or use standard 90º
bend meeting AWWA C110.
3.3 Anchoring tee: Clow Corporation, or approved equal.
3.4 Anchoring elbow: Clow Corporation, or approved equal.
3.5 Anchoring pipe: Clow Corporation, or approved equal.
Water Mains and Appurtenances
7-3
3.6 Anchoring coupling: Clow Corporation, or approved equal.
3.7 Retainer gland: Clow Corporation F-1058, or approved equal.
3.8 Cap: Clow Corporation, or approved equal.
3.9 Plug: Clow Corporation, or approved equal.
3.10 Anchoring rods and eye bolts: 3/4" stainless steel.
3.11 Sleeves: Dresser Style 38, or approved equal.
3.12 All T-bolts and hex-head nuts for mechanical joints shall be Cor-Blue steel or
approved equal.
3.13 All exposed hex bolts and nuts on gate valves: stainless steel.
3.14 All exposed hex bolts, set screws and nuts on hydrants: stainless steel.
4. VALVES
4.1 Type permitting repacking under pressure when wide open.
4.2 Provide special tools required for disassembling and repacking valves.
4.3 Gate valves: resilient wedge, bronze trim; mechanical joint ends; conform to
AWWA C515; non-rising stem with 2" square operating nut; open
counterclockwise; resilient-seated; use for main line water valves, hydrant auxiliary
valves, tapping valves and for services larger than 2"; American Flow Control 2500,
Clow Corporation F-6100 RW, Mueller A-2361, or approved equal.
4.4 Tapping sleeves and valves: Clow Corporation F-5205, Mueller H-304, Smith-Blair
665 stainless steel sleeves, or approved equal; use in conjunction with resilient
wedge valves specified hereinbefore except use a flanged/mechanical joint valve;
Clow Corporation F-6106 RW, Mueller A-2370-16, or approved equal.
4.5 If top of nut riser is more than 6' below finished surface elevation, provide extension
stem on valve nut to bring operating nut to within 4' of finished surface elevation.
Water Mains and Appurtenances
7-4
5. SERVICE CONNECTIONS
5.1 Services 2" and smaller between main and curb stop box and optional for services
2” and smaller between curb stop box and building:
5.1.1 Service pipe: Type K seamless, soft annealed copper water tube, ASTM
B88.
5.1.2 Corporation stops: Mueller, AY McDonald and Ford ball valve style, or
approved equal.
5.1.3 Taps and tapping saddles: ductile iron body, single stainless steel strap,
corrosion resistant nylon coating, design for use on pvc pipe, Rockwell
Type 317, or approved equal.
5.1.3.1 Use tapping saddles for all corporation stops.
5.1.3.2 Use shell type cutting tool made especially for direct
tapping heavy wall pvc.
5.1.4 Curb stops: AY McDonald 76100, or equal.
5.1.5 Curb stop box: AY McDonald 5601, or equal; provide lid and stainless steel
stationary rod.
5.1.5.1 Set lid at finish grade elevation as shown on Standard
Drawing; terminate rod 1'-6" below finish grade; lid must be
operable at time of final inspection.
5.1.5.2 Provide cast iron curb box receptacle where curb stop located
in pavement; A.Y. McDonald Mfg. No. 5639 or equal.
5.1.6 Meter setting: arrange piping to allow installation of meter in horizontal run
of pipe, above floor and as close to point at which service enters building as
possible; provide 1' minimum clearance over meter; install 1" full port ball
valve on both sides of meter; allow space for meter and connecting nipples.
5.1.6.1 Ball valve: AY McDonald 72032-T, or equal.
Water Mains and Appurtenances
7-5
5.1.7 Fittings: Compression or flared fittings are allowed for services less than 2”.
Compression fittings are required for services 2” and larger.
5.2 Services larger than 2" and optional for all service sizes between curb stop box
and building:
5.2.1 Service pipe: Crosslinked polyethylene (PEXa) pipe or approved
equal.
5.2.1.1 Pipe shall be approved by manufacturer for use with
AWWA C800 fittings, using stainless steel inserts.
5.2.1.2 Pipe shall be certified to AWWA C 904 “Cross-linked
Polyethylene (PEX) Pressure Pipe, 1/2 in. (12 mm)
Through 3 in. (76 mm), for Water Service” by approved
testing agency. In addition, pipe shall be certified to
standards ASTM F876, CSA B137.5, NSF 14, NSF 61 and
PPI TR-4, by approved testing agencies, with a standard
materials designation code of 3006, as certified by the
PPI.
5.2.1.3 Pipe shall be rated for not less than 160 psi @ 73.4°F
(1379 KPa @ 23°C) based on a 0.63 design factor.
5.2.1.4 Pipe shall have a co-extruded UV Shield made from UV-
resistant high-density polyethylene, color Blue.
5.2.1.5 Pipe shall have minimum recommended UV exposure
time of one (1) year when tested in accordance with
ASTM F2657, or as per manufacturer’s recommendations.
5.2.1.6 Pipe shall be compatible with cold-expansion
compression-sleeve fittings certified to ASTM F2080 for
installations as cold as -40°F (-40°C). Flared fittings are
allowed for services less than 2”.
5.2.1.7 Manufacturer shall warrant the pipe to be free from
defects in material and workmanship for a period of
twenty-five (25) years.
5.2.1.8 Pipe can be installed on native soil.
5.2.2 Service pipe: Polyethylene (PE) pipe; Class 200; AWWA C901; DR9.
Water Mains and Appurtenances
7‐6
5.2.3 Connection to main: provide suitable tee if main and service are
installed at same time; provide tapping valve and sleeve specified for
water main for service connected to existing main; spacing of service
connections: not less than 2' apart.
5.2.4 Curb stop: use resilient wedge gate valve specified for water main; omit
curb stop if tapping valve installed at main.
5.2.5 Curb stop box: use valve box as specified for water main except use
lock cover.
5.2.6 Meter setting: as specified for services 2" and smaller, except use gate
valves with end connections matching those on meter.
5.2.7 Fittings: Compression or flared fittings are allowed for services less than 2”.
Compression fittings are required for services 2” and larger.
5.3 City will furnish and install water meter, remote reading device; upon request
and payment of fee; all other materials and work for water services by
subdivider.
5.3.1 Provide a raceway of 1” minimum diameter electrical non‐metallic
tubing (ENT) conduit from the water meter(s) through joist/wall cavities
to the building exterior within 3 feet of the gas meter(s) on commercial
and residential buildings for device installation; wiring as per City
Standards.
5.4 Notify City 48 hours prior to tapping main, any proposed water shutdown and at
completion of installation of service; backfill after City has inspected installation.
Only City allowed to operate valves.
5.5 Mark end location of service connection with steel post painted blue; extend top
of post 3', minimum, above ground.
5.5.1 City will mark location of water service with the symbol "W" stamped in
front face of fresh concrete during pavement construction.
6. VALVE MANHOLES AND METER PITS
6.1 Use 60" dia. valve manholes or approved equal for water service greater than 1”:
install as shown on Standard Drawing; valve manholes not required except when
directed by Water Utility.
Water Mains and Appurtenances
7-7
6.1.1 Use precast manhole for pit mounted installations; set manhole frame
and cover directly above water service; install with sump pump and
grate over sump; discharge to sump line or storm sewer.
6.1.2 Reinforced concrete manhole: ASTM C478, minimum wall thickness: 6”.
6.1.3 Joints: cold-applied rubber asphalt pipe joint material; quality
standard: FS-SS-S-00210.
6.1.4 Frame and cover: Type C: SUDAS Standard Specifications Figure SW-602;
machined bearing surfaces, concealed pickhole; set frame and cover
directly over operating nut of valve.
6.1.5 Place manhole cover at finished grade; do not use adjusting rings.
6.2 Use meter pits as shown on Standard Drawings.
6.2.1 Meter pits are required under the following circumstances:
6.2.1.1 A satisfactory location to City is not available inside a building.
6.2.1.2 A building is more than 100 feet from property line, in such
case shall be reviewed by City.
6.2.1.3 The water service is installed within an easement and crosses
property lines.
6.2.2 Meter pits shall be located on private property as near as practical to the
property line.
6.2.3 When a meter is removed from meter pit and the pit is not to be reused,
it is the responsibility of the property owner to see that the rim and lid
are removed, the valves are removed from service, and the pit is filled to
grade with material approved by City. Before pit is filled, property owner
shall notify City to verify removals from service line. The service shall be
capped at the main following verification.
Water Mains and Appurtenances
7-8
7. VALVE BOXES
7.1 Tyler 6850 or 6855, valve box with standard drop cover and extension piece, or
approved equal; select top and bottom sections to suit depth of cover; use at hydrants
and all valves unless directed otherwise by City; slide type when used in concrete
street pavement areas; all other areas screw type; provide Valve Box
Adapter II or approved equal rubberized centering ring seal between valve box and
valve.
8. BLOWOFFS
8.1 Install hydrant and auxiliary valve at all dead ends.
9. HYDRANTS
9.1 Waterous Pacer WB-67 safety flange type hydrant or approved equal, with hydrant
auxiliary valve and valve box; conform to AWWA C502.
9.1.1 Provide two 2-1/2" hose nozzles and one 4-1/2" pumper nozzle with
National Standard threads; 0-ring packing; depth of bury to suit depth of
cover specified for various diameters of water mains.
9.1.1.1 Provide 6" mechanical joint inlet and 5-1/4" main valve,
unless otherwise directed by City.
9.1.1.2 Provide hydrant extension as required to set hydrant grade
mark at proper elevation per manufacturer’s recommendation.
Maximum of one hydrant extension allowed.
9.1.1.3 Operating nut: National Standard; open counterclockwise;
furnish with chains on caps.
9.1.1.4 Pumper nozzle equipped with factory installed 5” Storz quick
connect coupling and cap.
9.1.2 Auxiliary valve and box: as specified hereinbefore.
9.2 Use mechanical joint anchoring tee with plain end branch; Clow Corporation, or
approved equal; provide integral gland and split Roto-Ring; use Clow Corporation
anchoring pipe, or approved equal; connect mechanical joint end to anchoring tee;
connect anchoring end to valve with integral gland and split Roto-Ring.
Water Mains and Appurtenances
7-9
9.2.1 Mechanical joint tee and anchoring coupling may be used in lieu of
anchoring tee.
9.2.2 Mechanical joint tee, anchoring elbow and anchoring coupling may be
used where required.
9.3 Hydrant color: paint hydrant Safety Yellow to safety flange and black below
flange; Tnemec alkyd system for exterior exposure, or approved equal; surface
preparation SSPC-SP6 commercial blast.
9.4 Check all hydrant threads with City of Waukee fire department hose fittings
after completion of installation of hydrants.
10. THRUST BLOCKS
10.1 Provide poured in place concrete thrust blocks where piping changes direction or
deadends.
10.2 Carry thrust block to undisturbed edge of trench for bearing.
10.3 Minimum thickness of thrust blocks: 18".
10.4 Bearing area of thrust blocks, SF:
Pipe Size
(inches)
90° Bend
45° Bend
Tee or
Deadend
4 4 2 3
6 6 3 4 8 11 6 8 10 17 9 12 12 24 13 17 14 33 18 23 16 43 23 31
10.5 Refer to Standard Drawing for general arrangement of thrust blocks; place
plywood between fittings and thrust block; do not plug end of fitting with
concrete.
11. CONCRETE AND REINFORCING STEEL
11.1 Concrete materials and reinforcing steel for structures and thrust blocks are
specified under STRUCTURAL CONCRETE AND REINFORCING STEEL.
Water Mains and Appurtenances
7-10
12. PIPE INSTALLATION
12.1 Lay pipe in dry; 5’-6” minimum earth cover except where directed otherwise by
City Engineering Department; locate water main back of curb line of existing or
proposed pavement as shown on Standard Drawing.
12.1.1 Make pipe joints in accordance with AWWA C600 and C605 and as
recommended by manufacturer; use minimum amount of gasket
lubricant; apply to gasket only; do not apply to inside of bell.
12.1.2 Bottom of trench as specified under PIPE EXCAVATION AND BACKFILL.
12.2 Notify City 48 hours prior to tapping main or any proposed water shutdown. Only
City allowed to operate valves.
12.3 Clean pipe interior of foreign material before lowering into trench; keep clean at
all times; when pipe laying is not in progress, including lunch breaks, nights,
weekends and other non-working periods, securely close open ends of pipe and
fittings with watertight plug.
12.4 Place in trench in sound, undamaged condition; do not damage pipe coating or
lining; use web slings to install or move pipe; use of end hooks, dropping and
rolling pipe not permitted.
12.5 Cut iron pipe in neat and workmanlike manner without damage to pipe; bevel cut
ends of push-on type pipe; completely coat damaged ends of cut pipe with
bituminous sealer; use spray-on type sealer which will adhere to lining at any
temperature; do not install pipe and fittings showing blisters or holes.
12.6 Cut pvc pipe with fine tooth saw or tubing cutter; square cut; file jagged edges
smooth.
12.7 Before installation, tap iron pipe lightly with light hammer to detect cracks; visually
inspect pipe lining for defects; do not install defective, damaged or unsound pipe.
12.8 Deflect pipe joints not to exceed 3° as required in accordance with
recommendations of pipe manufacturer; use suitable fittings where grade or
alignment requires offsets of more than 5/8" per foot.
12.9 Minimum horizontal separation from sanitary sewers, storm sewers or sewer
manholes: Refer to SUDAS Design Manual Chapter 4, Section 4C-1, Subsection G.
Water Mains and Appurtenances
7-11
12.10 Minimum vertical clearance for water main crossing sewer service, sanitary sewer,
storm sewer or drainage tile: Refer to SUDAS Design Manual Chapter 4, Section 4C-
1, Subsection G.
12.11 Minimum horizontal separation from sewer force mains: Refer to SUDAS Design
Manual Chapter 4, Section 4C-1, Subsection G.
12.12 Plug or cap and block all pipe ends or fittings left for future connections. Use
alternate method thrust block; SUDAS Standard Specifications Figure WM-101.
12.13 Use tracer wire for all pvc water mains and polyethylene service pipe.
12.13.1 Provide AWG #12, solid, blue, single, insulated, direct-burial copper
wire along all pvc water mains; tuck tracer wire under water main at
approximate 45° angle below horizontal spring line of water main to
protect tracer wire. Use wire with steel core with directional bored
pipe.
12.13.2 Insulation: Linear low density polyethylene (LLDPE) suitable for direct
burial. Minimum thickness 0.045 inches.
12.13.3 Splice new tracer wire to existing tracer wire at existing main; if no tracer
wire exists drive ground rod, Blackburn Catalog #3755, or approved equal
and connect tracer wire to ground rod with a corrosion-resistant copper
clamp; Blackburn Catalog #G3, or approved equal.
12.13.4 Where splicing is necessary, either at end of existing tracer wire or along
new tracer wire, use splice kit, Scotchcast, 3M Company, or approved
equal.
12.13.5 Extend tracer wire along new main; terminate wire in tracer wire
receptacle box mounted on to each fire hydrant; secure to hydrant break
flange; receptacle box: AA Manufacturing Tracer Wire Receptacle Model
TW-18-2.
12.14 Water services not to be installed in granular bedding material at crossings of
sewer pipes and structures.
Water Mains and Appurtenances
7-12
13. VALVE INSTALLATION
13.1 When water main is installed in proposed or existing street right-of-way, install
valves at street intersections as shown on Standard Drawing; isolate pipe
serving each block.
13.2 Install with stems vertical and centered in manhole or box, as shown on
Standard Drawing.
13.3 Check all valve bolts when installed; tighten as necessary after valves are in
operation and up to operating pressure.
13.4 Support valves in manholes or boxes as required.
13.5 Carefully tamp earth around each valve box or manhole to distance of 4' on all
sides of box or manhole or to undisturbed trench face, if less than 4'; install as
shown on Standard Drawing.
14. HYDRANT INSTALLATION
14.1 Install plumb; set at elevation so that cover will not be less than for adjacent main;
set grade mark on hydrant barrel at finished ground level; install as shown on
Standard Drawing.
14.2 Set on concrete foundation; backfill with 3/4" washed gravel as shown on
Standard Drawing.
14.3 Carefully tamp backfill around hydrant to a distance of 4' on all sides of hydrant
or to undisturbed trench face, if less than 4'.
14.4 Tighten all stuffing boxes as hydrant is installed; operate hydrant in open and
closed position to assure all parts are in working condition.
14.5 Block hydrant in place with poured in place concrete thrust block.
14.6 Wrap hydrant barrel, minimum 8 mils thickness polyethylene encasement;
AWWA C105.
15. RAILROAD AND HIGHWAY CROSSINGS
15.1 Tunnel casing pipe in place; length of casing pipe and method of installation as
required by IDOT or railroad.
Water Mains and Appurtenances
7-13
15.2 Install ductile iron water main in casing pipe as soon as casing pipe is installed.
15.3 Do not stockpile or store excess material or debris in right-of-way.
15.4 Tunnelling as specified in PIPE EXCAVATION AND BACKFILL.
16. STREET CROSSINGS
16.1 Auger or directional bore water main or service pipe under shared use paths,
driveways, concrete pavement and curb and gutter except when stipulated
otherwise in writing by City; no casing pipe required.
16.2 Meet requirements as specified in PIPE EXCAVATION AND BACKFILL.
17. CREEK CROSSINGS
17.1 A minimum cover of five feet shall be provided over pipe.
17.2 See Standard Drawing for creek crossing for water main.
18. TESTS
18.1 Water test all piping after installation in accordance with AWWA C600 and C605.
18.2 Hydrostatic and leakage testing:
18.2.1 Flush out main before test to remove air; insert taps to release
trapped air.
18.2.2 Test at 1.5 times working pressure or 150 psi, whichever is greater, at
point of test for 2 hours; allowable pressure drop during test period:
5 psi.
18.2.3 Measure water loss by pumping from drum or by similar means.
18.2.4 Maximum allowable leakage (L) in gallons per hour:
L = (S)(D)(P)1/2
148,000
S = length in feet of section under test.
D = pipe diameter in inches.
P = average test pressure, psig.
Water Mains and Appurtenances
7-14
18.2.5 Provide all test pumps, test plugs, pipe and gauges; make all required
piping connections.
18.2.6 Examine trench for leakage during test; replace all defective pipe and
fittings that do not pass leakage test; repeat test until requirements have
been met.
18.2.7 Maximum test length is 1,000 feet.
19. DISINFECTION
19.1 Disinfect and sample prior to placing main in service; AWWA C651.
19.2 Disinfect by injecting a solution of calcium hypochlorite and water at slow rate to
provide minimum residual chlorine content of 25 mg/l not more than 10'
downstream of new water main; allow system to stand full of solution for
24 hours.
19.3 Minimum free chlorine residual at pipe extremities: 10 mg/l at end of test period;
if requirement is not met, repeat disinfection procedure.
19.4 Operate all valves and hydrants in new main to assure full disinfection; repeat test
procedure if necessary.
19.5 Thoroughly flush main after test until extremities indicate same chlorine residual
as supply water.
19.6 Dispose of chlorinated water to prevent damage to the environment; AWWA C655.
Chemically dechlorinate water or store water until chlorine residual is non-
detectable (<0.10 mg/l) before releasing into the ground or storm sewers. Disposal
not allowed into sanitary sewers.
19.6.1 Collect a minimum of 3 grab samples evenly spaced over course of
Discharge.
19.6.2 Test each sample within 15 minutes of the sample being collected for
chlorine residual.
19.6.3 Stop discharge if chlorine is detected in any test until subsequent test
shows chlorine is non-detectable.
Water Mains and Appurtenances
7-15
19.7 After final flushing, and before the water main is placed in service, two samples shall
be collected from the end of the main and tested for bacteriologic quality and shall
show the absence of coliform organisms. One set of samples shall be collected every
1,200 linear feet of pipe, plus one set from the end of the line and at least one from
each branch greater than one pipe length. There are two options for bacteriological
testing:
19.7.1 Option A: take an initial set of samples and then resample again after a
minimum of 16 hr using the sampling site procedure. Both sets of samples
must pass for the main to be approved for release.
19.7.2 Option B: let water main sit for a minimum of 16 hr without any water use.
Then collect, without flushing the main, two sets of samples a minimum of
15 min apart while the sampling taps are left running. Both sets of samples
must pass for the main to be approved for release.
19.7.3 Samples shall be collected in sterile bottles treated with sodium
thiosulfate. No hose or fire hydrant shall be used in the collection of
samples unless approved by City.
19.7.4 If the disinfection fails to produce satisfactory samples, disinfection shall be
repeated until satisfactory samples have been obtained.
19.7.5 After the second set of failed samples, additional water used shall be
charged to the Contractor at the retail rate for water usage.
8-1
PART 8 – STRUCTURAL CONCRETE AND REINFORCING STEEL
INDEX
1. GENERAL 5. MIXING, PLACING, PROTECTING
2. CONCRETE MATERIALS AND CURING
3. CONCRETE QUALITY 6. FINISHING
4. FORMS 7. REINFORCING STEEL
8. WIRE FABRIC
1. GENERAL
1.1 This part of the specifications includes all concrete and reinforcing steel placed
on project site except portland cement concrete paving for streets, driveways
and sidewalks.
2. CONCRETE MATERIALS
2.1 Portland cement: ASTM C150, Type I or Type III.
2.2 Aggregates: strong, durable, uniformly graded mineral grains conforming with
ASTM C33.
2.2.1 Fine aggregate: Gradation within requirements of ASTM C33,
Par. 3; natural or manufactured sand; clean, hard, strong, durable,
uncoated grains; maximum coal and lignite: 1.0%.
2.2.2 Coarse aggregate: Gradation within requirements of ASTM C33, Table II
#57, 1” to No. 4.
2.2.2.1 Crushed limestone: meet IDOT specifications 4115.03
for abrasion and 4115.04 for Class 2 or 3 durability; not more
than 1.0% of clay lumps and friable particles, 2.0% of soft
particles and 0.25% of coal and lignite allowed; prove
acceptability by submission of certified laboratory test report.
2.3 Storage:
2.3.1 Cement: keep clean, dry and free from weather damage.
2.3.2 Aggregates: stockpile each gradation separately on clean, non-
contaminating surfaces.
2.4 Water: clean and free from injurious materials; ASTM C94.
Structural Concrete and Reinforcing Steel
8-2
2.5 Admixtures: applicable sections of ASTM C94, C260, C494 and C168.
2.5.1 Fly ash: Class C.
2.5.2 Use of calcium chloride not permitted.
2.6 Non-shrink: Embeco by Master Builders Company, Alcoa, or approved equal.
2.7 Waterstops:
2.7.1 Polyvinylchloride with following characteristics when tested in
accordance with ASTM test method listed.
Specific Gravity 1.32 plus or minus 0.05 ASTM D792
Hardness 76 plus or minus 3 ASTM D2240
Tensile Strength 2250 psi (minimum) ASTM D638
Elongation 350% (minimum) ASTM D638
Cold Brittleness -35oF. or lower ASTM D476
2.7.2 Design: 6”, ribbed with corrugations and center bulb, except where shown
otherwise; Greenstreak Type 705, or equal.
2.7.3 Expansive waterstop may be used for vertical construction joints and
where approved by City Engineering Department; Volclay Waterstop-RX,
Greenstreak Hydrotitle, or equal.
2.8 Bonding Agent:
2.8.1 Epoxy bonding agent shall be a two-component, solvent-free, moisture
insensitive, epoxy resin material confirming to ASTM C884 (1999), Type V.
The bonding agent shall be Sikadur 32 Hi-Mod by Sika Corporation of
Lyndhurst, NJ; Concresive Liquid (LPL) by Master Builders of Cleveland, OH
or equal.
Structural Concrete and Reinforcing Steel
8-3
3. CONCRETE QUALITY
Class A Class B
3.1 Minimum compressive strength:
psi at 28 days 4,000 2,500
3.2 Maximum water-cement ratio:
pound per pound, including water
in aggregates 0.45 0.45
3.3 Minimum cement content: pound
per cubic yard 560 420
3.4 Slump: maximum 4" with no addition of water reducing admixture; with water
reducer; slump per manufacturer's recommendations; ASTM C143.
3.5 Air content: 6.5% with a maximum variation of –1.0% and +1.5% by volume air
entrained for the air content of fresh, unvibrated structural concrete; ASTM
C231.
3.6 Admixtures: manufacturer's recommendations.
3.7 Fly ash: Class C; maximum 15% replacement, pound for pound for specified
cement content, between and including April and October.
3.8 Concrete mix design: meet approval of City Engineering Department prior to
placement.
3.9 Use Class A concrete unless shown or specified otherwise; use Class A concrete
for fill, thrust blocks and to anchor sign posts.
4. FORMS
4.1 Form all concrete, unless permitted otherwise by City.
4.2 Use metal or plywood-lined forms for exposed surfaces; erect true to line and
grade; brace and tie securely.
4.3 Coat forms with non-staining mineral oil before placing reinforcing.
Structural Concrete and Reinforcing Steel
8-4
4.4 Strip forms only after concrete has cured for the following periods:
Footings 24 hours.
Walls 48 hours.
Self-supported beams and slabs 2 weeks.
5. MIXING, PLACING, PROTECTING AND CURING
5.1 Provide accurate control for measuring materials
5.2 Mix until mass is homogeneous and uniform in color.
5.3 Ready-mixed concrete: conform with specifications and with ASTM C94.
5.4 Clean and dampen forms, reinforcing steel and embedded items: transfer concrete
promptly from mixer to forms; thoroughly compact by tamping or vibrating.
5.5 Prevent segregation during placing; do not drop concrete more than 5'.
5.6 Place concrete continuously in each section until complete; permit not more than
30 min. between depositing adjacent layers of concrete within each section.
5.7 Thoroughly compact, puddle and vibrate concrete into corners and around
reinforcing and embedded items.
5.8 Place sections of concrete in sequence which eliminates effect of shrinkage to
greatest extent practicable.
5.9 Do not finish concrete with bleed water present on surfaces; do not over-finish.
5.10 Surfaces: float to uniform finish with cork float; use edger on exposed edges.
5.11 Immediately after finishing or stripping forms, apply continuous cover of
polyethylene film; thickness: 0.004"; minimum lap: 6".
5.11.1 Keep film in place for 7 days.
5.12 Maintain concrete temperature between 60°F. and 90°F. when placing and
not less than 50°F. for 72 hours after placing.
5.13 Do not place concrete when storm or inclement weather is approaching or when
air temperature is 38°F. or less and falling, or when darkness prevents good
workmanship.
Structural Concrete and Reinforcing Steel
8-5
6. FINISHING
6.1 Patching:
6.1.1 Chip out honeycomb to sound concrete.
6.1.2 Fill with patching mortar: one part portland cement, three parts sand.
6.1.3 Fill holes left by form ties with non-shrink grout to within 1" of surface; fill
with patching mortar.
6.1.4 Where existing concrete has been removed, patch uneven surfaces with
patching mortar.
7. REINFORCING STEEL
7.1 Billet steel bars: ASTM A615, Grade 60.
7.2 Bend cold to conform with required details; bend bars in fabricating
shop before delivery to site.
7.3 Space properly and tie securely in position before placing concrete; tie with
minimum No. 18 tie wires as directed by City Engineer.
7.4 Lap bars 48 diameters, minimum.
7.5 Remove scale, rust, dirt or other coatings which may impair bond; comply with
ACI 318.
7.6 Install reinforcing steel in correct position with preformed wire bar bolsters and
spacers.
7.7 Place concrete only after reinforcing system is in place and approved by City
Engineering Department; install reinforcing system plumb and true; tie securely:
reinforcing must remain in proper position without distortion or displacement
of individual bars or system during pour.
7.8 All reinforcing steel epoxy coated; IDOT Section 4151.03B.
8. WIRE FABRIC
8.1 Electrically welded wire fabric: ASTM A185.
Structural Concrete and Reinforcing Steel
8-6
8.2 Sizes and mesh: as shown on plans for Standard Drawing.
8.3 Place securely when show on plans or Standard Drawing.
8.4 Lap fabric not less than 6".
8.5 Remove scale, rust, dirt and other bond-impairing materials.
9-1
PART 9 - SURFACE RESTORATION AND PAVEMENT REPLACEMENT
INDEX
1. GENERAL 5. SIDEWALK AND SHARED USE PATH 2. SURFACE RESTORATION REMOVAL AND REPLACEMENT 3. SODDING 6. STREET AND DRIVEWAY SURFACE 4. SEEDING REMOVAL AND REPLACEMENT
7. PUBLIC SAFETY
1. GENERAL
1.1 This part of specifications includes surface restoration and removal and
replacement of existing sidewalks, shared use paths, driveways, streets and
parkings by subdivider, utility companies and others in public rights-of-way and
easements.
1.2 Submit plans of proposed construction for approval and acceptance by City;
notify City Engineering Department in advance of performing work in public
right-of-way.
1.3 Locate utilities parallel to right-of-way lines as shown on Standard
Drawing unless otherwise approved by City.
1.4 Unless otherwise specified on plans, restore surfaces and replace pavement to
conform with existing grade and cross section prior to construction.
1.5 Prepare subgrade or subbase and finish grade as specified in EARTHWORK AND
INCIDENTALS FOR PAVEMENT.
1.6 Sod all grassed surfaces disturbed with nursery sod as specified herein, unless
seeding is approved by City.
2. SURFACE RESTORATION
2.1 Furnish all materials, equipment and labor necessary to seed, sod, replace
damaged flowers, shrubbery and trees and perform complete surface
restoration on land not owned by subdivider to original or better condition.
2.2 Excavate and backfill trench and holes for utility installation and repair in
accordance with specifications.
2.2.1 Backfill trenches and holes below street and driveway pavement full
depth to bottom of pavement with IDOT 3/4” Class A granular backfill
material.
Surface Restoration and Pavement Replacement
9-2
2.3 Surface restoration including replacement of plantings, seeding and sodding: use
competent subcontractor experienced in this type work.
2.4 Replace topsoil and fine grade all areas disturbed by construction.
2.5 Dispose of all brush and rubbish as directed by City Engineering
Department.
3. SODDING
3.1 Sod areas which are disturbed by construction; extent and locations subject to
approval of City.
3.2 Place new 1-1/2" Kentucky Bluegrass nursery sod; secure approval of City for
new sod; field sod not acceptable.
3.3 Water thoroughly initially; keep damp until growth is well established.
3.4 Do not sod between June 15 and August 15 unless permitted by City
Engineering Department.
3.5 Do not lay frozen sod. Do not lay sod on frozen soil or when freezing conditions
are forecasted within 24 hours.
3.6 Provide two applications of fertilizer in accordance with SUDAS Standard
Specifications.
3.7 Replace sod areas where 50% of the grass fails to grow within 1 year of
placement.
4. SEEDING
4.1 Seed areas in public right-of-way, other than parkings, which are disturbed by
construction, if approved by City.
4.2 Prepare site for seeding by discing, harrowing and hand raking or other means
following site grading; work soil to depth of 3". Remove all rock from seed bed.
Surface Restoration and Pavement Replacement
9-3
4.3 Precede seeding with uniform application of commercial grade fertilizer at rate
and grade in accordance with SUDAS Standard Specifications; cultivate area 3"
deep and work with harrow within 24 hours before seeding; smooth surface to
eliminate clods and lumps before seeding.
4.4 Seed mixture: Type 1 in accordance with SUDAS Standard Specifications unless
otherwise permitted by City Engineering Department.
4.5 Seed between dates of August 10 and September 30 or between dates of March
1 and May 30. Do not seed on frozen soil.
4.6 Cover seed by rolling with cultipacker, or by dragging or hand raking.
4.7 Mulch all areas subject to erosion and where directed by City Engineering
Department; mulch in accordance with SUDAS Standard Specifications.
4.8 Water seeded area sufficiently to saturate seed bed.
4.9 Replant or redevelop any bare spots or areas which do not attain a full stand
during first growing season.
4.10 Seed areas within IDOT right-of-way in accordance with IDOT Standard
Specifications.
4.10.1 Include fertilizer and mulch; maintain as stated hereinbefore.
5. SIDEWALK AND SHARED USE PATH REMOVAL AND REPLACEMENT
5.1 Removal: saw cut and remove shared use paths and sidewalks, at joints, as
required to accommodate construction.
5.2 Replacement: match existing construction for type, width, thickness,
reinforcement and surface texture. Minimum thickness 4 inches.
5.2.1 Reconstruct joints to match existing work.
5.2.2 Concrete: Class C-4 or M-4 in accordance with IDOT specifications.
Surface Restoration and Pavement Replacement
9-4
5.2.3 Provide truncated dome warning panels at junction of handicapped
sidewalk ramps and street pavement; provide at location directed by
City where sidewalk abuts gravel roadways and other roadways without
curb and gutter sections; truncated domes as specified in PORTLAND
CEMENT CONCRETE PAVEMENT. Replace as originally designed.
6. STREET AND DRIVEWAY SURFACE REMOVAL AND REPLACEMENT
6.1 Saw cut and remove portland cement concrete or hot mix asphalt pavement on
lines parallel to or perpendicular to centerline of pavement.
6.1.1 Make saw cuts only at locations of existing joints in portland cement
concrete pavement or at locations approved by City Engineering
Department.
6.1.2 Minimum pavement replacement area 1’ wider than the trench on all
sides.
6.2 Reinstall driveway and road culverts; if culverts are damaged during
construction, replace with new, identical size and type.
6.3 Replace street and driveway surfaces:
6.3.1 Portland cement concrete pavement: match existing surface texture;
thickness 1” thicker than existing pavement; minimum 8" thickness of
new pour for streets; 6" minimum thickness of new pour for driveways.
6.3.2 Hot mix asphalt (HMA) pavement: replace with portland cement
concrete pavement; depth of pavement specified hereinbefore.
6.3.3 Seal coat or low grade asphalt surfacing: replace with portland cement
concrete pavement; depth of pavement specified hereinbefore.
6.3.4 Granular surfacing: match existing surface; depth of surfacing specified
hereinafter.
6.4 Portland cement concrete pavement replacement:
6.4.1 Subgrade: provide approved, selected material; compact to 95%
maximum density; 12" minimum thickness.
6.4.2 Place new concrete slab 1" thicker than existing slab; minimum 8"
thickness of new pour for streets.
Surface Restoration and Pavement Replacement
9-5
6.4.3 Vibrate, screed, float, drag and finish to match existing surface texture.
6.4.4 Concrete: Class M-4 in accordance with IDOT specifications.
6.4.5 Concrete curb and gutter: form and construct curb and gutter with
mechanical equipment; finish curbs by hand methods with straight edge or
slipform where necessary to produce uniform finish.
6.4.6 Use Type C joints, for pavement thicknesses 8” or less and Type CD joints for
pavements thicknesses greater than 8”; use RD joints at existing pavement;
seal joints; saw as specified herein; joint types in accordance with SUDAS
Standard Specifications.
6.5 Gravel or crushed stone:
6.5.1 Place in 6" of compacted crushed stone to width of existing street or
driveway; conform to IDOT Class A crushed stone; place and compact in
2 lifts.
6.5.2 Place additional compacted crushed stone beyond width of existing street
or driveway to restore to existing condition; minimum thickness: 2".
7. PUBLIC SAFETY
7.1 Provide temporary fence or cover excavated trench or hole during periods when
construction and testing activity has ceased.
7.1.1 Provide barricades and flashers in accordance with Iowa Manual on
Uniform Traffic Control Devices to warn motorists and pedestrians when
light intensity is less than 0.9 foot-candles.
10-1
PART 10 – PORTLAND CEMENT CONCRETE PAVEMENT
INDEX
1. GENERAL 8. CURING AND PROTECTION
2. MATERIALS 9. RESTRICTIONS
3. STORAGE AND PROTECTION OF MATERIALS 10. DEFECTS
4. PROPORTIONS FOR MIX 11. DRIVEWAY APPROACH, SHARED USE
5. MIXING PATHS AND SIDEWALK CONSTRUCTION
6. EQUIPMENT REQUIREMENTS 12.
PAVEMENT MARKINGS
7. PAVEMENT CONSTRUCTION 13. SHOULDERS
1. GENERAL
1.1 This part of the specifications includes construction of portland cement concrete
pavement with integral curb, driveway approaches, shared use paths and sidewalks,
using preset forms on prepared subgrade or subbase.
1.1.1 Prepare subgrade or subbase as specified in EARTHWORK AND
INCIDENTALS FOR PAVEMENT.
1.1.2 Construct non-reinforced or reinforced pavement as agreed upon
between City and subdivider and as specified in DESIGN STANDARDS; use
portland cement concrete as specified herein.
1.1.3 Install joints in accordance with SUDAS Standard Specifications Figures PV-
101, 7010.904 and 7010.905 except on Sheet 3 of Figure PV-101 replace
Note No. 11 with “Sawing and sealing of joint is required.”
1.1.4 Construct driveway approaches, sidewalks and shared use paths as
specified hereinafter.
1.1.5 Construct railroad crossing approaches in accordance with SUDAS
Standard Specifications Figure 7010.903.
1.1.6 Construct boxouts for intakes in accordance with SUDAS Standard
Specifications Figure SW-514, Sheet 1.
1.2 Non-reinforced portland cement concrete pavement includes CD baskets as
required, deformed tie bars on longitudinal joints, expansion joints and dowels; see
Standard Drawings.
Portland Cement Concrete Pavement
10-2
1.3 Reinforced portland cement concrete pavement includes joint reinforcement and
dowels and deformed bar reinforcing throughout remainder of pavement; see
Standard Drawing.
1.4 Use slip form paving machine for all uniform width street pavements 150’ or more
in length, unless alternate methods are approved by the City Engineering
Department. Mechanical screeds may be used on short pavement runs up to 150’.
Place, consolidate, and finish the concrete to the full depth and width conforming
to the specified crown and cross-section in a single operation. Pavement cannot be
paved in short sections just to meet the requirements above.
1.5 City will stamp location of sump pump drain line with the symbol "S" lying on its
side, water service with the symbol "W" or sanitary sewer service with the symbol
"S" in front face of fresh concrete during pavement construction.
1.6 Electronic concrete tickets are required.
2. MATERIALS
2.1 Portland cement: ASTM C150, Type I.
2.2 Admixtures:
2.2.1 Air entraining: ASTM C260; no admixtures containing chlorides will be
permitted.
2.2.2 Retarding: a suitable retarding admixture may be used during hot
weather, with approval of City Engineering Department.
2.2.3 Other admixtures may be used, subject to approval of City Engineering
Department.
2.2.4 Only use compatible admixtures per manufacturer’s recommendation.
2.3 Fine aggregate:
2.3.1 Clean, hard, durable particles of natural sand, free from injurious
amounts of silt, shale, coal, organic matter or other deleterious
substances.
2.3.2 Deleterious substances: not more than 2.0% shale and coal by weight
retained on No. 16 sieve.
Portland Cement Concrete Pavement
10-3
2.3.3 Organic matter: other than coal, not more than standard reference
color; ASTM C40.
2.3.4 Conform to Gradation No. 1 of the Aggregate Gradation Table in the
Appendix of the IDOT Standard Specifications for Highway and Bridge
Construction.
2.3.5 Percent passing one sieve and retained on next higher number sieve not
more than 40% when sieved through 4 and 8 numbered sieves.
2.3.6 Mortar strength at 7 days not less than 1.5 times standard sand strength;
IDOT Laboratory Test Method 212.
2.4 Coarse aggregate:
2.4.1 Clean, hard, durable particles of crushed stone free from injurious
amounts of objectionable materials; Class 3 durability crushed stone;
IDOT 4115.01.
2.4.2 Objectionable materials not more than:
Materials Percent
Clay lumps 0.5
Coal and carbonaceous shale 0.5
Sticks (wet weight) 0.1
Total of all shale and coal combined 1.0 Organic material other than coal and sticks 0.0
Unsound chert particles retained on
3/8" sieve 3.0
2.4.2.1 Chert particles breaking into three or more pieces in freezing
and thawing test, IDOT Laboratory Test Method 211, Method A,
are considered unsound.
2.4.3 Conform to Gradation No. 4 of the Aggregate Gradation Table in the
Appendix of the IDOT Standard Specifications for Highway and Bridge
Construction.
2.4.4 Percent of wear, AASHTO T96, Grading A or B, not to exceed 35 for gravel,
50 for crushed stone which contains 90% or more calcium carbonate or 45
for all other crushed stone.
2.4.5 Particle durability: aggregate considered durable when it has no adverse
affect upon durability of concrete in which used; minimum percent of
durable particles in aggregate: 95; durability based on following:
Portland Cement Concrete Pavement
10-4
2.4.5.1 That loss in freezing and thawing test, IDOT Laboratory Test
Method 211, Method A, does not exceed 6%.
2.4.5.2 Behavior of existing concrete containing aggregate of similar
geological origin or chemical and mineral composition.
2.5 Water: clean and clear, free from salt, oil, acid, strong alkalis, vegetable matter, or
other substances injurious to concrete.
2.5.1 Water may be heated for cold weather paving operations; anti-freezing
agents not permitted.
2.6 Reinforcing:
2.6.1 Steel deformed bars: ASTM A615, Grade 40; epoxy coated.
2.6.2 Plain and smooth steel dowel bars: ASTM A615, Grade 40; epoxy
coated.
2.6.3 Glass fiber reinforced polymer dowel bars: Comply with IDOT 4156.
2.7 Expansion tubes: Comply with IDOT 4191.01.B.
2.8 Metal keyways: Comply with IDOT 4191.01.A.
2.9 Supports for reinforcing bars:
2.9.1 Support tie bars as required to place and maintain correct location
during construction.
2.9.2 Support dowel bars at expansion joints as shown on SUDAS Standard
Specifications Figure PV-101.
2.10 Joints:
2.10.1 Bituminous joint filler and sealer: hot poured joint filler; comply with IDOT
4136.02.A.
2.10.2 Preformed expansion joint filler: asphalt saturated fiber strips; AASHTO
M213; furnish in strips of plan dimensions.
Portland Cement Concrete Pavement
10-5
2.11 Liquid curing compound: white pigmented compound: IDOT Section 4105.
2.12 Plastic film: opaque, white pigmented polyethylene plastic, 0.00085"
minimum thickness, use only once if less than 0.0034" thick.
2.13 Fly ash: Class C permitted as substitute for portland cement; comply with
requirements of IDOT Standard Specifications and Supplemental
Specifications for portland cement concrete proportions. Fly ash is not
allowed after October 15 unless authorized by City. If fly ash is approved
after October 15, the SUDAS Standard Specifications maturity curve
requirement will be followed.
2.14 Slag is not allowed in any mix design.
3. STORAGE AND PROTECTION OF MATERIALS
3.1 Aggregates:
3.1.1 Store fine and coarse aggregate in separate stockpile: avoid
contamination of aggregates.
3.1.1.1 Place fine aggregate with more than 5.0% moisture in
separate stockpile and allow to drain.
3.1.2 Stockpile coarse aggregate and unscreened gravel in horizontal layers;
maximum depth: 4'.
3.1.3 Handle aggregates to avoid frequent variations in specific gravity, sieve
analysis or moisture content.
3.1.3.1 Prevent variations of more than 0.5% in moisture content
of aggregates in successive batches.
3.1.4 Coarse aggregate having absorption greater than 0.5%: wet 1 hour
before use.
3.1.5 Place fine aggregate in proportioning bin only when uniform content can
be maintained in successive batches for one day's run.
3.2 Cement:
3.2.1 Store cement in suitable weatherproof structure; prevent loss of cement
during handling.
Portland Cement Concrete Pavement
10-6
3.2.2 Use cement containing lumps only after careful screening through
20 mesh screen; retest in accordance with ASTM C150 before use.
4. PROPORTIONS FOR MIX
4.1 Mix proportions for street pavement, drive approaches and parking areas
adjacent to street pavement.
4.1.1 Basic absolute volumes of materials per unit volume of concrete
per IDOT 2301.02:
C-4
M-4
Cement Minimum 0.118 0.156
Water 0.159 0.161
Entrained Air 0.060 0.060 Fine Aggregate 0.331 0.311 Coarse Aggregate 0.332 0.312
4.1.2 Above quantities based on specific gravity of cement: 3.14; specific
gravity of aggregates: 2.65; air voids: 6.0%.
4.1.3 Use C-4 mix unless otherwise shown on plans or directed by City
Engineering Department.
4.2 Proportion adjustments:
4.2.1 Basis: when actual quantity of concrete is more than 101% or less than
99% of calculated quantity or if combination of materials does not
produce quality of concrete specified.
4.2.1.1 Fine aggregate: not to exceed 50% of total aggregate in any
adjustment.
4.2.1.2 Do not exceed maximum water-cement ratio specified.
4.3 Water quantity and concrete consistency:
4.3.1 Use proper amount of mixing water to produce concrete of uniform
consistency; adapt to mix, characteristics of materials used, methods of
consolidation, weather conditions and slope of finished surface.
Portland Cement Concrete Pavement
10-7
4.3.2 Modify proportion if maximum water-cement ratio does not produce
workability; increase cement to aggregate proportion to produce specified
degree of workability without exceeding maximum water-cement ratio.
4.4 Tests on trial batches and concrete placed at project site:
4.4.1 Slump: ASTM C143; 1-1/2" to 3" for machine finished concrete; 4",
maximum, for hand finished concrete.
4.4.2 Air voids, of fresh concrete, by pressure method: ASTM C231; 8.0% +/- 2.0%
for machine placed pavement and 7.0% +/- 1.5% for hand placed pavement.
4.4.3 Minimum compressive strength: ASTM C39; 3,000 psi when tested at 7 days
and 4,000 psi when tested at 28 days.
4.4.4 Quantity of compression cylinders as specified in GENERAL CONDITIONS;
cast, protect and cure cylinders in accordance with ASTM C31.
4.4.5 City will allow use of IDOT IM383 method of test for maturity to
determine time for opening pavement to traffic.
5. MIXING
5.1 Batch mix:
5.1.1 Handle batches and charge mixer to insure complete introduction of batches
separately without loss of materials; add water with other materials.
5.1.2 Maximum batch volume:
Mixer Size Volume of Batch
Designation CF of Mixed Concrete
16E 17.6
27E 29.7
34E 37.4
5.1.2.1 For other size mixers, do not allow batch volume of mixed
concrete to exceed mixer size designation number.
5.1.2.2 Size designations: as shown in Concrete Mixer Standards of
Mixer Manufacturers Bureau of Associated General Contractors
of America, Inc. in effect at time of manufacture of mixer.
Portland Cement Concrete Pavement
10-8
5.1.3 If uniform concrete cannot be produced with maximum batch volume;
reduce batch volume and/or increase mixing time.
5.2 Ready-mix:
5.2.1 Applies to either central plant-mixed concrete or central
plant-proportioned, truck-mixed concrete.
5.2.2 Time lapse from addition of water until placing on subgrade: not to exceed
30 min. when concrete is hauled in nonagitating trucks; 1-1/2 hours when
hauled in truck mixers or agitating trucks.
5.2.2.1 Provide reliable reset-revolution counter on truck mixer.
5.2.3 Place concrete in plastic and workable condition; do not retemper
partially hardened concrete.
6. EQUIPMENT REQUIREMENTS
6.1 Batch or ready-mix plant: IDOT 2001.06, 2001.20 and 2001.21.
6.1.1 Automatic cut-off gates at cement batching scale not required.
6.1.2 Certified scales and measuring devices.
6.2 Concrete mixing equipment: IDOT 2001.21.
6.3 Forms, form-line excavating machine, consolidating and finishing equipment, slip
form paving equipment and equipment for hand methods: IDOT 2301.03.A.3.
7. PAVEMENT CONSTRUCTION
7.1 Setting and removing forms:
7.1.1 Set forms accurately to required grade and alignment on properly
compacted subgrade or subbase.
7.1.1.1 For forms to support mechanical subgrader, mechanical
spreader, mechanical finisher or other similar heavy
equipment, excavate with machine designed to shape subgrade
for forms.
Portland Cement Concrete Pavement
10-9
7.1.2 Set base of forms at or below subgrade elevation and with top of form at
pavement surface elevation at edge of slab.
7.1.2.1 Extra height forms may be used to back up integral curb; set
base at or below subgrade elevation and top of form at top of
curb elevation.
7.1.2.2 Comply with IDOT 2301.03.C for additional excavation and
concrete if base of form is set below subgrade elevation.
7.1.3 Secure forms in place to maintain grade and alignment while concrete is
placed and finished.
7.1.3.1 If voids occur under forms, remove forms and bring
subgrade to proper elevation as specified in EARTHWORK
AND INCIDENTALS FOR PAVEMENT.
7.1.3.2 Check form joints with 10' straight edge; adjust forms to
proper grade and alignment.
7.1.4 If supporting soil becomes softened by rain or standing water so form is
inadequately supported, reset form on suitable material before placing
concrete.
7.1.5 Oil forms before concrete is placed; prevent adherence of concrete.
7.1.6 Leave side forms in place not less than 6 hours after concrete is placed.
7.1.6.1 If form removal causes damage to concrete, leave
remaining forms in place longer than 6 hours, as required.
7.1.7 Remove forms with care to prevent cracking, spalling or overstressing
concrete; remove form stakes prior to raising forms.
7.1.8 Clean forms before resetting.
7.2 Concrete and bar placement:
7.2.1 Uniformly moisten subgrade or place plastic film, specified hereinbefore,
on prepared subgrade or subbase; lap plastic film 12", minimum.
7.2.2 Adjust manholes and other castings within area to be paved to conform to
finished surface; clean outside of casting.
Portland Cement Concrete Pavement
10-10
7.2.3 Place reinforcing, dowel and tie bars as shown on plans or specified;
secure in position by approved method. Hand placement of dowels and
tie bars into wet concrete not allowed.
7.2.4 Place concrete to full depth of pavement in single operation for plain
pavement or pavement reinforced with deformed bars; do not pile
concrete more than 8" above design elevation of surface.
7.2.4.1 Allow no segregation of material when concrete is deposited
on subgrade.
7.2.5 Carefully place concrete; minimize disturbance of reinforcement.
7.2.6 Vibrate; do not displace or distort reinforcement.
7.2.7 If 2’ or less of earthen cover is provided between bottom of pavement and
top of sewer pipe, use #4 epoxy coated bars in a 2’ x 2’ spaced grid within
concrete panel over sewer.
7.2.8 Ensure concrete is delivered at a rate sufficient to maintain a sustained rate
of progress no less than 100 feet per hour for the width and depth of slab
to be placed. The City reserves the right to suspend paving operations if the
specified rate cannot be met.
7.3 Finishing:
7.3.1 Begin finishing operations promptly after concrete has been placed and
consolidated.
7.3.2 Screed surface to grade and crown shown on plans.
7.3.3 Finish surface with 10' long lightweight float; finish from both sides
simultaneously if pavement is placed to full width of street with one pass
of paving machine; finish gutter area and curbs as specified hereinafter.
7.3.4 Provide uniformly gritty surface with burlap; round edges of pavement to
1/8" radius.
7.3.5 Check pavement surface with 10' long straightedge; maximum
permissible deviation: 1/8"; grind high spots, over 1/8", with
carborundum grinding wheel.
Portland Cement Concrete Pavement
10-11
7.4 Integral curb:
7.4.1 Construct 6" integral curb, as shown on SUDAS Standard Specifications
Figure PV-102, along with pavement or immediately following finishing of
pavement; use paving machine with integral slip-forms for curb, curb
mule or similar mechanical equipment providing equivalent results.
7.4.2 Construct depressed curb where sidewalks intersect street and at driveways
constructed prior to pavement; use templates to form faces of such curbs.
7.4.2.1 Mill and remove 6" integral curb at sidewalks and driveways
constructed after pavement. Sidewalks to meet Americans
with Disabilities Act (ADA) and Public Right of Way Access
Guidelines (PROWAG).
7.4.3 Form and construct curb by hand only where barrier or depressed curb is
required, where curb length is less than 150’ and where small radii or other
special sections preclude use of mechanical equipment. Curb cannot be
paved in short sections just to meet the requirements above.
7.4.3.1 Construct curb as rapidly as finishing operations on pavement
permit; maximum distance behind paving machine: 100'.
7.4.3.2 Remove free water, laitance, dust, leaves or other foreign
matter prior to placing concrete for curb.
7.4.3.3 Use freshly mixed concrete; do not store concrete in
receptacles at side of street for use in curb at a later time; do
not use concrete requiring retempering.
7.4.3.4 Secure bond with paving slab and eliminate rock pockets.
7.4.3.5 Forms: IDOT 2301.03.A.3.
7.4.4 Secure final finish on curbs by hand method, including 6' straight edge
or 6' slipform.
7.4.5 Edge, protect and cure curb in same manner as pavement.
7.4.6 Check surfaces of curb and gutter with 10' straight-edge; correct
variations greater than 1/8"; remove and replace curbs having varying
cross section if directed by City.
Portland Cement Concrete Pavement
10-12
7.4.7 Provide expansion joint in curb over expansion joint in pavement; saw cut
face and top of curb to depth of 3" over contraction joint in pavement
and seal as specified hereinafter.
7.4.8 If curb is damaged by subsequent construction operations, saw cut, remove
and replace as shown on Standard Drawing. Minimum length replaced is
length of curb and gutter panel.
7.5 Construct joints as shown on Standard Drawings; seal as specified hereinafter.
7.5.1 Round edges of concrete adjacent to header boards and expansion
joint material to 1/8" radius.
7.5.2 Provide supplemental vibration adjacent to header boards and expansion
joint material as required.
7.5.3 Begin saw cutting as soon as concrete can be sawed without objectionable
tearing of sawed edges; complete such work under reasonable weather
conditions within 18 hours after concrete is placed.
7.5.4 For adverse weather, end of day's work or when 30 min. elapse between
concrete placement, install header board and 3/4" smooth dowels 1'-3" long
at 1'-0" spacing through header board; grease protruding ends prior to next
concrete placement.
7.5.5 ‘CD’ joints shall be used in gutterline joints to within 12” of the back of the
curb. Early entry saw cutting can be used for ‘CD’ joints.
7.5.6 Keyway tie (KT) joints are not allowed without prior approval by City.
7.6 Seal all joints before pavement is opened to Contractor's forces or general traffic;
seal only dry and clean joint surfaces; slightly under-fill joints, keep sealer off of
adjacent pavement.
7.6.1 Heat joint sealer to required temperature in thermostatically controlled
heating kettle, do not overheat.
8. CURING AND PROTECTION
8.1 Apply liquid curing compound in fine spray to form continuous, uniform film on
surface and vertical edges of pavement and curbs.
Portland Cement Concrete Pavement
10-13
8.1.1 Apply compound with power sprayer, operating at 40 psi or less; rate of
application: 0.067 gal. per square yard (1 gal. per 15 SY); do not dilute
compound.
8.1.2 Apply to pavement surface after finishing and after surface moisture has
disappeared; apply to pavement edges within 30 min. after forms are
removed.
8.2 Protect concrete pavement in place for less than 36 hours during cold weather
as follows:
Forecast or Actual
Temperature Protection
35° to 32°F. One layer burlap.
31° to 25°F. Two layers burlap or one layer
burlap under one layer plastic
film.
Below 25°F. Four layers burlap between layers of 4
mil plastic film or equivalent
commercial insulating material
approved by the City.
8.2.1 Burlap: AASHTO M182, Class 3.
8.2.2 Commercial insulation blankets may be substituted for burlap when
approved by City Engineering Department.
8.2.3 Protect insulation from disturbance by wind; leave in place for 5 days,
minimum, or until pavement is opened to traffic.
8.2.4 Lap plastic film 18" at junctions.
8.2.5 Have materials available, near the worksite, for cold weather
protection as specified for temperature below 25o F. for all
concrete placed after November 15.
8.3 Concrete damaged by rain or freezing: remove and replace.
8.4 Protect concrete pavement during hot weather in accordance with SUDAS Standard
Specifications Section 7010, Paragraph 3.05.A.2.
Portland Cement Concrete Pavement
10-14
9. RESTRICTIONS
9.1 Weather:
9.1.1 Place no concrete when stormy or inclement weather prevents good
workmanship, when subgrade is frozen, if air temperature is 38°F. or below
or evaporation rate is 0.3 pounds per square foot per hour or greater; use
no aggregates containing frozen lumps.
9.1.2 With favorable weather conditions, start paving operations when
temperature of concrete delivered to subgrade is 40°F. or higher.
9.1.3 Continue paving operations as long as concrete temperature requirement
is met and air temperature remains above 38°F.
9.2 Night operation:
9.2.1 Place no concrete when darkness prevents good workmanship in placing
and finishing.
9.2.2 Unless specifically approved by City Engineering Department, do not place
or finish concrete under artificial light.
9.3 Use of pavement:
9.3.1 Time for opening pavement for use will be determined by results of test on
cylinders taken during concrete placement or from testing of in place
concrete using IDOT IM383 maturity method; City Engineering Department
reserves the right to require use of test cylinders only.
9.3.2 Pavement may be opened to Contractor's forces and light equipment after 7
days for purpose of removing coverings and building shoulders if tests of
cylinders from section show compressive strength of 3,000 psi or higher.
9.3.3 Open pavement to general traffic when authorized by City Engineering
Department.
9.3.4 Concrete placed in cold weather may require additional curing time, as
directed by City Engineering Department; keep all vehicles off pavement
until such curing time has been completed.
Portland Cement Concrete Pavement
10-15
10. DEFECTS
10.1 Pavement containing fractures, spalls, more than one random crack per
panel, one random crack within 2’ of a joint, or other defects: remove and
replace at no cost to City; rout and seal random cracks; saw cut and epoxy
cement tie bars at 30” centers transverse to crack where crack is 1/8” or
wider.
10.2 Water ponding deeper than 1/8” in gutter: remove and replace panel, or
grind gutter in adjacent panels to drain; City reserves the right to select
method of correcting defects at no cost to City.
10.3 Remove and replace pavement if mud or mud balls appear.
10.4 Pavement thickness: determined by random cores as determined by the City
Engineering Department; one 4" dia. core taken for each section of approximately
1,000 SY with a minimum of 3 cores per project. Cores, if required to be taken, at
no cost to City.
10.5 Restore core holes by tamping non shrink cement grout into hole, finishing and
texturing surface.
10.6 If concrete cores taken are less than the specified thickness, remove and replace
pavement at no cost to City; deficient thickness pavement will not be accepted.
10.7 Area represented by each core is one-half of distance to next core or to end of
pavement.
10.8 Additional core samples may be made and measured at Contractor's expense to
determine the extent and severity of pavement deficiency; minimum distance
between core samples: 100'.
11. DRIVEWAY APPROACH, SHARED USE PATHS AND SIDEWALK CONSTRUCTION
11.1 Conform to details shown on Standard Drawing for new driveway approaches
and sidewalks; prepare subgrade as specified under EARTHWORK AND
INCIDENTALS FOR PAVEMENT.
11.2 Constructed shared use paths and sidewalk drop curbs to meet Americans
with Disabilities Act (ADA) and Public Right of Way Access Guidelines
(PROWAG).
Portland Cement Concrete Pavement
10-16
11.3 Construct drop curb in existing pavement for driveways as shown on Standard
Drawing.
11.3.1 Mill to provide smooth uniform surface for approach.
11.3.2 Remove concrete curb and gutter section and replace with depressed
curb as shown on Standard Drawing.
11.3.3 Remove and replace unacceptable drop curbs as directed by City
Engineering Department.
11.4 Concrete materials:
11.4.1 Portland cement, admixtures, fine aggregate and water; as specified for
pavement.
11.4.2 Coarse aggregate: as specified for pavement.
11.5 Concrete mix: as specified for pavement for IDOT C-4 mix proportions; test in
accordance with ASTM C39; 28 day compressive strength: 4,000 psi, minimum.
11.6 Forms: use wood or steel forms adequately staked and braced for all exposed slab
edges; secure forms in place to maintain grade and alignment while concrete is
placed and finished.
11.6.1 Set base of form at subgrade elevation or below with top of form at
pavement surface elevation at edge of slab; set forms on properly
compacted materials.
11.6.2 Oil forms before concrete is placed.
11.6.3 Leave forms in place not less than 24 hours after concrete is placed.
11.6.4 Remove forms with care to prevent cracking, spalling or
overstressing concrete.
11.7 Concrete placement: as specified for pavement; provide supplemental vibration or
spading at edges, joints and other areas where honeycombing may occur.
11.8 Screed to uniform lines; finish surface with wood or cork float.
11.9 Construct expansion joints as shown on Standard Drawing; seal joints after concrete
has cured; use applicable materials specified for pavement expansion joints.
Portland Cement Concrete Pavement
10-17
11.10 Cure and protect driveway approaches and sidewalks as specified for pavement.
11.11 Restrictions on construction and use of pavement apply to driveway approaches
and sidewalks.
11.12 Provide raised truncated dome concrete detectable warning panels at ramps
in compliance with Americans with Disabilities Act (ADA) and Public Right of
Way Access Guidelines (PROWAG). At each ramp location provide 2' wide
strip, minimum 5' long measured parallel to curb and along back of curb; for
wider ramps, extend warning panels full width of ramp; provide cast iron
panels with natural finish.
12. PAVEMENT MARKINGS
12.1 Meet requirements of Section 2527, except method of measurement and basis
of payment, of the IDOT Standard Specifications for Highway and Bridge
Construction.
12.2 Meet requirements of Manual on Uniform Traffic Control Devices (MUTCD).
12.3 Materials: durable paint pavement markings; IDOT 4183.04.
13. SHOULDERS
13.1 Install shoulders on rural section streets as shown on Standard Drawing.
13.2 Conform to IDOT Class A crushed stone.
11-1
PART 11 – KETTLESTONE STREET LIGHTS
INDEX
1. GENERAL 4.
CABINET AND CONTROLLER
2. DESIGN STANDARDS 5. POLES AND LUMINAIRES
3. UNDERGROUND PRODUCTS
1. GENERAL
1.1 This part of the specifications includes details for street lighting installed within the
Kettlestone corridor shown in Exhibit No. 2 following PART 11 – KETTLESTONE STREET
LIGHTS.
2. DESIGN STANDARDS
2.1 All lighting within the Kettlestone corridor shown in Exhibit No. 2 following PART 11 –
KETTLESTONE STREET LIGHTS shall conform to the standards in the Kettlestone Design
Guidelines and the specifications in this section.
2.2 All lighting on private property including lighting for buildings, parking lots and private
streets shall conform to the City of Waukee Site Plan Ordinance.
2.3 All lighting on public streets shall conform to the design standards contained in the
SUDAS Design Manual and the following standards:
2.4 Poles:
2.4.1 All new street light poles and appurtenances installed within the clear zone
of any public street right-of-way shall be of a design to break-away when hit
by a vehicle. The break-away design shall conform to the definitions of the
U.S. Department of Transportation.
2.4.2 Street light poles shall be placed near all intersections, outside the sight
triangle, for proper lumination of the intersection.
2.4.3 Locate poles in a straight line 3-feet to 6-feet behind the back of curb. Install
poles plumb.
2.5 Fixtures:
2.5.1 All fixtures shall be full cut-off (no sag lenz).
Kettlestone Street Lights
11-2
2.5.2 All fixtures shall be supported by MidAmerican Energy unless otherwise
approved by the City as a part of a development agreement related to
special development characteristics of a subdivision.
2.5.3 Mounting height shall be 30 feet.
2.6 Provide photometric plan identifying all pole locations and project lighting levels with
foot-candle measurements at 10’ increments.
2.7 In cases where a homeowners association is created for a particular subdivision and
includes the responsibility of on-going maintenance of street light poles and fixtures, a
street lighting design utilizing unique poles and fixtures may be approved at the
discretion of the City.
2.8 Street light design shall incorporate existing City infrastructure.
2.9 Street light pole spacing shall be as follows:
2.9.1 25’ Back to Back with Luminaires 4-ft Offset
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P35-60L4K 180 0.37 1.85 0.37
Alt2P35-96L4K 175 0.57 1.54 0.39
Alt2P70-60L4K 186 0.60 1.94 0.38
Alt2P70-96L4K 202 0.90 2.81 0.40
Alt3P35-60L4K 153 0.40 1.74 0.32
Alt3P35-96L4K 184 0.58 1.76 0.39
Alt3P70-60L4K 193 0.54 2.45 0.38
Alt3P70-96L4K 194 0.96 3.00 0.39
2.9.2 25’ Back to Back with Luminaires 6-ft Offset
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P35-60L4K 180 0.37 1.85 0.40
Alt2P35-96L4K 161 0.63 1.58 0.38
Alt2P70-60L4K 180 0.63 1.91 0.39
Kettlestone Street Lights
11-3
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P70-96L4K 224 0.81 3.86 0.49
Alt3P35-60L4K 158 0.40 1.60 0.37
Alt3P35-96L4K 169 0.65 1.63 0.39
Alt3P70-60L4K 177 0.60 2.07 0.38
Alt3P70-96L4K 194 1.01 3.16 0.40
2.9.3 29’ Back to Back with Luminaires 4-ft Offset
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P35-60L4K 180 0.37 1.85 0.40
Alt2P35-96L4K 173 0.58 1.53 0.39
Alt2P70-60L4K 226 0.49 4.08 0.50
Alt2P70-96L4K 233 0.76 4.75 0.50
Alt3P35-60L4K 158 0.40 1.74 0.35
Alt3P35-96L4K 169 0.65 1.76 0.39
Alt3P70-60L4K 174 0.60 1.76 0.39
Alt3P70-96L4K 196 1.00 3.23 0.39
2.9.4 29’ Back to Back with Luminaires 6-ft Offset
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P35-60L4K 180 0.37 1.85 0.40
Alt2P35-96L4K 159 0.62 1.59 0.40
Alt2P70-60L4K 226 0.49 4.08 0.53
Alt2P70-96L4K 160 1.11 1.68 0.38
Alt3P35-60L4K 180 0.36 2.40 0.39
Alt3P35-96L4K 165 0.69 1.64 0.40
Alt3P70-60L4K 180 0.60 2.22 0.39
Alt3P70-96L4K 185 1.09 2.95 0.40
Kettlestone Street Lights
11-4
2.9.5 31’ Back to Back with Luminaires 4-ft Offset
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P35-60L4K 108 0.62 1.94 0.28
Alt2P35-96L4K 165 0.60 1.54 0.40
Alt2P70-60L4K 165 0.66 1.74 0.39
Alt2P70-96L4K 173 1.02 1.65 0.40
Alt3P35-60L4K 105 0.60 1.82 0.29
Alt3P35-96L4K 165 0.68 1.79 0.39
Alt3P70-60L4K 180 0.59 2.19 0.38
Alt3P70-96L4K 189 1.05 2.84 0.40
2.9.6 31’ Back to Back with Luminaires 6-ft Offset
Fixture Max
Spacing
(ft)
Average
Illuminance
(fc)
(min=0.4)
Uniformity
Ratio
Eave/Emin
(min=6.0)
Veiling
Luminance
Ratio Lmax/Lavg
(min=0.4)
Alt2P35-60L4K 108 0.61 1.91 0.29
Alt2P35-96L4K 150 0.65 1.67 0.40
Alt2P70-60L4K 150 0.72 1.80 0.38
Alt2P70-96L4K 157 1.12 1.70 0.40
Alt3P35-60L4K 108 0.60 1.88 0.29
Alt3P35-96L4K 150 0.77 1.67 0.38
Alt3P70-60L4K 150 0.72 1.67 0.38
Alt3P70-96L4K 187 1.09 2.87 0.40
3. UNDERGROUND PRODUCTS
3.1 Handholes:
3.1.1 General:
3.1.1.1 Cable Hooks: Provide four galvanized steel cable hooks with a
minimum diameter of 3/8 inch and a minimum length of
5 inches.
Kettlestone Street Lights
11-5
3.1.1.2 Granular Base: Comply with the following gradations; however,
the Engineer may authorize a change in gradation, subject to
materials available locally at the time of construction.
Sieve Percent Passing
2” 100
1 1/2” 80 to 90
1” 15 to 20
3/4” 0 to 0.5
3.1.1.3 Cover: Include “LIGHTING”, as shown on the plans, as a message
on the cover.
3.1.2 Precast Concrete Handhole:
3.1.2.1 Pipe: Comply with ASTM C 76. Minimum Class III, Wall B
(Iowa DOT Class 2000D). Four, 8 inch knockouts (conduit
entrance points) equally spaced around the handhole.
3.1.2.2 Casting: Gray cast iron and certified according to requirements
of AASHTO M 306 for a 16,000 pound proof-load (HS-20).
3.1.3 Composite Handhole and Cover: Precast polymer concrete handholes shall
be stackable with a minimum depth of 24 inches and an “open” bottom,
unless otherwise specified in the plans. Composed of mortar consisting of
sand, gravel, and polyester resin reinforced by a woven glass fiber mat or
of resin mortar and fiberglass, shall meet or exceed all appropriate
ANSI/SCTE 77 tests and requirements. Ensure the cover satisfies loading
requirements of ANSI Tier 15. Provide a skid resistant surface on the cover.
Provide two 3/8-16 UNC stainless steel hex head bolts with washers.
3.2 Conduit:
3.2.1 General:
3.2.1.1 Furnish weatherproof fittings of identical or compatible
material to the conduit. Use standard factory elbows,
couplings, and other fittings.
Kettlestone Street Lights
11-6
3.2.1.2 Use a manufactured conduit sealing compound that is
readily workable material at temperatures as low as
30°F and will not melt or run at temperatures as high as
300°F.
3.2.2 Steel Conduit and Fittings:
3.2.2.1 Comply with ANSI C80.1, latest revision.
3.2.2.2 Use weatherproof expansion fittings with galvanized,
malleable iron, fixed and expansion heads jointed by rigid steel
conduit sleeves. As an option, the fixed head may be integral
with the sleeve, forming a one piece body of galvanized
malleable iron.
3.2.2.3 Provide steel bushings.
3.2.3 Plastic Conduit and Fittings:
3.2.3.1 PVC:
3.2.3.1.1 PVC Schedule 80 plastic conduit and fittings
complying with NEMA TC-2 (pipe), NEMA TC-3
(fittings), and UL 651 for Schedule 80 heavy wall
type.
3.2.3.1.2 Solvent welded, socket type fittings, except where
otherwise specified in the contract documents.
3.2.3.1.3 Threaded adaptors for jointing plastic conduit to
rigid metal ducts.
3.2.3.1.4 Provide bell end fittings or bushings.
3.2.3.2 HDPE:
3.2.3.2.1 UL Listed, comply with ASTM F 2160 (conduit) and
ASTM D 3350 (HDPE material), SDR 13.5.
3.2.3.2.2 Use red colored conduit or color as specified in the
plans.
Kettlestone Street Lights
11-7
3.2.3.2.3 Continuous reel or straight pieces to minimize
splicing.
3.2.3.2.4 For dissimilar conduit connections, provide an
adhesive compatible with both materials.
3.3 Wiring and Cable: Provide wire that is plainly marked on the outside of the sheath
with the manufacturer's name and identification of the type of the cable.
3.3.1 General:
3.3.1.1 Shall be rated 600 volts minimum.
3.3.2 Power Cable: Comply with Article 4185.12 of the Standard Specifications.
3.3.3 Tracer Wire: Comply with #12 AWG, single conductor, stranded copper,
Type thermoplastic high-heat nylon-coated (THHN), with UL approval, and
an orange colored jacket.
3.4 Footings:
3.4.1 Concrete Footing:
3.4.1.1 Use Class C structural concrete complying with Section 2403 of
the Standard Specifications.
3.4.1.2 Reinforcing steel shall be the type and size as shown on the
plans and shall conform to the requirements of Section 2404 of
the Standard Specifications.
3.4.1.3 Use uncoated reinforcing steel complying with Section 4151 of
the Standard Specifications.
3.4.2 Power Installed Foundation:
3.4.2.1 All material made of steel or iron, hot dipped galvanized
complying with ASTM A 123 or ASTM A 153.
3.4.2.2 Shaft complying with ASTM A 53 Schedule 40, Grade B, or ASTM
A 501 or ASTM A 252 Grade 2.
3.4.2.3 Base Plate complying with ASTM A 36.
Kettlestone Street Lights
11-8
3.4.2.4 Helix complying with ASTM A 29.
3.4.2.5 Pilot complying with ASTM 575.
3.5 Bonding and Grounding:
3.5.1 Provide Type L-1 connector at each pole footing base as shown in Slip Base
detail in Iowa Department of Transportation Standard Road Plan LI-142 –
Electrical Installation (Bases).
3.5.2 Ground Rods: Provide 5/8 inch by 10 foot copper clad, steel ground rod at
each pole and controller footing.
3.5.3 Bonding Jumper or Connecting Wire: Provide #6 AWG bare conductor,
copper wire.
4. CABINET AND CONTROLLER
4.1 Lighting Control Cabinet, and Auxiliary Equipment: Comply with the latest edition of
NEMA TS1 or TS2 standards.
4.1.1 Control Cabinet:
4.1.1.1 Unpainted aluminum cabinet according to NEMA standards.
4.1.1.2 Aluminum cabinet riser with same dimensions as cabinet,
18 inch height and matching finish on the lighting cabinet, as
specified in the contract documents.
4.1.1.3 Maintenance panel on inside of the main door containing the
following test switch.
4.1.1.4 Heavy-duty clear plastic envelope attached to inside wall of
cabinet or cabinet door, for cabinet wiring diagrams, 12 inches
by 18 inches minimum.
4.1.1.5 GFI electrical outlet and lamps in accessible location near the
front of the cabinet. GFI outlet fused separately from main AC
circuit breaker. Two LED cabinet lamps connected and fused
with GFI outlet.
Kettlestone Street Lights
11-9
4.1.1.6 Power protection devices including AC power circuit breakers,
and lightning and surge protectors.
4.1.1.6.1 Main AC line breaker, two pole, nonadjustable,
100A, UL listed.
4.1.1.6.2 Four branch circuit breakers, 2-pole rated for 30A.
4.1.1.6.3 Lightning arrestor/surge protectors capable of
withstanding repeated (minimum of 25)
30,000 ampere surges.
4.1.1.6.4 100A meter socket as specified by local utility.
4.1.1.7 Neatly train wiring throughout the cabinet. Bundle and attach
wiring to interior panels using nonconductive clamps or
tie-wraps.
5. POLES AND LUMINAIRES
5.1 Luminaires
5.1.1 Kim Lighting Altitude Luminaires:
5.1.1.1 Type III light distribution as specified on plans.
5.1.1.2 LED drive current 700mA.
5.1.1.3 240VAC.
5.1.1.4 4000k color temperature.
5.1.1.5 Custom color RAL7043.
5.1.1.6 Photocell receptacle.
5.1.1.7 Warranty 10 years for complete product.
5.1.2 Mounting Hardware:
5.1.2.1 Horizontal slipfitter mounting hardware for 2 inch arm.
Kettlestone Street Lights
11-10
5.2 Poles and Mast Arms:
5.2.1 General:
5.2.1.1 Mast arm length and vertical pole height as specified in the
contract documents.
5.2.1.2 Provide non-shrink grout (complying with Materials I.M. 491.13)
or a rodent guard (complying with Materials I.M. 443.01) for
placement between the pole base and the foundation.
5.2.1.3 Custom color RAL7043.
5.2.2 Pole Design:
5.2.2.1 Designed to support the loading necessary for all lighting
equipment. Capable of withstanding winds up to 80 MPH with a
1.3 gust factor without failure.
5.2.2.2 Continuous tapered, 8” round, aluminum poles with slip base
mounting. Fabricated from 6063-T6 aluminum alloy.
5.2.2.3 Provide a handhole and cover in the pole shaft for cable access.
Secure the cover to the base with simple tools. Hardware to be
corrosion resistant.
5.2.2.4 Provide a 12 foot luminaire mounting arm and 34 inch banner
arm on each pole.
5.2.3 Hardware:
5.2.3.1 Equipped with all necessary hardware and anchor bolts to
provide for a complete installation without additional parts.
5.2.3.2 Anchor bolts complying with ASTM F 1554 Grade 105, hot dip
galvanized and threaded a minimum of 6 inches at one end and
have a 4 inch long, 90 degree bend at the other end.
5.2.3.3 Washers complying with ASTM F 436.
5.2.3.4 Heavy hex nuts complying with ASTM A 563.
Kettlestone Street Lights
11-11
5.2.3.5 All hardware made of steel, hot dipped galvanized complying
with ASTM F 2329, or ASTM B 695, Class 50, Type I, or
electrodeposited coated of the same coating thickness and
designed for this purpose.
5.2.4 wiScape Control:
5.2.4.1 Hubbell Automation wiScape External Fixture Module
(WIR-RME-L) installed at each luminaire using the photocell
receptacle.
EXHIBIT NO. 2
12-1
PART 12 – TRAFFIC SIGNALS
INDEX
1. GENERAL
1. GENERAL
1.1 All traffic signals shall be constructed in accordance with SUDAS standard
specifications Section 8010 – Traffic Signals with the following modifications:
1.2 8010, 1.07 – SPECIAL REQUIREMENTS: Add the following notes:
D. The Contractor shall be responsible for ONE CALL locates of the fiber cables
installed under this project until acceptance of the project by the City. Any
damage as a result of failure to locate the equipment shall be the
responsibility of the Contractor to replace with no additional cost to the City.
E. The Contractor shall coordinate with the City for splice connections of the
fiber into the existing fiber optic system. The Contractor to supply fiber optic
wiring diagram as-built drawings. The Contractor shall maintain accurate
quantities of the splices and terminations at each location during the project.
F. The Contractor shall notify and receive approval from the City prior to any
operational shutdown of any existing traffic signal installation.
G. Contractor shall provide to the City “as-built” drawings that identify all
changes made to the contract plans.
1.3 8010, 2.01 – UNDERGROUND, C. Wiring and Cable: 5. Fiber Optic Cable and
Accessories: q. Fiber Optic Jumpers/Patch Cords: Delete the subsection and
replace with the following:
(a) Six fibers in the single mode fiber optic cable (bundle color and individual
fiber color to be specified by the City) shall be terminated in the distribution
unit with the traffic signal controller cabinet.
(b) Duplex pigtail jumpers shall be used to branch traffic signal controller circuits
from the distribution panel in the cabinet to Ethernet switch.
(c) Length of pigtail jumpers will vary according to distribution panel to Ethernet
switch. Length of jumper should provide for a minimum of 2 feet total slack
between distribution panel and switch connections.
Traffic Signals
12-2
(d) Controller cabinet pigtail jumpers shall consist of factory-assembled patch
cords, each of which shall contain two fibers. Each such fiber shall have an
SC compatible, physical contact connector with ceramic ferrule on one end
(i.e., a total of four SCPC connectors per cord). Each patch cord shall have a
dielectric strength member and a durable outer jacket designed to withstand
handling.
1.4 8010, 2.01 – UNDERGROUND, C. Wiring and Cable: 6. Pull Tape: Add the
following subsection:
6. Pull Tape: Pull tape shall be flat woven lubricated polyester tape with 1,250
lb. pulling strength and 0.5 width.
1.5 8010, 2.01 – UNDERGROUND, E. Bonding and Grounding: 1. Ground Rods:
Delete subsection and replace with the following:
1. Ground Rods: Provide 5/8 inch by 8 foot copper clad, steel ground rod at each
pole and controller footing.
1.6 8010, 2.02 – DETECTION, B. Pedestrian Push Button Detectors: 1. Assembly: Add
the following subsection:
f. Housing shall have a black finish.
1.7 8010, 2.02 – DETECTION, B. Pedestrian Push Button Detectors: 3. Solid State
Pedestrian Push Button (Non-APS): c. Switch Replace with the following:
c. Switch: Solid state rated at 20 million operations minimum with
momentary LED and audible confirmation tone.
1.8 8010, 2.02 – DETECTION: C. Video Detection System: Replace entire subsection
C. with the following:
C. Video Detection System: Video detection shall be Gridsmart video
detection system, latest generation processor with performance
reporting (including turning movement counts), and cameras unless
otherwise specified on the plans, all with a minimum five-year warranty
and support, or approved equal.
Traffic Signals
12-3
1.9 8010, 2.03 – COMMUNICATIONS, A. Traffic Monitoring System: Add the
following notes:
Camera shall be latest version of the Axis Q60-E series with a minimum 1080p
resolution, 0.15 minimum illumination, and IP addressable, or approved equal.
1.10 8010, 2.03 - Communications, A. Traffic Monitoring System: Add the following
subsection:
D. Ethernet Switch: Provide the following:
1. Dymec Model KY-CPXB1604, DIN-Rail Mount with dual power
inputs
a. 20 Port total, with 4x 10Gb Uplink via SFP+, 16 ports
supporting Ethernet 10/100/1000 speeds
b. 16 ports are POE capable and can deliver 30w each
c. Supports managed Layer 3 - OSPFv2, and Layer 2 ERPSv2
2. Provide Din-Rail Mounted External Power Supply. Power Supply
shall be:
a. KY-PS48-120W for intersections with two to four 30w POE
devices
b. KY-PS48-240W for intersections with four to six 30w POE
devices
1.11 8010, 2.04 – CABINET AND CONTROLLER, A. NEMA Controller, Cabinet, and
Auxiliary Equipment, 1. Controller: Delete the section and replace with the
following:
1. Controller: Shall be an Econolite ATCC Cobalt controller with EOS
Software and communication capability.
1.12 8010, 2.04 - CABINET AND CONTROLLER, A. NEMA Controller, Cabinet, and
Auxiliary Equipment, 2. Cabinet: a. Add the following text to the existing
subsection:
Cabinet shall be a McCain 350i ATC Cabinet, High Voltage
Traffic Signals
12-4
1.13 8010, 2.04 – CABINET AND CONTROLLER, A. NEMA Controller, Cabinet, and
Auxiliary Equipment, 2. Cabinet: b. Delete the subsection and replace with the
following:
b. Aluminum cabinet riser with same dimensions as cabinet, 12 inch height
and matching finish on the signal cabinet.
1.14 8010, 2.04 – CABINET AND CONTROLLER, A. NEMA Controller, Cabinet, and
Auxiliary Equipment, 2. Cabinet: Add the following subsections:
k. All fiber optic cable shall be suitably identified inside the cabinet.
l. Included as incidental to Auxiliary Equipment, is any and all
jumpers/pigtail cables, splice trays/enclosures, termination panels to
accommodate the number of terminations per plan, fiber optic
connectors, and fiber breakout kits
1.15 8010, 2.04 – CABINET AND CONTROLLER, B. Uninterruptable Power Supply
Battery Backup System: Delete the entire subsection and replace with the
following:
System shall be Clary Traffic/ITS UPS system with the following components:
1. Control Unit - SP1400LT
2. Communication - SNMP
3. Bypass Switch
4. 2 Lithium Batteries
1.16 8010, 2.04 - CABINET AND CONTROLLER, C. Emergency Vehicle Preemption
System: Delete subsection and replace with the following:
System shall be Opticom GPS EVP system with the following components:
1. Intersection Radio/GPS - GTT 3100
2. Phase Selector - GTT 764
3. Interface Panel - GTT 768
4. Cable - GTT 1070
1.17 8010, 2.05 – POLES, HEADS, AND SIGNS, A. Vehicle Traffic Signal Head Assembly,
1. Housing: Delete subsection a. and replace with the following:
a. Individual signal sections made of durable polycarbonate. Color shall be
black and integral to the materials composition.
Traffic Signals
12-5
1.18 8010, 2.05 – POLES, HEADS, AND SIGNS, A. Vehicle Traffic Signal Head Assembly,
7. Mounting Hardware: Add the following to subsection b. Universally
Adjustable:
Banding shall be galvanized steel cable.
1.19 8010, 2.05 – POLES, HEADS, AND SIGNS, B. Pedestrian Traffic Signal Head
Assembly, 1. Housing: Delete subsection a. and replace with the following:
a. Made of a durable polycarbonate. Color shall be black and integral to the
materials composition.
1.20 8010, 2.05 – POLES, HEADS, AND SIGNS, C. Traffic Signal Poles and Mast Arms, 1.
General: Add the following subsection:
i. When a finish color is specified, poles shall be galvanized and
electrostatically painted with a zinc primer and specified finish color, per
supplier specification. All visible connection hardware shall have similar
finish.
1.21 8010, 2.05 – POLES, HEADS, AND SIGNS, D. Pedestal Poles, 1. Materials: Add the
following subsection:
d. When a finish color is specified, pedestal poles and bases shall be
finished with color specified, per supplier specification. All visible
connection hardware shall have similar finish.
1.22 8010, 2.05 – POLES, HEADS, AND SIGNS, E. Traffic Signs: Add the following note:
4. Street name lettering shall be white FHWA Series C with 12 inch
uppercase and lowercase letters on green background.
5. All sheeting material for traffic, street name, and pedestrian signs shall be
3M Diamond Grade DG3.
Traffic Signals
12-6
1.23 8010, 3.01 – UNDERGROUND, B. Conduit, 1. General: Delete subsection a. and
replace with the following:
a. Place conduit to a minimum depth of 30 inches and a maximum depth of
60 inches below the gutterline. When conduit is placed behind the curb,
place to a minimum depth of 30 inches and a maximum depth of 48
inches below top of curb.
1.24 8010, 3.01 – UNDERGROUND, C. Wiring and Cable, 9. Fiber Optic Cable and
Accessories: Delete subsection g. and replace with the following:
g. Provide cable slack in each handhole, junction box, and cabinet as
specified:
Traffic Cabinet 50 feet
Type I, II, III Handhole 50 feet
Type IV Handhole (tub) 100 feet
Where handholes or junction boxes lack sufficient area for cable storage
or bend radius requirements, provide equivalent additional slack in
adjacent facilities. Coil and bind slack cable at three points around the
cable perimeter and support in its static storage position.
1.25 8010, 3.01 – UNDERGROUND, C. Wiring and Cable, 10. Fiber Optic Cable Field
Testing: Utilize with the following exception:
Single mode fiber shall be tested at 1550 ± 30 nanometer wavelength
1.26 8010, 3.03 - COMMUNICATIONS, A. Traffic Monitoring System: Add the following
note:
3. Ethernet Switch: Install inside the traffic signal controller cabinet
according to manufacturer’s recommendations.
1.27 8010, 3.03 – CABINET AND CONTROLLER, A. Controller, Cabinet and Auxiliary
Equipment: Add the following note:
3. This installation includes any and all jumpers/pigtail cables, splice
trays/enclosures, termination panels to accommodate the number of
terminations per plan, fiber optic connectors, and fiber breakout kits.
Traffic Signals
12-7
1.28 8010, 3.07 SURFACE RESTORATION: Add the following subsections:
C. All waste material and debris shall be disposed of at a sanitary landfill as
incidental to the overall project.
13-1
PART 13 - EROSION AND SEDIMENT CONTROL
INDEX
1. GENERAL 3. INSTALLATION
2. DESIGN 4. MAINTENANCE
1. GENERAL
1.1 This part of the specifications includes requirements for erosion and sediment
control during construction. The method of erosion and sediment control and
the materials used for erosion and sediment control during construction must
comply with the Stormwater Pollution Prevention Plan prepared to meet IDNR
General Permit No. 2 requirements. Maintain erosion and sediment control
devices in functional condition from beginning of construction to notice of
discontinuation filed with IDNR and the City.
1.2 Subdivider responsible for hiring persons knowledgeable in preparation of a
Stormwater Pollution Prevention Plan. Subdivider will be the responsible party for
publishing notice of intent as required for IDNR General Permit No. 2. Subdivider
will be responsible party for development, implementation and monitoring for
compliance of the Stormwater Pollution Prevention Plan requirements and IDNR
General Permit No. 2. Subdivider will be responsible for filing the notice of
discontinuation of IDNR General Permit No. 2 after vegetative growth has been re-
established to the required levels of the permit. Subdivider will pay all fees and
pay all fines for permit violation.
1.2.1 Subdivider responsible to provide Construction Site Erosion and Sediment
Control Ordinance (COSESCO) submittals.
1.3 Subdivider responsible for maintaining a copy of the Stormwater Pollution
Prevention Plan and permit for inspection by regulatory agencies.
1.4 Subdivider responsible to coordinate Stormwater Pollution Prevention Plan and
erosion and sediment control activities with other contractors working in same
general area.
1.5 Disturbed areas of the project shall be inspected at intervals in accordance with
IDNR General Permit No. 2. Sudivider is responsible for conducting inspection and
creating a report for each inspection.
1.6 For additional information for appropriate erosion and sediment control measures
see the SUDAS Design Manual and the IDNR Iowa Stormwater Management
Manual.
Erosion and Sediment Control
13-2
2. DESIGN
2.1 Erosion and sediment control design must prevent siltation of downstream
waterways, ponds and detention basins. If downstream on-site detention basin is
utilized as a temporary sediment basin, Subdivider is responsible to restore design
volume and depth of pond in detention basin after completion of activities which
cause siltation including home building.
2.2 Erosion and sediment control design must not place materials on surface of
roadway open to traffic or devices in intakes which can cause flooding of roadways
open to traffic. Surface applied intake protection not permitted.
2.3 Erosion and sediment controls must keep streets, sidewalks and adjacent
properties clear of silt, mud, dirt and debris.
3. INSTALLATION
3.1 Meet requirements of SUDAS Standard Specifications Section 9040-Erosion and
Sediment Control.
3.2 Provide concrete washout to meet SUDAS 10,050.
3.3 Waste from concrete washout and wet sawing of concrete is not allowed to be
discharged to surface waters and is not allowed to adversely affect a water of the
state.
4. MAINTENANCE
4.1 Clean out, repair or reconstruct erosion and sediment control features as
required.
SD-1
STANDARD DRAWINGS
DRAWING
NO. TITLE
1A UTILITY SERVICE LOCATIONS, REV. 1 1B UTILITY SERVICE LOCATIONS, REV. 2 2 GRANULAR ENCASEMENT STANDARD PVC PIPE BEDDING 3 CLASS C BEDDING – GRANULAR TYPE I 4 CLASS B BEDDING – GRANULAR TYPE II 5 CLASS A BEDDING - CONCRETE CRADLE TYPE V 6 CLASS A BEDDING - CONCRETE CRADLE 7 CLASS A BEDDING - CONCRETE ARCH TYPE VII 8 CLASS A BEDDING – CONCRETE ENCASEMENT TYPE VIII 9 HAND SHAPED TRENCH BOTTOM 10A CREEK CROSSING FOR WATER MAIN 10B CREEK CROSSING FOR SANITARY SEWER, REV. 2 11 SPECIAL MANHOLE 12 SHALLOW MANHOLE 13 OUTSIDE DROP CONNECTION 14 INSIDE DROP CONNECTION 15 RISER 16 TYPICAL PAVEMENT CROSS SECTION - 26' PAVEMENT, REV. 2 17 TYPICAL PAVEMENT CROSS SECTION - 29' PAVEMENT, REV. 2 18 TYPICAL PAVEMENT CROSS SECTION - 31' PAVEMENT, REV. 2 19 TYPICAL PAVEMENT CROSS SECTION - 41’ PAVEMENT, REV. 2 20 NOT USED 21 NOT USED 22 NOT USED 23 CURB DETAILS 24 HEADER DETAILS 25 BURIED LUG DETAIL 26 DRIVEWAY APPROACH DETAIL - NEW PAVEMENT 27 DRIVEWAY APPROACH DETAIL - EXISTING PAVEMENT 28 NOT USED 29 HEADWALL DETAIL 30 FLARED END SECTION FOOTING DETAIL, REV. 1 31 CONCRETE FLUME DETAIL 32 SERVICE CONNECTION, REV. 1 33 STANDARD VALVE MANHOLE 34 HYDRANT, REV. 2 35 THRUST BLOCK DETAILS 36 SUMP PUMP DRAIN LINES 37 SUBDRAINS, REV. 4 38A – 38E SUBDIVISION LOT GRADING
39 TYPICAL RURAL PAVEMENT CROSS SECTION, REV. 1
40
TYPICAL RIGHT OF WAY GRADING AT STORM WATER OVERFLOW POINTS
41 STANDARD METER PIT 5/8”, 3/4” & 1” METERS (FOR OFF ROAD USE ONLY) 42 STANDARD METER PIT 1-1/2” & 2” METERS 43 PLASTIC METER PIT 1-1/2” & 2” METERS 44 NOT USED
SD-2
DRAWING
NO. TITLE
45 CONDUIT AND PRECAST HANDHOLES, REV. 2
46
GENERAL FEATURES OF AN ACCESSIBLE SIDEWALK 47 GENERAL SIDEWALK AND CURB RAMP DETAILS 48 CURB RAMPS OUTSIDE OF INTERSECTION RADIUS 49 CURB RAMP FOR CLASS B OR C SIDEWALK 50 ALTERNATIVE CURB RAMP FOR CLASS B OR C SIDEWALK 51 CURB RAMPS FOR CLASS A SIDEWALK 52 DETECTABLE WARNING PLACEMENT 53 WATER SERVICES FOR COMMERCIAL BUILDINGS, REV. 1
54 1” WATER SERVICE COPPER TO STOP BOX/PEX TO HOUSE. REV. 1
°
°
°
±
°
CS
B
-
1
1
/
2
FO
R
D
FORD
FORD
1 1/2" MIPINLET & OUTLET
CO
N
D
U
I
T
I
N
T
R
E
N
C
H
Conduit Depth
Tr
e
n
c
h
4"
m
i
n
.
En
s
u
r
e
b
a
c
k
f
i
l
l
m
a
t
e
r
i
a
l
is
f
r
e
e
o
f
c
i
n
d
e
r
s
,
co
n
c
r
e
t
e
,
o
r
o
t
h
e
r
ru
b
b
l
e
.
2'-0" min.
1"
Fi
n
i
s
h
e
d
P
a
v
e
m
e
n
t
G
r
a
d
e
1"
t
o
3
"
Sk
i
d
R
e
s
i
s
t
a
n
t
Su
r
f
a
c
e
Sk
i
d
R
e
s
i
s
t
a
n
t
Su
r
f
a
c
e
Co
n
d
u
i
t
30" min. to 48" max.
2'
-
0
"
d
i
a
.
St
a
i
n
l
e
s
s
St
e
e
l
B
o
l
t
St
a
i
n
l
e
s
s
St
e
e
l
B
o
l
t
Co
m
p
a
c
t
B
a
c
k
f
i
l
l
M
a
t
e
r
i
a
l
Pu
l
l
S
l
o
t
Pu
l
l
S
l
o
t
Ex
t
e
n
d
8
"
g
r
a
n
u
l
a
r
ba
s
e
6
"
b
e
y
o
n
d
wa
l
l
s
o
f
h
a
n
d
h
o
l
e
.
L
W
L
W
PR
E
C
A
S
T
C
O
N
C
R
E
T
E
H
A
N
D
H
O
L
E
(
T
Y
P
E
I
)
II
I
IV
30
"
17
"
24
"
LO
G
O
HA
N
D
H
O
L
E
D
I
M
E
N
S
I
O
N
S
T
A
B
L
E
(N
O
M
I
N
A
L
)
On
e
P
i
e
c
e
Li
d
(
T
y
p
e
I
l
o
r
I
I
I
)
Tw
o
P
i
e
c
e
Li
d
(
T
y
p
e
I
V
)
TY
P
E
36
"
48
"
24
"
30
"
30
"
36
"
L
W
D
II
Ca
s
t
i
n
g
s
h
a
l
l
h
a
v
e
a
cl
o
s
e
d
p
i
c
k
h
o
l
e
D
PR
E
C
A
S
T
C
O
N
C
R
E
T
E
C
O
M
P
O
S
I
T
E
H
A
N
D
H
O
L
E
Ex
t
e
n
d
8
"
g
r
a
n
u
l
a
r
ba
s
e
6
"
b
e
y
o
n
d
wa
l
l
s
o
f
h
a
n
d
h
o
l
e
.
Co
n
d
u
i
t
E
n
t
r
y
T
h
r
o
u
g
h
Si
d
e
o
f
H
a
n
d
h
o
l
e
1
1
PO
T
E
N
T
I
A
L
C
O
N
D
U
I
T
E
N
T
R
Y
T
H
R
O
U
G
H
B
O
T
T
O
M
O
F
H
A
N
D
H
O
L
E
.
Existing
Sidewalk
Cross Slope Transition
Segment (where necessary)
Curb ramp requirements:
1. Maximum curb ramp slope
of 8.3%, or
Grade Break
Grade Break
Back of Curb
Face of Curb
Pa
r
a
l
l
e
l
Cu
r
b
R
a
m
p
(i
f
r
e
q
u
i
r
e
d
)
1
1
1
2
Special
Shaping
Special
Shaping
Detectable Warning
Key
Turning Space
Curb Ramp
Grass
Perpendicular Curb
Ramp Slope:
6.25% (target)
8.3% (max)
2. Minimum length of 15'-0"
at any constant slope
Match existing
sidewalk cross slope.
3
3
Match pedestrian street crossing slope,
or flatter.
Minimum 5 feet by 5 feet. Target cross
slope of 1.5% with a maximum cross
slope of 2.0%.
Target cross slope of 1.5% with a
maximum cross slope of 2.0%.
Turning
Space
2
DETECTABLE WARNING LOCATION AT RAILROAD CROSSING
4
3
6 6
12"
6.25% (targ
e
t
)
8.3% (max.
)
1 2
Detectable warning
1
6" min.
Edge of Pavement
5
2
3
5
4
6
Key
Turning Space
See Detail A
5
Curb Ramp
Standard Sidewalk
5% max.
Cross Slope
24" Wide (min.)
Detectable Warning
Possible Crossing Arm
(location varies)
Back of Curb
Gutterline
Level
Line
12" expansion joint or KT-2
or BT-3 joint when specified.
When a KT or BT joint is
installed at the back of curb,
provide 12" expansion joint at
front or back of the turning space.
12" (max.)
4" min.
6" min.
18"
Provide a minimum 2 foot width of detectable warning surfaces in the direction of
pedestrian travel across the full width of the curb ramp or turning space, exclusive of
curbs or flares.
Provide a minimum of 6 inches of concrete below the detectable warning panel.
Minimum 5 feet by 5 feet. Target cross slope of 1.5% with a maximum cross slope of
2.0%.
If normal sidewalk elevation cannot be achieved with the perpendicular ramp between
the street and landing due to limited ramp length, provide a parallel ramp to make up
the elevation difference between the landing and the standard sidewalk.
The length of the parallel ramp is not required to exceed 15 feet, regardless of the
resulting slope. Do not exceed 8.3% slope for parallel ramps shorter than 15 feet.
If crossing gate conflicts with location of detectable warning or if pedestrian crossing
gate is provided, place detectable warning panel in advance of the crossing gate.
Locate front edge of detectable warning panel 12 to 15 feet from centerline of nearest
rail. Orient truncated domes parallel to the direction of pedestrian travel.
Parallel Curb RampTurning SpacePerpendicular Curb Ramp
P
a
r
a
l
l
e
l
R
a
m
p
(
i
f
r
e
q
u
i
r
e
d
)
St
a
n
d
a
r
d
Si
d
e
w
a
l
k
1'-
0
"
(typ
.
)
Grade Break
Special Shaping
Parallel Curb Ramp: If normal sidewalk
elevation cannot be achieved with the
perpendicular ramp between the street
and landing due to limited ramp length,
provide a parallel ramp to make up the
elevation difference between the
landing and the standard sidewalk.
The length of the parallel ramp is not
required to exceed 15 feet, regardless
of the resulting slope. Do not exceed
8.3% slope for parallel ramps shorter
than 15 feet.
Turning Space: Target slope of 1.5%
with maximum slope perpendicular to the
travel directions of 2.0%. Minimum 5
feet by 5 feet.
Perpendicular Curb Ramp: Target
running slope of 6.25% with maximum
running slope of 8.3%.
Target cross slope of 1.5% with a
maximum cross slope of 2.0%.
Match pedestrian street crossing cross
slope or flatter.
1
2
3
4
3 3
1
2
4
4
5
5
1
2
3
3
2
1
W
Stan
d
a
r
d
Side
w
a
l
k
1'-
0
"
(ty
p
.
)
1'-0"
(typ.
)
W
Cut panels as required to provide
continuous detectable warning
surface around radius.
Back of Curb
Face of Curb
Para
l
l
e
l
R
a
m
p
(if r
e
q
u
i
r
e
d
)
1
22
W 5'-
0
"
m
i
n
.
Face of Curb
1
2
CLASS A SIDEWALK CURB RAMP
Face of Curb
1
5'-
0
"
m
i
n
.
CLASS A SIDEWALK CURB RAMP ALTERNATIVE
1
5'-0
"
m
i
n
.
5'-0" min
.
5'-0"
m
i
n
.
Varies
3
3
3
Property Line
12" Expansion
Joint Material
Back of Curb
10:1 max
Property Line
12" Expansion
Joint Material
Back of Curb
Key
Curb Ramp
Turning Space
Detectable Warning
Turning Space: Target slope of 1.5%
with maximum slope perpendicular to the
travel direction of 2.0%. Minimum 5
feet by 5 feet (turning spaces may
overlap).
Perpendicular Curb Ramp: Target
running slope of 6.25% with maximum
running slope of 8.3%.
Parallel Curb Ramp: Target running
slope of 6.25% with maximum running
slope of 8.3%. The length of the
parallel ramp is not required to exceed
15 feet, regardless of the resulting
slope. Do not exceed 8.3% for parallel
ramps shorter than 15 feet.
1
2
2
Grade Break
Grade Break
Grade Break
1
1
1
2
Provide a minimum 2 foot width of detectable
warning surfaces in the direction of pedestrian
travel across the full width of the curb ramp or
turning space, exclusive of curbs or flares.
Grade Break
12
"
MI
N
.
D
E
P
T
H
O
F
C
O
V
E
R
PLAN
SECTION
1" BALL COCK
MIN. DEPTH 5'-6"
MAX. DEPTH 7'-0"
12"
(MIN.)
5'
-
6
"
STOP BOX WITH 1" RISER, STAINLESS
STEEL ROD TERMINATED 1'-6" BELOW
FINISH GRADE, & STAINLESS STEEL PIN
WATER MAIN
WATER MAIN
STOP
BOXVALVES TO BE SAME
SIZE AS SERVICE PIPE
METER
SERVICE LINE
PROPERTY LINE
1" CORPORATION TAPPED
AT 45 ABOVE HORIZONTAL.
MIN. DISTANCE OF 18" FROM
PIPEBELL OR OTHER CORPORATION.
12
"
SEE NOTE 1
AWG #12, SOLID, BLUE, SINGLE,
INSULATED, DIRECT-BURIAL
COPPER TRACER WIRE REQUIRED.
FASTEN TRACER WIRE WITH ZIP
TIES EVERY 5 FEET.
1" PEXa PIPE
STOPBOX TO HOUSE
1" TYPE "K"
COPPER PIPE
MAIN TO STOPBOX
1/2" TO 1" GROUND CLAMP (DIRECT BURY)
BURNDY C11D
15-1/4" (FACE TO
FACE OF VALVES)
15-1/4" (FACE TO
FACE OF VALVES)
NOTES:
1.PROTECT WIRE PASSING THROUGH WALL OR SLAB. SUPPORT PIPE PASSING THROUGH WALL
OR SLAB BY ZIP TYING PIPE SECURELY TO ONE OF THE FOLLOWING:
- 1/2" DIAMETER REBAR EMBEDDED THE FULL DEPTH OF THE CONCRETE FLOOR, OR
- 1" SQUARE UNISTRUT PIPE ANCHORED TO THE FLOOR WITH A 1/4" THICK STEEL PLATE, OR
- 1/2" DIAMETER ALL THREAD PIPE ANCHORED TO THE FLOOR WITH A 1/4" THICK STEEL
PLATE
COIL 12" OF
TRACER WIRE