HomeMy WebLinkAbout1993-02-01-Ordinance 2168_Uniform Building Code, Plumbing Backflow ValveORDINANCE NO 2168 AN ORDINANCE TO AMEND CHAPTER 222,THE BUILDING CODE OF THE CITY OF WAUKEE,IOWA,BY ADDING THERETO PROVISIONS TO ESTABLISH A CROSS CONNECTION CONTROL PROGRAM REQUIRING BACKFLOW PREVENTION AS A PART OF THE PLUMBING CODE,AND TO PROVIDE PENALTIES FOR VIOLA- TIONS. BE IT ORDAINED by the Council of the City of Waukee: Section 1.Amendment.Chapter 222.3 (3),Waukee Municipal Code,is hereby amended by adding as (c)thereof,(which shall be referred to as §l003A of the Uniform Plumbing Code)the following: (c)Cross Connection Control-Containment Provisions. 1.Definitions.The following definitions shall apply only to subsection (c)hereof,(Also cited as §l003A, Uniform Plumbing Code).For the purpose of this section, these definitions supersede definitions given elsewhere in this code. a. b. c. Approved backflow prevention assembly for containment.A backflow prevention assembly which is listed by the University of Southern California-Foundation for Cross Connection Control and Hydraulic Research as having met the requirements of ANSI-AWWA Standard C510- 89,"Double Check Valve Backflow-Prevention Assemblies",or ANSI-AWWA Standard C511-89, "Reduced-Pressure Principle Backflow-Prevention Assemblies"for containment.The listing shall include the limitations of use based on the degree of hazard.The backflow prevention assembly must also be listed by the Interna- tional Association of Plumbing and Mechanical Officials. Approved backflow prevention assembly for containment in a fire protection system.A backflow prevention assembly to be used in a fire protection system which meets the requirements of Factory Mutual Research Corporation (FM)and Underwriters Laboratory (UL),in addition to the requirements of paragraph 1 (a)of this section. Auxiliary water supply.Any water supply on or available to the premises other than the water purveyor's approved public water supply such as,but not limited to a private well, pond,or river. d.Containment.A method of backflow prevention which requires the installation of a backflow prevention assembly at the water service entrance. e.Cross connection.Any connection or arrange- ment,physical or otherwise,between a potable water supply system and any plumbing fixture or tank,receptacle,equipment,or device, through which it may be possible for non- potable,used,unclean,polluted,and con- taminated water,or other substance,to enter into any part of such potable water system under any condition. f.Customer.The owner,operator,or occupant of a building or property which has a water service from a public water system,or the owner or operator of a private water system which has a water service from a public water system. g.Degree of hazard.The rating of a cross- connection or water service which indicates if it has the potential to cause contamination or pollution. h.Double check valve backflow prevention assembly.A backflow prevention devise consisting of two independently acting internally loaded check valves,four properly located test cocks,and two isolation valves. i.High hazard cross connection.A high hazard cross connection is a cross connection which may cause an impairment of the quality of the potable water by creating an actual hazard to the public health,through poisoning or through the spread of disease by sewage,industrial fluids,or waste. j.Isolation.A method of backflow prevention in which a backflow prevention assembly is located at the cross connection rather than at the water service entrance. k ,Low hazard cross connection.A low hazard cross connection is a cross connection which may cause an impairment of the quality of potable water to a degree which does not create a hazard to the public health,but which does adversely and unreasonable affect the aesthetic qualities of such potable waters for domestic use. 1.Reduced pressure principle backflow prevention assembly.A backflow prevention device consisting of two independently acting internally loaded check valves,a different pressure relief valve,four properly located test cocks,and two isolation valves. m.Registered technician. to test or semblies and assemblies. backflow prevention assembly A person who is registered by law repair backflow prevention as- report on the condition of those n.Thermal expansion.Volumetric water due to heating resulting pressure in a closed system. increase of in increased o ,Water service.Depending on the context,water service is the physical connection between a public water system and a customer's building, property,or private water system,or the act of providing potable water to a customer. 2.Administrative authority. a.For the purposes of this Section 3 only,the administrative authority is the City Council acting through such persons or agencies the City Council shall designate by Resolution. b.The administrative authority shall have the right to enter,with the consent of the customer or upon the basis of a suitable warrant issued by a court of appropriate jurisdiction,any property to inspect for possible cross-connections. c.The administrative authority may approve training programs for backflow prevention assembly technicians and register backflow prevention assembly technicians who successful- ly complete an approved training program. d.The administrative authority may collect fees for the administration of this program. e.The administrative authority may recognize backflow prevention assembly technicians registered by other administrative authori- ties.This provision shall not be effective during any time that the State of Iowa registers backflow prevention assembly technicians. f.The administrative authority shall maintain records of cross connection hazard surveys,and the installation,testing,and repair of all backflow prevention assemblies installed for containment purposes. g.The administrative authority shall maintain, records of registration of backflow prevention assembly technicians and shall maintain a current list of all backflow prevention assembly technicians registered by the administrative authority.This provision shall not be effective during any time that the State of Iowa registers backflow prevention assembly technicians. 3.New Water Services. a.Plans shall be submitted to the administrative authority for review on all new water services in order to determine the degree of hazard. b.The administrative authority shall determine the type of backflow prevention assembly required for containment based on the degree of hazard. c.The administrative authority shall require the installation of the appropriate backflow prevention assembly for containment before the initiation of water service. 4.Existing Water Services. Upgrade of existing water treated as a new water purposes of Section I003A. b.Within six (6)months after adoption of this ordinance,the administrative authority shall publish and make available to each customer a copy of the standards used to determine the degree of hazard. services services shall be for the a. c.Within three (3)months after publication of the standards,the administrative authority shall,in writing,notify customers whose premises are classified as single family residential of the provisions of this ordinance and shall require compliance therewith. d.Within three (3)months after publication of the standards,customers whose premises are not classified as single family residential shall complete and return to the administrative authority a cross-connection hazard survey to be used to determine the type of containment device. e.The administrative authority shall,on the basis of information received from customers or gathered through on-premise investigations or surveys,determine the type of backflow prevention assembly required by containment based on the degree of hazard. f.within the time frame specified in writing by the administrative authority,the customer shall install a backflow prevention assembly for containment required by the administrative authority. g.For existing water services,the administrative authority may inspect the premises to determine the degree of hazard.When high hazard cross connections are found,the administrative authority shall,at its sole discretion:(1) develop a schedule of compliance which the customer shall follow,or (2)terminate the water service until a backflow prevention assembly for containment required by the administrative authority has been installed. h.Failure of the administrative authority to notify a customer that they are believed to have a high hazard cross connection and that they shall install backflow prevention assemblies for containment in no way releases a customer from the responsibility to comply with all requirements of this section. 5 •Customer. a.The customer shall be responsible for ensuring that no cross connections exist without approved backflow protection within his or her premises starting at the point of service from the public potable water system. b.The customer shall,at his or her own expense, cause installation,operation,testing and maintenance of the backflow prevention assemblies required by the administrative authority. c.The customer shall ensure the administrative authority is provided copies of records of the installation and of all tests and repairs made to the backflow prevention assembly on the approved form within fifteen (15)days after testing and/or repairs are completed. d.In the event of a backflow incident,the customer shall immediately notify the local water supplier,City of Waukee,of the incident and take steps to confine the contamination or pollution. 6.Required Backflow Prevention containment -Water Services. Assemblies for a.An air gap or an approved reduced pressu:;e principle backflow prevention assembly 1S required for water services having one or more cross connections which the administrative authority classifies as high hazard. b.An approved double check valve assembly is required for water services having no high hazard cross connections but having one or more cross connections which the administrative authority has classified as low hazard. 7.Required Backflow Prevention Assemblies Containment -Fire Protection Systems. for a.A reduced pressure principle backflow preven- tion assembly shall be installed on all new and existing fire protection systems which the administrative authority determines to have any of the following: 1.Direct connections from public water mains with an auxiliary water supply on or available to the premises for pumper connection. 2.Interconnections with auxiliary supplies such as reservoirs,rivers,ponds,wells, mills,or other industrial water systems. 3.Use of antifreezes or other additives in the fire protection system. 4.Combined industrial and fire protection systems supplied from the public water mains only with,or without gravity storage or pump suction tanks. 5.Any other facility,connection,or condition which may cause contamination. b.A double check valve assembly will be required for all other fire protection systems.The double check valve shall be required on all new systems at the time of installation and on existing systems at the time that they are upgraded. 8.Registration of Backflow Prevention Assembly Technicians.The prOV1Slons in subparagraphs "a" through "d"of this paragraph shall not be effective during any time that the State of Iowa registers backflow prevention assembly technicians. a.Any person who tests or repairs backflow prevention assemblies shall be registered by the administrative authority. b.Any person who wishes to become a backflow prevention assembly technician must submit the following to the administrative authority in order to meet the registration requirements of the administrative authority: 1.A certificate of completion from a training program approved by the ad- ministrative authority.The training program shall provide at least 40 hours of classroom and practical training which shall include an examination. 2.A fee of $25.00. c.Registrations issued by the administrative authority shall be for a period not to exceed two years and shall expire on December 31st of even numbered years. d.To renew the registration Prevention Assembly Technician the administrative authority: 1.A certificate of completion from a continuing education course approved by the administrative authority. the Backflow must submit to (a)The certificate of completion shall indicate at least 5 contact hours of continuing education on backflow, backflow prevention devices and related topics. (b)The certificate of completion must have been completed within the most .~~~-_._-----------_._----_._-----------~~~---~----------- L~ recent registration period. 2.A fee of $5.00. e.A Backflow Prevention Assembly Technician registered by the State of Iowa shall include his or her registration number on all cor- respondence and forms required by,or as- sociated with this ordinance. 9.Registered Backflow Prevention Assembly Technician Noncompliance. a.The registration of a technician may be revoked or suspended for a period of up to two years for noncompliance with this ordinance. b.Any of the following conditions constitute non- compliance: 1.Improper testing or repair of backflow prevention assemblies. 2.Improper reporting of the testing or of repairs made prevention assemblies. results of to backflow 3.Failure to meet registration requirements. 4.Related unethical practices. 10.Installation of Backflow Prevention Assemblies. a.The required backflow prevention assemblies for containment shall be installed in horizontal plumbing immediately following the meter or as close to that location as deemed practical by the administrative authority.In any case,it shall be located upstream from any branch piping.Installation at this point does not eliminate the responsibility of the customer to protect the water supply system from contaminants or pollution between the backflow prevention assembly and the water main. b.Reduced pressure principle backflow prevention assemblies shall be installed so as to be protected from flooding. c.Reduced pressure principle backflow prevention assemblies shall not be installed in under- ground vaults or pits. d.All backflow prevention assemblies shall be ��-�-�-�----��-�------ protected from freezing. e.If hot water is used within the water system, thermal expansion shall be provided for when installing a backflow prevention assembly for containment. f.Provisions discharge principles a suitable shall be made to convey the of water from reduced pressure backflow prevention assemblies to drain. g.No backflow prevention assemblies shall be installed in a place where it would create a safety hazard,such as but not limited to,over an electrical panel,or above ceiling level. h.If interruption of water service during testing and repair of backflow prevention assemblies for containment is unacceptable to the customer,two backflow prevention assemblies, sized to handle the temporary water flow needed during the time of test or repair,should be installed in parallel piping. i.All backflow prevention assemblies shall be installed so that they are accessible for testing as stated in Section 1003. j.All shut-off valves shall conform with the current edition of the Manual of Cross- Connection Control (University of Southern California)requirements for either baIlor resilient seat gate valves at the time of installation.Ball valves shall be used on assemblies installed in piping two inches and smaller and resilient seat gate valves on assemblies installed in piping larger than two inches. 11.Testing of Backflow Prevention Assemblies. a.Testing of backflow prevention assemblies shall be performed by a registered backflow preven- tion assembly technician.The costs of tests required in the following paragraphs "b" through "e"shall be borne by the customer. b.Backflow prevention assemblies shall be tested upon installation and tested and inspected at least annually. c.Backflow prevention assemblies which are in place,but have been out of operation for more than three months,shall be tested before being put back into operation.Backflow prevention assemblies used in seasonal applications shall be tested before being put into operation each season. d.Any backflow prevention assembly which fails a periodic test shall be repaired or replaced. When water service has been terminated for non- compliance,the backflow prevention assembly shall be repaired or replaced prior to the resumption of water service.l Backflow prevention assemblies shall be retested by a registered backflow prevention assembly technician immediately after repair or replacement. e.The administrative authority may require backflow prevention assemblies to be tested at any time in addition to the annual testing requirement. f.The registered backflow prevention assembly technician shall report the successful test of a backflow prevention assembly to the customer and to the administrative authority on the form provided by the administrative authority within 15 days of the test. g.The administrative authority may require,at its own cost,additional tests of individual backflow prevention assemblies as it shall deem necessary to verify test procedures and results. 12.Repair of Backflow Prevention Assemblies. a.All repairs to backflow prevention assemblies shall be performed by registered backflow prevention assembly technicians. b.The registered backflow prevention assembly technician shall not change the design, material,or operational characteristics of a backflow prevention assembly during repair or maintenance,and shall use only original manufacturer replacement parts. c.The registered backflow prevention assembly technician shall report the repair of a backflow prevention assembly to the customer and to the administrative authority on the form provided by the administrative authority with 15 days of the repair.The report shall include the list of materials or replacement parts used. 13.Water supply interconnections. a.It is unlawful to interconnect,in any manner, the municipal water supply to any other source of water. 14.Customer Noncompliance. a.The water service may be discontinued in the case of noncompliance with section 1003A, [cited as 222.3 (3)(c)]of this ordinance. Noncompliance includes,but is not limited to, the following: 1.Refusal to allow the administrative authority access to the property to inspect for cross connections. 2.Removal of a backflow prevention assembly which has been required by the administra- tive authority. 3.Bypassing of a backflow prevention assembly which has been required by the administrative authority. 4.Providing inadequate backflow prevention when cross connections exist. 5.Failure to install a backflow prevention assembly which has been required by the administrative authority. 6.Failure to test and/or properly repair a backflow prevention assembly as required by the administrative authority. 7.Failure to comply with the requirements of this ordinance. 15.Penalty. In addition to any other remedy provided,any person,firm or corporation violating any provisions of this ordinance shall be guilty of a simple misdemeanor and,upon conviction thereof,shall be punished by a fine not exceeding one hundred dollars ($100.00),or imprisonment not exceeding thirty (30) days,or by both such fine and imprisonment.Each day upon which such violation occurs after notice shall constitute a separate violation. Section 2.Repealer.All ordinances or parts of ordinances in conflict with the provisions of this ordinance are hereby repealed. Section 3.Severability Clause.If any section,provision or part of this ordinance shall be adjudged invalid or unconstitu- tional,such adjudication shall not affect the validity of the ordinance as a whole or any section,provision,or part thereof not adjudged invalid or unconstitutional. Section 4.Effective Date.This ordinance shall be in effect upon its final passage,approval and publication as provided by law. Passed by the City Council of the Ci~y ofLWaukee,Iowa,this 1st day of ~Y~~ry,1993,and approved thlS J§r day of F.eb~u~~=r'1993. r&j~)&;~'r~ 1/MAYOR Attested: Clerk