HomeMy WebLinkAbout2018-10-15-K12 Lush Dental_Site Plan AGENDA ITEM:
CITY OF WAUKEE, IOWA
CITY COUNCIL MEETING COMMUNICATION
MEETING DATE: October 15, 2018
AGENDA ITEM: Consideration of approval of a resolution approving a site plan for Lush
Dental (2505 SE Encompass Drive)
FORMAT: Resolution
SYNOPSIS INCLUDING PRO & CON: Dr. Mike Louscher, requests approval of a site plan to
allow for the construction of two single-story dental office building. The
proposed building is 6,710 square feet in area. The first floor is intended to be
used for the dental clinic. The second floor is intended to be utilized as living
quarters for the clinic owner. The subject property is located south of SE
Tallgrass Lane and west of Grand Prairie Parkway. The proposed project is
located within the Kettlestone master planned area.
The applicant has provided elevations for the proposed building on the site,
which meets the intent of the architectural guidelines within the Site
Development and Building Standards Ordinance and the Kettlestone Design
Guidelines.
FISCAL IMPACT INCLUDING COST/BENEFIT ANALYSIS:
COMMISSION/BOARD/COMMITTEE COMMENT: The Planning and Zoning
Commission reviewed this project at the October 9, 2018 Commission Meeting and
recommended approval subject to remaining staff comments:
Approval of a Site Plan for Lush Dental (2505 SE Encompass Drive)
City Planner, Andy Kass, introduced the request for approval of a site plan for a dental clinic, as made
by the applicant Dr. Mike Louscher. The Subject property is located south of SE Tallgrass lane and
Ease of SE Parkview Crossing Drive, Containing approximately 0.71 acres.
Mr. Kass advised that the project would include the construction of a 6,710 square foot in area Dental
Clinic and second story living quarters for the owner of the practice. The proposed site plan also
identifies the trash enclosure in the southwest corner of the parking lot. Access to the property will be
provided on the west side of the site off of the private Street, SE Encompass Drive. This street will be
extended with future phases of development from SE Tallgrass Lane to Grand Prairie Parkway. Until
that time, a temporary turnaround has been indicated on the out lot to the south for emergency
vehicles.
Mr. Kass advised that public utilities will be extended to the site with storm water detention provided
in the regional detention basin located to the north of the subject property. All landscape, open space,
parking and lighting plans meet the required guidelines for the Kettlestone District.
K12
At this time staff recommends approval of the site plan for Lush Dental subject to any remaining staff
comments.
Commissioner Broderick questioned what the square footage of the living space on the second
floor is. a representative of the applicant advised it is approximately 2,350 square feet.
Commissioner Streit clarified if the intent is for only the owner of the practice to reside there.
Mr. Kass advised that is a provision in the Planned Development.
Commissioner Broderick moved to approve the site plan for Lush Dental (2505 SE Encompass Drive)
subject to any remaining staff comments. Commissioner Hoifeldt seconded the motion. Ayes: Sandie,
Streit, Tietz, Broderick, and Hoifeldt. Nays: None. Motion Carries.
STAFF REVIEW AND COMMENT: The site plan and building elevations comply with all
applicable ordinances and policies. There ae some remaining staff comments
that need to be addressed. Staff is working with the applicant to address the
remaining comments.
RECOMMENDATION: Approve the resolution subject to remaining staff comments.
ATTACHMENTS: I. Proposed Resolution
II. Staff Report
III. Site Plan & Elevations
PREPARED BY: Andy Kass, Senior Planner
REVIEWED BY:
THE CITY OF WAUKEE, IOWA
RESOLUTION 18-
APPROVING THE SITE PLAN FOR LUSH DENTAL (2505 SE ENCOMPASS DRIVE)
IN THE NAME AND BY THE AUTHORITY OF THE CITY OF WAUKEE, IOWA
WHEREAS, the City of Waukee, Dallas County, State of Iowa, is a duly organized Municipal
Organization; AND,
WHEREAS, the City of Waukee Planning and Zoning Commission recommended approval of
the Site Plan for Lush Dental, subject to remaining staff comments on October 9, 2018; AND,
WHEREAS, the Site Plan for Lush Dental is in general conformance with §304 – Site and
Building Development Standards Ordinance of the Waukee Municipal Code; AND,
WHEREAS, the Site Plan for Lush Dental is in general conformance with §301.27(A) –
Landscaping and Open Space Ordinance of the Waukee Municipal Code; AND,
NOW THEREFORE BE IT RESOLVED by the City Council of the City of Waukee, Iowa on
this 15th day of October, 2018 that the Site Plan for Lush Dental is approved subject to remaining
staff comments.
____________________________
William F. Peard, Mayor
Attest:
___________________________________
Rebecca D. Schuett, City Clerk
RESULTS OF VOTE: AYE NAY ABSENT ABSTAIN
Anna Bergman
R. Charles Bottenberg
Courtney Clarke
Shelly Hughes
Larry R. Lyon
PLANNING AND ZONING COMMISSION STAFF REPORT
PROJECT: Lush Dental – Site Plan PREPARED BY: Andy Kass, AICP – Senior Planner
REPORT DATE: October 5, 2018
MEETING DATE: October 9, 2018
GENERAL INFORMATION
Applicant / Owner: Dr. Mike Louscher
Engineer: Nathan Gruver, P.L.A., with ISG
Request: The applicant is requesting approval of a site plan
for a dental clinic.
Location and Size: Property is located south of SE Tallgrass Lane and
east of SE Parkview Crossing Drive, containing
approximately 0.71 acres.
Property Address: 2505 SE Encompass Drive
AREA MAP
ABOVE: Aerial of subject property (outlined in BLUE) in relation to the surrounding area.
October 5, 2018
2 of 3
LAND USES AND ZONING
Location Existing Land Use Comprehensive Plan Current Zoning
Property in
Question
Vacant – Undeveloped Office K-OF (Kettlestone Office) /
PD-1 (Planned
Development Overlay)
North Vacant – Undeveloped Multi-Family Stacked
Medium and Office
A-1 (Agricultural District)
South Vacant – Undeveloped Community Commercial K-RC (Kettlestone Retail
Community District)
East Holmes Murphy Office K-OF (Kettlestone Office
District)
West Kettlestone Ridge
Neighborhood
Single Family Residential R-2 (One & Two Family
Residential District)
HISTORY
The proposed project is located within Kettleview Development that was rezoned in 2018. The overall
development is intended to be a professional office park. The proposed project will be the first phase within
the Kettleview Development.
PROJECT DESCRIPTION
The site plan identifies the construction of a 6,710 square foot dental clinic. The proposed building is two
stories with an overall maximum height of 30-feet. The first floor of the proposed building will be a dental
clinic and the second floor will include living quarters for the owner of the dental practice. The Planned
Development that was approved as part of the rezoning for the Kettleview Development allows for the
second story apartment on this lot. In addition to the proposed building the site plan identifies the proposed
trash enclosure in the southwest corner of the parking lot.
ACCESS AND PARKING
Access to the property will be provided on the west side of the site off of SE Encompass Drive, a private
street. SE Encompass Drive will be extended from SE Tallgrass Lane to just beyond the entrance to the subject
property as part of the first phase of the Kettleview Development. Future phases will extend SE Encompass
Drive to Grand Prairie Parkway. A temporary turnaround has been indicated on the site plan on the outlot to
the south to allow for emergency vehicles a place to turnaround on the site.
A total of 22 parking spaces are required for the site and the site plan identifies a total of 25 parking spaces.
SIDEWALKS/TRAILS
A 5-foot-wide sidewalk will be constructed along the south side of SE Tallgrass Lane as part of the
improvements to the site. Sidewalks will also be provided along one side of the street internal to the
development.
UTILITIES
Utilities to the site will be extended from existing water main and sanitary sewer that is located along SE
Tallgrass Lane. Storm water detention will be provided in the regional detention basin located to the north of
the subject property. The regional detention basin is owned and maintained by the City.
October 5, 2018
3 of 3
LANDSCAPING & OPEN SPACE
A minimum of 25% of the project area is required to be open space. The total amount of open space
proposed is 36%. The plantings shown on the landscape plan meet the minimum requirements of the
Landscape & Open Space Ordinance and the Kettlestone Design Guidelines.
ELEVATIONS
The building is proposed to include glazing, cultured stone, three different varieties of fiber cement paneling,
steel awnings, and metal roofing. The trash enclosure will incorporate the same stone that is proposed on the
building. Proposed elevations are attached for your review. The proposed materials and elevations meet the
requirements of the Kettlestone Design Guidelines. Material samples will be available for review at the
Planning & Zoning Commission meeting.
PHOTOMETRIC PLAN
The site plan includes a photometric plan for the proposed site lighting. A total of two pole mounted lights are
proposed for parking lot lighting. These proposed fixtures comply with the lighting requirements within the
Kettlestone Design Guidelines. In addition to the parking lot lighting the photometric plans identifies 7 pedestrian
level bollards with lighting surround the building. These fixtures comply with the requirements of the Kettlestone
Design Guidelines.
STAFF RECOMMENDATION
Staff recommends approval of the site plan for Lush Dental subject to remaining staff comments.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 G0-TITLE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
TITLE SHEET
G0-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
LUSH DENTAL DEVELOPMENT
WAUKEE, IOWA
PROJECT INDEX:
LEGEND
EXISTING
CITY LIMITS
ACCESS CONTROL
SECTION LINE
QUARTER SECTION LINE
RIGHT OF WAY LINE
PROPERTY / LOTLINE
EASEMENT LINE
CULVERT
WATER EDGE
WETLAND BOUNDARY
WETLAND / MARSH
WATER
FENCE LINE
STORM SEWER
SANITARY SEWER
SANITARY SEWER FORCEMAIN
CONTOUR (MAJOR)
UNDERGROUND TELEPHONE
OVERHEAD ELECTRIC
UNDERGROUND ELECTRIC
UNDERGROUND TV
GAS
UNDERGROUND FIBER OPTIC
CONTOUR (MINOR)
DECIDUOUS TREE
CONIFEROUS TREE
TREE LINE
MANHOLE/STRUCTURE
CATCH BASIN
HYDRANT
CURB STOP
VALVE
UTILITY PEDESTAL / CABINET
POWER POLE
990
989
PROPOSED
CULVERT
STORM SEWER
SANITARY SEWER
WATER
OVERHEAD ELECTRIC
UNDERGROUND ELECTRIC
UNDERGROUND TV
GAS
CONTOUR
MANHOLE
CATCH BASIN
HYDRANT
VALVE
EASEMENT
RIGHT OF WAY
STORM SEWER (PIPE WIDTH)
CONSTRUCTION PLANS FOR:
1015
LOT LINE
SITE IMPROVEMENTS
SANITARY SEWER (PIPE WIDTH)
OWNER:
DR. MIKE LOUSCHER
85 LINDEN DRIVE
MASON CITY, IA 50401
PH: (641) 420-6437
EMAIL: lushdds@gmail.com
PROJECT
.71 ACRES LOCATED DIRECTLY SOUTH OF
TALLGRASS AVE
EXISTING LEGAL DESCRIPTION:
OUTLET "W" IN THE SHOPS OF KETTLESTONE
NORTH PLAT 4, AN OFFICIAL PLAT, NOW
INCLUDED IN AND FORMING A PART OF THE
CITY OF WAUKEE, DALLAS COUNTY, IOWA.
PROPOSED LEGAL DESCRIPTION:
PROPOSED LOT 1 TO BE PLATTED.
ZONED: K-OF (KETTLESTONE OFFICE DISTRICT
/ PD-1 (PLANNED DEVELOPEMENT OVERLAY
DISTRICT)
PROJECT MANAGER: NATHAN GRUVER
EMAIL: nathan.gruver@is-grp.com
DOWNING CONSTRUCTION
ISG PROJECT # 18-22051
PROJECT LOCATION
B.M. ELEVATION=1032.32
BURY BOLT ON FIRE HYDRANT,
EAST SIDE OF GRAND PRAIRIE PARKWAY,
790' NORTH OF S.E. ESKER RIDGE DRIVE.
MANAGING OFFICE:
508 EAST LOCUST STREET
DES MOINES, IA 50309
PHONE: 515.243.9143
DES MOINES OFFICE
SPECIFICATIONS REFERENCE
ALL CONSTRUCTION SHALL COMPLY WITH THE WAUKEE
STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENTS AND
WITH THE 2018 EDITION OF THE STATEWIDE URBAN DESIGN AND
SPECIFICATIONS (SUDAS) FOR PUBLIC IMPROVEMENTS, UNLESS
DIRECTED OTHERWISE.
PROJECT DATUM
HORIZONTAL COORDINATES HAVE BEEN REFERENCED TO THE
NORTH AMERICAN DATUM OF 1983 (NAD83), ZONE 8, ON THE IOWA
REGIONAL COORDINATE SYSTEM, IN U.S. SURVEY FEET.
ELEVATIONS HAVE BEEN REFERENCED TO THE NORTH
AMERICAN VERTICAL DATUM OF 1988 (NAVD 88).
RTK GPS METHODS WERE USED TO ESTABLISH HORIZONTAL AND
VERTICAL COORDINATES FOR THIS PROJECT.
TOPOGRAPHIC SURVEY
THIS PROJECT'S TOPOGRAPHIC SURVEY CONSISTS
OF DATA COLLECTED IN JUNE, 2018 BY LANDMARK
ENGINEERING GROUP.
LOCATION MAP
0
SCALE IN FEET
1000 2000
OVERHEAD UTILITY
UNDERGROUND UTILITY
G0-10 TITLE SHEET
---- 18-22051 G0-10
GRAND PRAIRIE PARKWAYASHWORTH ROAD
INTERSTATE I-80SE WESTOWN PAR
K
W
A
Y
SE TALLGRASS LA
N
E
SE UNIVERSITY AVENUE
SE LA GRANT PARKWAYUTILITY CONTACTS:
1.CITY OF WAUKEE, IA
WAUKEE, IA 50263
515-978-7920
2.ELECTRIC
MID AMERICAN ELECTRIC
515-252-6632
3.WATER SERVICE
CITY OF WAUKEE
515-978-7920
4.SANITARY SEWER
WAUKEE PUBLIC WORKS DEPARTMENT
515-978-7920
5.STORM SEWER
WAUKEE PUBLIC WORKS DEPARTMENT
515-978-7920
6.CITY STREETS
WAUKEE STREETS DEPARTMENT
515-978-7920
7.NATURAL GAS
WAUKEE PUBLIC WORKS DEPARTMENT
515-978-7920
8.TELEPHONE & INTERNET
UNITE PRIVATE NETWORKS
515-321-3336
MEDIACOM
1-877-481-2225
9.CABLE
MEDIACOM
1-877-481-2225
TITLE SHEET
CONSTRUCTION NOTES
PROJECT ESTIMATE & QUANITITIES REFERENCE
SITE DETAILS
SITE DETAILS
SITE DETAILS
SITE DETAILS
SITE DETAILS
SITE DETAILS
C1-30 SWPPP GENERAL INFORMATION & NOTES
C1-40 SWPPP DETAILS
C2-10 EXISTING SITE PLAN
C3-10 PROPOSED SITE PLAN
DRAWING INDEX
G0-10
G0-11
G0-12
C0-30
C0-31
C0-32
C0-33
C0-34
C0-35
21 TOTAL DRAWINGS
N
S
W E
DOWNING
CONSTRUCTION
C3-20 PROPOSED UTILITY SITE PLAN
C5-20 PLANTING NOTES & DETAILS
C4-10 PROPOSED GRADING SITE PLAN
C5-10 PLANTING PLAN
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
PRINTED SIGNATURE
SIGNATURE SIGNATURE DATE
REGISTRATION EXPIRES DATE ISSUED
SEAL
SHEETS COVERED BY THIS SEALPROFESSI
O
N
AL LAND S C A P E ARCHITECTI OWA
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT
PERSONAL SUPERVISION AND THAT I AM A DULY
LICENSED PROFESSIONAL LANDSCAPE ARCHITECT
UNDER THE LAWS OF THE STATE OF IOWA.
NATHAN S.
GRUVER
00655
NATHAN SCOTT GRUVER
06/30/2019 04/16/2015
C3-10, C4-10,
C5-10 & C5-20
PRINTED SIGNATURE
SIGNATURE SIGNATURE DATE
REGISTRATION EXPIRES DATE ISSUED
SEAL
TSIGEWE L
A
NOISSEFORP
RDERIO A NREENIGEI HEREBY CERTIFY THAT THIS ENGINEERING
DOCUMENT WAS PREPARED BY ME OR UNDER MY
DIRECT PERSONAL SUPERVISION AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF IOWA.
SHEETS COVERED BY THIS SEAL
DEREK A.
JOHNSON
20894
DEREK ALAN JOHNSON
12/31/2019 01/30/2012
G0-10 - C4-10
PRE CONSTRUCTION EROSION & SEDIMENT CONTROL PLANC1-10
PROPOSED EROSION & SEDIMENT CONTROL PLANC1-20
C7-10 SITE LIGHTING PLAN & PHOTOMETRIC PLAN
C6-10 PROPOSED TRASH ENCLOSURE
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 G0-TITLE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
CONSTRUCTION
NOTES
G0-11
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
G0-11 CONSTRUCTION NOTES
---- 18-22051 G0-11
1.ALL WORK SHALL BE IN ACCORDANCE WITH OSHA CODES AND STANDARDS. NOTHING INDICATED ON THE DRAWINGS SHALL RELIEVE THE CONTRACTOR FROM
COMPLYING WITH ANY APPROPRIATE SAFETY REGULATIONS.
2.ALL WORK SHALL CONFORM TO THE CONTRACT DOCUMENTS. WHICH INCLUDE, BUT ARE NOT LIMITED TO, THE OWNER - CONTRACTOR AGREEMENT, THE
PROJECT MANUAL (WHICH INCLUDES GENERAL SUPPLEMENTARY CONDITIONS AND SPECIFICATIONS), DRAWINGS OF ALL DISCIPLINES AND ALL ADDENDA,
MODIFICATIONS AND CLARIFICATIONS ISSUED BY THE ARCHITECT / ENGINEER.
3.CONTRACT DOCUMENTS SHALL BE ISSUED TO ALL SUBCONTRACTORS BY THE GENERAL CONTRACTOR IN COMPLETE SETS IN ORDER TO ACHIEVE THE FULL
EXTENT AND COMPLETE COORDINATION OF ALL WORK.
4.ALL PROPERTY PINS SHALL BE PROTECTED FROM GRADING OR OTHER OPERATIONS. ANY PINS DISTURBED SHALL BE RESET AT THE CONTRACTOR'S EXPANSE.
5.THE WAUKEE STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENTS AND 2018 EDITION OF THE STATEWIDE URBAN DESIGN AND SPECIFICATIONS (SUDAS)
SHALL APPLY TO CONSTRUCTION WORK ON THE PROJECT. A FULL IOWA SUDAS SPECIFICATIONS MANUAL CAN BE FOUND ONLINE FOR FREE AT
WWW.IOWASUDAS.COM.
6.WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. NOTIFY ARCHITECT / ENGINEER OF ANY DISCREPANCIES OR CONDITIONS REQUIRING
INFORMATION OR CLARIFICATION BEFORE PROCEEDING WITH THE WORK.
7.THE WORK TO BE ACCOMPLISHED FOR THE CONSTRUCTION OF THIS PROJECT WILL OCCUR ON OWNER'S PROPERTY. THE CONTRACTOR SHOULD CONFINE
OPERATIONS, PEOPLE, AND EQUIPMENT TO THE OWNER'S PROPERTY.
8.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE WASTE AREAS OR DISPOSAL SITES FOR EXCESS MATERIALS NOT TO BE INCORPORATED IN THE
WORK INVOLVED IN THE PROJECT (UNSUITABLE EXCAVATION, WASTE PIPE, ETC.).
9.PUBLIC UTILITY FIXTURES ARE EXISTING WITHIN THE CONSTRUCTION AREA. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY THE OWNERS OF THESE
UTILITIES PRIOR TO THE BEGINNING OF ANY CONSTRUCTION. THE CONTRACTOR SHALL AFFORD ACCESS TO THESE FACILITIES FOR ANY NECESSARY
MODIFICATION OF SERVICES. NO ADDITIONAL COMPENSATION WILL BE ALLOWED TO THE CONTRACTOR FOR ANY INTERFERENCE OR DELAY CAUSED BY SUCH
WORK.
10.SEEDING AND FERTILIZING IS INCLUDED IN THIS CONTRACT. CONTRACTOR SHALL BE RESPONSIBLE FOR GRADING AND PREPARING AREAS DISTURBED BY
CONTRACTOR'S OPERATIONS FOR SEEDING. ALL DEBRIS GREATER THAN GOLF BALL SIZE SHALL BE REMOVED AND AREA SHALL BE RAKED SMOOTH.
CONTRACTOR SHALL NOT DISTURB AREAS OUTSIDE OF THE OWNER'S PROPERTY DURING OPERATIONS AND SHALL MAKE A REASONABLE EFFORT TO NOT
DISTURB AREAS GREATER THEN NECESSARY DURING CONSTRUCTION. AREAS OF NONGERMINATION WILL BE RESEEDED AND REFERTILIZED BY THE
CONTRACTOR. COST IS TO BE CONSIDERED INCIDENTAL.
11.IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY TRAFFIC CONTROL SIGNS, DEVICES, ETC., AND TO PLACE, MAINTAIN, AND REMOVE
SAME AS CONSTRUCTION COMMENCES AND IS COMPLETED IN ACCORDANCE WITH THE CURRENT EDITION OF THE IOWA MANUAL ON UNIFORM TRAFFIC
CONTROL DEVICES FOR STREETS & HIGHWAYS. FAILURE TO COMPLY WITH THIS PORTION OF THE SPECIFICATIONS WILL RESULT IN SUSPENSION OF WORK
UNTIL. THE SITUATION IS CORRECTED. A REDUCTION IN THE LUMP SUM TO BE PAID WILL BE MADE FOR EXCESSIVE NONCOMPLIANCE WITH REQUIRED TRAFFIC
CONTROL. NO WORK SHALL COMMENCE IN ANY GIVEN AREA UNTIL ALL APPROPRIATE TRAFFIC CONTROL IS IN PLACE.
12.THE CONTRACTOR SHALL NOT DISTURB GRASSED AREAS AND TREES OUTSIDE THE CONSTRUCTION LIMITS. TREES AND BUSHES SHALL BE RETAINED AS POSSIBLE.
THE CONTRACTOR WILL NOT BE PERMITTED TO PARK SERVICE VEHICLES AND EQUIPMENT OR USE THESE AREAS FOR STORAGE OF MATERIALS. STORAGE,
PARKING AND SERVICE AREA(S) WILL BE SUBJECT TO APPROVAL OF THE ENGINEER.
13.ALL EXISTING TREES AND BUSHES SHALL BE MAINTAINED AND PROTECTED UNLESS NOTED OTHERWISE. AREAS OF HAND FORMING MAY BE REQUIRED TO
PROTECT TRESS.
14.THE CONSTRUCTION OPERATIONS ARE TO TAKE PLACE IN A RESIDENTIAL AREA. THE CONTRACTOR'S ATTENTION IS DIRECTED TO THE REQUIREMENTS INCLUDED
IN THE SPECIFICATIONS IN REGARD TO POSITIVE DUST CONTROL DURING ALL OPERATIONS TO INCLUDE REMOVAL, CLEAN UP, ETC.
15.CONTRACTOR SHALL PROVIDE BARRICADES AND SIGNS IDENTIFYING VEHICLES AND OBSTACLES IN THE DRIVEN ROADWAYS.
16.FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS, NOTIFY ARCHITECT / ENGINEER OF ANY DISCREPANCIES OR CONDITIONS REQUIRED INFORMATION
OR CLARIFICATION BEFORE PROCEEDING WITH THE WORK.
17.EXISTING STORM SEWERS, SANITARY SEWERS, AND WATER MAINS ARE LOCATED BASED ON CITY RECORDS AND ACTUAL LOCATIONS MAY VARY GREATLY FROM
THAT SHOWN. THE LOCATIONS AND TYPE OF ALL INPLACE UTILITIES SHOWN ON THE PLANS ARE FOR GENERAL INFORMATION ONLY AND ARE ACCURATE AND
COMPLETE TO THE BEST OF THE KNOWLEDGE OF ISG. NO WARRANTY OR GUARANTEE IS IMPLIED. THE CONTRACTOR SHALL VERIFY THE SIZES, LOCATIONS, AND
ELEVATIONS OF ALL INPLACE UTILITIES PRIOR TO CONSTRUCTION. CONTRACTOR SHALL IMMEDIATELY NOTIFY ENGINEER OF ANY DISCREPANCIES OR
VARIATIONS FROM PLAN.
18.CONTRACTOR SHALL REPLACE AND REPAIR ALL EXISTING STORM SEWERS THAT ARE ENCOUNTERED DURING CONSTRUCTION IN ACCORDANCE WITH THE
SPECIFICATION. CONTRACTOR SHALL USE 2000D RCP WITH FLEXIBLE O-RING GASKET JOINTS, PLACE PIPES SO JOINTS ARE NOT DIRECTLY OVER WATER MAIN,
AND RECONNECT TO EXISTING STORM SEWER WITH REINFORCED FERNCO COUPLING.
19.PROPOSED WATER DISTRIBUTION LINE SHALL BE INSTALLED WITH A MINIMUM OF FIVE AND ONE-HALF (5.5') OF COVER. IN LOCATIONS WITH A SEPARATION
DISTANCE OF LESS THAN TEN FEET (10') FROM SANITARY SEWER OR STORM SEWER, THE SANITARY SEWER OR STORM SEWER SHALL BE INSTALLED EIGHTEEN
INCHES (18") BELOW THE BOTTOM OF THE WATER MAIN AND SHALL BE PLACED IN A SEPARATE TRENCH AT A MINIMUM HORIZONTAL SEPARATION OF THREE
FEET PER SUDAS SPECIFICATIONS.
20.AT ALL SANITARY SEWER AND WATER MAIN CROSSOVER, MAINTAIN A MINIMUM OF 18" SEPARATION BETWEEN BOTTOM OF WATER MAIN AND TOP OF
SEWER. PLACE ONE FULL LENGTH OF WATER PIPE, LOCATED SO BOTH JOINTS ARE AS FAR AS POSSIBLE FROM SEWER. USE LOW PERMEABILITY SOIL FOR
BACKFILL WITHIN 10' OF CROSSOVER.
21.THRUST BLOCKS SHALL BE POURED CONCRETE, INSTALLED BEHIND ALL BENDS, TEES AND DEAD ENDS IN ACCORDANCE WITH SPECIFICATIONS.
22.GRANULAR BEDDING IS REQUIRED FOR ANY TYPE OF PIPE USED AND SHALL BE AS SPECIFIED.
23.A NEAT VERTICAL EDGE WILL BE REQUIRED FOR ALL JOINTS BETWEEN THE NEW PAVEMENT SURFACE AND EXISTING PAVING AS SHOWN IN THE PLANS. SAW
CUTTING OR OTHER TECHNIQUES MAY BE USED TO PROVIDE THIS EDGE. COST OF THE SAW CUT IS TO BE CONSIDERED INCIDENTAL. ADDITIONAL REMOVAL
AND REPLACEMENT DUE TO THE CONTRACTOR'S OPERATION WILL BE MEASURED SEPARATELY BUT WILL BE THE CONTRACTOR'S RESPONSIBILITY.
24.ANY DEWATERING NECESSARY FOR CONSTRUCTION SHALL BE CONSIDERED INCIDENTAL TO INDIVIDUAL CONSTRUCTION ITEM. PLEASE REFER TO SUBSURFACE
EXPLORATION REPORT FOR ANTICIPATED SITE CONDITIONS. REPORT IS FOR INFORMATIONAL PURPOSES ONLY AND DOES NOT GUARANTEE CONDITIONS TO BE
EXPERIENCED.
25.THE CONTRACTOR SHALL INSPECT AND VERIFY SOIL CONDITIONS AS NECESSARY IN ORDER TO DETERMINE THE TYPE OF CONSTRUCTION TO EMPLOY. NATURAL
AND/OR MANMADE OBSTRUCTIONS MAY BE ENCOUNTERED IN THE SOIL. THESE CONTRACT DOCUMENTS DO NOT WARRANT THE NATURE OR CONDITIONS OF
THE SOILS, AND DO NOT WARRANT THAT NATURAL OR MANMADE OBSTRUCTIONS WILL NOT BE ENCOUNTERED, NOR GUARANTEE THE EXTENT TO WHICH
ROCKS, BOULDERS, OR OTHER OBSTRUCTIONS, REGARDLESS OF SIZE, MAY BE ENCOUNTERED DURING BORING OPERATIONS. THE CONTRACTOR SHALL NOT BE
ENTITLED TO ADDITIONAL COMPENSATION FOR ANY NATURAL OR MANMADE OBSTRUCTIONS ENCOUNTERED DURING TRENCHLESS CONSTRUCTION.
26.DETAILS SHOWN ARE INTENDED TO BE INDICATIVE OF THE PROFILES AND TYPE OF DETAILING REQUIRED THROUGHOUT THE WORK. DETAILS NOT SHOWN ARE
SIMILAR IN CHARACTER TO DETAILS SHOWN. WHERE SPECIFIC DIMENSIONS, DETAILS, OR DESIGN INTENT CANNOT BE DETERMINED, NOTIFY ARCHITECT /
ENGINEER BEFORE PROCEEDING WITH THE WORK.
27.ALL MANUFACTURED ARTICLES, MATERIALS AND EQUIPMENT SHALL BE APPLIED, INSTALLED, CONNECTED, ERECTED, CLEANED, AND CONDITIONED ACCORDING
TO MANUFACTURERS' INSTRUCTIONS. IN CASE OF DISCREPANCIES BETWEEN MANUFACTURERS' INSTRUCTIONS AND THE CONTRACT DOCUMENTS, NOTIFY
ARCHITECT / ENGINEER BEFORE PROCEEDING WITH THE WORK.
28.ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO AVOID GALVANIC CORROSION.
29.THE LOCATION AND TYPE OF ALL INPLACE UTILITIES SHOWN ON THE PLANS ARE ACCURATE AND COMPLETE TO THE BEST OF THE KNOWLEDGE OF ISG. NO
WARRANTY OR GUARANTEE IS IMPLIED. THE CONTRACTOR SHALL VERIFY THE SIZES, LOCATIONS AND ELEVATIONS OF ALL INPLACE UTILITIES PRIOR TO
CONSTRUCTION. CONTRACTOR SHALL IMMEDIATELY NOTIFY ENGINEER OF ANY DISCREPANCIES OF VARIATIONS FROM PLAN.
30.THIS SITE WILL HAVE SAWCUTTING AND/OR CONCRETE GRINDING, SO PROTECTION OF STORM SEWERS AND DRAINAGE WAYS WILL NEED TO BE PROTECTED
FROM SLURRY FROM THE CONCRETE OPERATION TO DISCHARGE OFFSITE.
31.THE CONTRACTOR IS TO CONTACT "IOWA ONE CALL" FOR UTILITY LOCATIONS, 48 HOURS PRIOR TO EXCAVATION / CONSTRUCTIONS (1-800-292-8989).
32.ANY PROPOSED CHANGES TO THE PLAN SET SHALL BE APPROVED IN WRITING BY THE CITY OF WAUKEE DEVELOPMENT SERVICES DEPARTMENT.
33.THE CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES MADE DURING CONSTRUCTION THAT HAVE NOT BEEN GRANTED APPROVAL IN WRITING BY THE CITY OF
WAUKEE DEVELOPMENT SERVICES DEPARTMENT.
34.ALL FIRE HYDRANTS ARE TO HAVE 4" STORZ FITTINGS.
35.ALL UTILITIES ARE TO BE CONSTRUCTED TO THE CITY OF WAUKEE STANDARDS.
36.ALL UTILITIES ARE TO BE TESTED TO CITY OF WAUKEE STANDARDS, AND THE CITY IS TO WITNESS ALL TESTING.
37.COORDINATE ALL TIE-INS TO EXISTING UTILITIES WITH CITY OF WAUKEE PUBLIC WORKS DEPARTMENT.
38.APPROVED FIRE APPARATUS ACCESS ROADS SHALL BE PROVIDED AS SOON AS CONSTRUCTION COMMENCES. THE FIRE APPARATUS ROAD SHALL COMPLY WITH
THE REQUIREMENTS OF SECTION 503.2 AND SHALL EXTEND TO WITHIN 100-FEET OF THE EXTERIOR WALLS OF THE BUILDING AS MEASURED BY AN APPROVED
ROUTE AROUND THE EXTERIOR OF THE BUILDING.
CONSTRUCTION NOTES
PROJECT GENERAL NOTES
6.ALL MANUFACTURED ARTICLES, MATERIALS AND EQUIPMENT SHALL BE
APPLIED, INSTALLED, CONNECTED, ERECTED, CLEANED AND CONDITIONED
ACCORDING TO MANUFACTURERS' INSTRUCTIONS. IN CASE OF DISCREPANCIES
BETWEEN MANUFACTURERS' INSTRUCTIONS AND THE CONTRACT DOCUMENTS,
NOTIFY ENGINEER BEFORE PROCEEDING WITH THE WORK.
7.ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH
OTHER TO AVOID GALVANIC CORROSION.
8.THE LOCATION AND TYPE OF ALL INPLACE UTILITIES SHOWN ON THE
PLANS ARE FOR GENERAL INFORMATION ONLY AND ARE ACCURATE AND
COMPLETE TO THE BEST OF THE KNOWLEDGE OF I & S GROUP, INC. (ISG). NO
WARRANTY OR GUARANTEE IS IMPLIED. THE CONTRACTOR SHALL VERIFY THE
SIZES, LOCATIONS AND ELEVATIONS OF ALL INPLACE UTILITIES PRIOR TO
CONSTRUCTION. CONTRACTOR SHALL IMMEDIATELY NOTIFY ENGINEER OF ANY
DISCREPANCIES OR VARIATIONS FROM PLAN.
9.THE CONTRACTOR IS TO CONTACT "IOWA ONE CALL" FOR UTILITY
LOCATIONS, MINIMUM 2 BUSINESS DAYS PRIOR TO ANY EXCAVATION /
CONSTRUCTION (1-800-292-8989).
1.ALL WORK SHALL CONFORM TO THE CONTRACT DOCUMENTS, WHICH
INCLUDE, BUT ARE NOT LIMITED TO, THE OWNER - CONTRACTOR AGREEMENT,
THE PROJECT MANUAL (WHICH INCLUDES GENERAL SUPPLEMENTARY
CONDITIONS AND SPECIFICATIONS), DRAWINGS OF ALL DISCIPLINES AND ALL
ADDENDA, MODIFICATIONS AND CLARIFICATIONS ISSUED BY THE
ARCHITECT/ENGINEER.
2.CONTRACT DOCUMENTS SHALL BE ISSUED TO ALL SUBCONTRACTORS BY
THE GENERAL CONTRACTOR IN COMPLETE SETS IN ORDER TO ACHIEVE THE FULL
EXTENT AND COMPLETE COORDINATION OF ALL WORK.
3.WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS.
NOTIFY ENGINEER OF ANY DISCREPANCIES OR CONDITIONS REQUIRING
INFORMATION OR CLARIFICATION BEFORE PROCEEDING WITH THE WORK.
4.FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. NOTIFY
ENGINEER OF ANY DISCREPANCIES OR CONDITIONS REQUIRING INFORMATION
OR CLARIFICATION BEFORE PROCEEDING WITH THE WORK.
5.DETAILS SHOWN ARE INTENDED TO BE INDICATIVE OF THE PROFILES AND
TYPE OF DETAILING REQUIRED THROUGHOUT THE WORK. DETAILS NOT SHOWN
ARE SIMILAR IN CHARACTER TO DETAILS SHOWN. WHERE SPECIFIC DIMENSIONS,
DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, NOTIFY ENGINEER BEFORE
PROCEEDING WITH THE WORK.
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 G0-TITLE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PROJECT
ESTIMATES &
QUANTITIES
REFERENCES
G0-12
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
G0-12 PROJECT ESTIMATES & QUANTITIES REFERENCES
---- 18-22051 G0-12
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
8"18"6"13 12"6"
3
1
R3"
R12"
R3"
HORIZONTAL LINE7"2
NOTES:
LONGITUDINAL JOINT WHEN ADJACENT TO RIGID PAVEMENT OR BASE.
SLOPE 0.06 FT/FT NORMAL, UNLESS OTHERWISE SPECIFIED. IF A DIFFERENT GUTTER SLOPE IS
PERMITTED, THE FORM MAY BE TILTED.
DO NOT INSTALL 6" BARRIER PORTION OF CURB WHERE ZERO-HEIGHT CURB IS CALLED OUT ON
THE PLANS. FOLLOW NOTE 2 FOR SLOPING OF ZERO-HEIGHT CURB.
1
2
1
CONCRETE CURB & GUTTER
NTSNTS
CONCRETE PAVEMENT
HEAVY-DUTY 7"
CONCRETE SLAB (MIN 4000 PSI)
MODIFIED SUBBASE
7"12"12" SUBGRADE PREPARATION
HORIZONTAL LINE
MATCH CONCRETE CURB & GUTTER
SECTION SEE PLAN FOR LOCATION
SECTION TO MATCH CONCRETE CURB
SHOE ROTATED TO DRAIN SEE PLAN
FOR LOCATION
SLOPE TO DRAIN
2.0% (TYP)
NTS
CONCRETE CURB & GUTTER
REVERSE PITCH
NTS
CONCRETE PAVEMENT
HEAVY-DUTY 6"
CONCRETE SLAB (MIN 4000 PSI)
MODIFIED SUBBASE
6"12"12" SUBGRADE PREPARATION
SD400NTS
VERTICAL RAIN LEADER
4" PERIMETER DRAIN
HORIZONTAL ROOF DRAIN,
SIZE VARIES.
6" PVC LEADER
45° FITTING
6" PVC REDUCER
4" DOWNSPOUTBUILDING LINE
FINISH FLOOR
(SEE PLANS)
18 GAUGE ALUMINUM
R
1
-
1
/
2
"
T
Y
P
DIGITALLY PRINTED VINYL (7 YR MIN)
APPLY TO FRONT SIDE OF SIGN PANEL
STANDARD ACCESSIBLE PARKING SIGN
BLUE. COLORS SHALL BE REFLECTIVE
PER IOWA D.O.T. STANDARDS.
PRE-DRILL HOLE TO ACCEPT 5/16" GALV.
TAMPER PROOF NUT AND BOLT. PRE-DRILL
PRIOR TO POWDER COATING.
NTS
ACCESSIBLE PARKING SIGN
℄
±10.0'±8.0'±12.0'±8.0'
PEDESTRIAN
AREA
PARALLEL
PARKING
±12.0'
TRAVEL
LANE
TRAVEL
LANE
ON STREET
PARKING
±10.0'
PEDESTRIAN
AREA
r/w r/w
±15.0'
PARKWAY
AREA
±15.0'
PARKWAY
AREA
NTS
TYPICAL ACCESS ROAD SECTION
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C0-DETAILS
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE DETAILS
C0-30
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C0-30 SITE DETAILS
---- 18-22051 C0-30
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C0-DETAILS
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE DETAILS
C0-31
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C0-31 SITE DETAILS
---- 18-22051 C0-31
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/11/2018 2ND CITY SITE SUBMITTAL DNA/BLF
22051 C0-DETAILS
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE DETAILS
C0-32
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C0-32 SITE DETAILS
---- 18-22051 C0-32
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C0-DETAILS
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE DETAILS
C0-33
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C0-33 SITE DETAILS
---- 18-22051 C0-33
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C0-DETAILS
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE DETAILS
C0-34
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C0-34 SITE DETAILS
---- 18-22051 C0-34
DOWNING
CONSTRUCTION
SUDAS CURB TO BE USED UNLESS
OTHERWISE SPECIFIED ON PLAN
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C0-DETAILS
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE DETAILS
C0-35
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C0-35 SITE DETAILS
---- 18-22051 C0-35
DOWNING
CONSTRUCTION
SUDAS SIDEWALK DETAIL TO BE USED
UNLESS OTHERWISE SPECIIFIED ON PLAN
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
1035
10
3
4
1
0
3
3
1
0
3
3
1
0
3
2
1
0
3
1
1
0
3
3
1
0
3
2
1
0
3
1
1
0
3
0
1
0
2
9
1
0
2
8
1
0
2
7
1
0
2
6
10
3
0
1
0
2
5
103
0
1
0
3
5
1
0
3
6 1031SE PARKVIEWTempora
ry
Easemen
tPer
Bk
2013
Pg
10390
8" WAT
E
R
M
AI
N
SE T
A
L
L
G
R
A
S
S
L
A
N
E
102510301
0
3
5
1
0
2
3
1024102610271028102910311032103310361
0
3
6
1
0
3
6
10371037103709/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C1-SWPPP
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PRE CONSTRUCTION
EROSION &
SEDIMENT
CONTROL PLAN
C1-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
DOWNING
CONSTRUCTION
LUSH DENTAL
DEVELOPMENT
18-22051
C1-10 PRE CONSTRUCTION EROSION & SEDIMENT CONTROL PLAN
---- 18-22051 C1-10
EROSION CONTROL LEGEND
SYMBOL DESCRIPTION UNITS QUANTITY SYMBOL DESCRIPTION UNITS QUANTITY
EXISTING STORM DRAIN INLET
PROTECTION EACH 2 *PERIMETER CONTROL LF 531
EXISTING DRAINAGE ARROW
* PERIMETER CONTROL SHALL BE SILT FENCE ONLY, PER SUDAS SPECIFICATION 9040-2.13
** QUANTITIES ARE FOR INFORMATIONAL PURPOSES TO MEET THE REQUIREMENTS OF THE CONSTRUCTION STORMWATER PERMIT. NO GUARANTEE IS MADE TO THE ACTUAL
QUANTITIES REQUIRED.
*** THE QUANTITIES SHOWN ARE TOTAL FOR THE ENTIRE PROJECT NOT SPECIFIC TO THIS SHEET.
**** SEE SITE RESTORATION PLAN FOR FINAL TURF ESTABLISHMENT
NOTE: SWPPP COVERAGE INCLUDES ELECTRIC, GAS, TELEPHONE, AND CABLE INSTALLATION. EACH COMPANY OR THEIR SUBCONTRACTOR IS RESPONSIBLE TO FOLLOW
THE REQUIREMENTS OF THIS SWPPP INCLUDING PROVIDING THEIR OWN RESTORATION IF INSTALLATION OCCURS AFTER PRIMARY INSTALLATION OF
SEEDING/SODDING/MULCHING DURING CONSTRUCTION OF EACH UTILITY.
0
SCALE IN FEET
30 60
EXISTING
TEMPORARY
SEDIMENT BASIN
EXISTING CONTOURS, TYP
PROPERTY LINE, TYP
15' SANITARY SEWER
EASEMENT
STABILIZED
CONSTRUCTION
EXIT
CONCRETE
WASHOUT
CONCRETE WASHOUT AREA EACH 1
STABILIZED CONSTRUCTION
EXIT EACH 1
AREA OF DISTURBANCE IS 162,660 SF / 3.73 ACRES.
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
KETTLESTONE REGIONAL STORMWATER
DETENTION B ASIN TO FOX CREEK-
REFER TO KETTLESTONE MASTER PLAN
DOCUMENTS AND CONSTRUCTION
DOCUMENTS ON FILE WITH THE CITY OF
WAUKEE FOR MORE INFORMATION.
***** CONCRETE WASHOUT CONTAINERS:
PROVIDE ROLLOFF TYPE METAL CONTAINER THAT IS LEAK PROOF AND DESIGNED SPECIFICALLY FOR COLLECTION OF CONCRETE AND CONCRETE WASHWATER. WHEN
CONCRETE PUMPER TRUCKS ARE UTILIZED, PROVIDE A RAMP OR OTHER MEANS TO ALLOW ACCESS FOR PUMPER TRUCKS.
PROVIDE INLET PROTECTION
TO EXISTING INTAKE.
ANTICIPATED LOCATION
PROPOSED TEMPORARY
SEDIMENT BASIN
NOTE:
DE-WATER EXISTING TEMPORARY SEDIMENT BASIN,
COLLECT DIMENSION AND ELEVATION INFORMATION
AS NEEDED TO VERIFY VOLUME.
CONSTRUCT NEW BASIN IN PROPOSED LOCATION
AND PROVIDE EQUIVALENT VOLUME PER FIELD
COLLECTED INFORMATION.
EXISTING SEDIMENT BASIN AREA=30,343 SF
PROPOSED SEDIMENT BASIN AREA=30,500 SF
cp MAGNAIL
7
1036.39
SE PARKVIEWSE T
A
L
L
G
R
A
S
S
L
A
N
E
ENCOMPASS
DR
IVE
103
01030 1030102610271028102910311031103110321029
1028
1027 1
0
2
6
10
3
7
1
0
3
6
1
0
3
5
1
0
3
4
10
3
3
1034
10
3
3
103
2
103
1
103
0
10
2
9 102810271026102510241
0
2
5
1026102
7
1028
10
2
9
10
3
0
10
3
1
10
3
2
10
3
3
103410
3
5
1
0
3
4 10331
0
3
2
1
0
3
1
1
0
3
0
1
0
2
9
1
0
2
8
1
0
2
7
1
0
2
6
1
0
2
5
1
0
2
4 10
2
311 SPACES
5 SPAC
E
S
9 SPACES
DW
ELEC.#1 ELEC.#2PROPOSED BUILDING6,710 SF.FFE = 1031.001030
1033
1032
1031
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C1-20-SWPPP
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PROPOSED
EROSION &
SEDIMENT
CONTROL PLAN
C1-20
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C1-20 PROPOSED EROSION & SEDIMENT CONTROL PLAN
---- 18-22051 C1-20
EROSION CONTROL LEGEND
SYMBOL ITEM
NO.DESCRIPTION UNITS QUANTITY
SILT FENCE, PER SUDAS
SPECIFICATION 9040-2.13 LF 1520
2573.502 PROPOSED STORM DRAIN
INLET PROTECTION EACH 2
PROPOSED DRAINAGE ARROW
* PERIMETER CONTROL CAN BE SILT FENCE OR SEDIMENT CONTROL LOG.
** QUANTITIES ARE FOR INFORMATIONAL PURPOSES TO MEET THE REQUIREMENTS OF THE
CONSTRUCTION STORMWATER PERMIT. NO GUARANTEE IS MADE TO THE ACTUAL QUANTITIES
REQUIRED.
*** THE QUANTITIES SHOWN ARE TOTAL FOR THE ENTIRE PROJECT NOT SPECIFIC TO THIS SHEET.
**** SEE SITE RESTORATION PLAN FOR FINAL TURF ESTABLISHMENT
NOTE: SWPPP COVERAGE INCLUDES ELECTRIC, GAS, TELEPHONE, AND CABLE INSTALLATION. EACH
COMPANY OR THEIR SUBCONTRACTOR IS RESPONSIBLE TO FOLLOW THE REQUIREMENTS OF THIS
SWPPP INCLUDING PROVIDING THEIR OWN RESTORATION IF INSTALLATION OCCURS AFTER PRIMARY
INSTALLATION OF SEEDING/SODDING/MULCHING DURING CONSTRUCTION OF EACH UTILITY.
DOWNING
CONSTRUCTION
PROPERTY LINE, TYP
EXISTING CONTOUR, TYP
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
KETTLESTONE REGIONAL STORMWATER
DETENTION BASIN TO FOX CREEK -
REFER TO KETTLESTONE MASTER PLAN
DOCUMENTS AND CONSTRUCTION
DOCUMENTS ON FILE WITH THE CITY OF
WAUKEE BY FOTH ENGINEERING FOR
MORE INFORMATION.
CLASS "E" REVETMENT, TYP.
STABILIZED
CONSTRUCTION
ENTRANCE / EXIT
CONCRETE
WASHOUT
2573.503
TEMPORARY WASTEMATERIALS
STORAGEPROPOSEDSTAGING
&MATERIALSLOCATION
LIMITS OF DISTURBANCE
3.73 ACRES
AREA OF DISTURBANCE IS 162,660 S.F. / 3.73 ACRES
PROPOSED CONTOUR, TYP
CONCRETE WASHOUT AREA
STABILIZED CONSTRUCTION
EXIT
EACH 1
EACH 1
0
SCALE IN FEET
30 60
TEMPORARY TOPSO
ILSTORAGE LOCAT
ION
PROVIDE INLET PROTECTION
TO EXISTING INTAKE.
ULTIMATE DISCHARGE TO
KETTLESTONE REGIONAL STORMWATER
DETENTION BASIN INTO FOX CREEK.
ANTICIPATED LOCATION
PROPOSED TEMPORARY
SEDIMENT BASIN
DIVERSION BERM, TYP
NOTE:
DE-WATER EXISTING TEMPORARY SEDIMENT BASIN,
COLLECT DIMENSION AND ELEVATION INFORMATION
AS NEEDED TO VERIFY VOLUME.
CONSTRUCT NEW BASIN IN PROPOSED LOCATION
AND PROVIDE EQUIVALENT VOLUME PER FIELD
COLLECTED INFORMATION.
EXISTING SEDIMENT BASIN AREA=30,343 SF
PROPOSED SEDIMENT BASIN AREA=30,500 SF
NOTE:
MAXIMUM AREA PERMITTED TO SINGLE SILT FENCE = 1/4 ACRE PER 100 FT
PROPOSED TRIBUTARY AREA TO SILT FENCE=3.73 ACRES
LENGTH OF SILT FENCE REQUIRED=1492 LF
LENGTH OF SILT FENCE PROVIDED=1520 LF
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C1-SWPPP
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SWPPP GENERAL
INFORMATION &
NOTES
C1-30
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C1-30 SWPPP GENERAL INFORMATION & NOTES
---- 18-22051 C1-30
ACTIVITY SCHEDULE
Install all BMP's needed and associated with the
Grading Phase such as stabilized construction
entrances, silt basins, riser pipes, outlet pipes silt
traps, silt fence, diversions, terraces, and
etcetera.
Prior to any stripping of existing vegetation or
grading.
Proceed with stripping of existing vegetation and
grading in accordance with the grading plan,
while disturbing no more than necessary.
After Installing all BMP's needed and associated with
the Grading Phase. Furthermore, INSPECTOR
approval must be obtained before the start of any
stripping of existing vegetation or grading.
Proceed with infrastructure installation.
Infrastructure installation must occur prior to any
building construction.
Implement the installation of Temporary Seeding,
Permanent Seeding, and/or Mulching.
Proceed with removal of BMP's.
BMP's may not be removed until each impacted
drainage basin has been fully developed. Full
development shall mean installation of pavement,
buildings, and utilities, landscaping, and fully
established permanent seeding. Furthermore,
INSPECTOR approval must be obtained before the
removal of any BMP's.
CONSTRUCTION ACTIVITIES & SCHEDULING
CONSTRUCTION ACTIVITY NOTES:
EROSION PREVENTION:
Construction of silt fence and all other erosion control measures shall be complete before other
construction activity occurs.
Use phased construction wherever practical and establish turf as soon as possible to minimize
sediment transport.
Turf establishment or temporary seeding or mulching of all exposed soil not being actively worked
should be immediately initiated once earth disturbing activities have ceased.
Temporary cover during construction is incidental.
Pipe outlets must be provided with temporary or permanent energy dissipation within 24 hours after
connection to a surface water.
.
SEDIMENT CONTROL PRACTICES:
Construction of silt fence and all other erosion control measures shall be complete prior to land
disturbing activities occur.
Inlet erosion protection shall be installed and maintained until turf has been established.
The contractor shall be responsible to control erosion from leaving the construction zone. All
eroded material that leaves the construction zone shall be collected by the contractor and returned
to the site at the contractor's expense.
All streets must be swept at the end of each working day and prior to a rain event.
Silt fence or other effective erosion control measures must be installed around the perimeter of any
soil stockpiles, including temporary stockpiles. Stockpiles cannot be placed in surface waters,
including storm water conveyances such as curb and gutter systems, or conduits and ditches.
Perimeter control shall be installed along the back of curb immediately following curb installation at
all locations with positive drainage to parking lot and/or streets, and shall remain until stabilization is
achieved. This shall be accomplished through the use of silt fence, biorolls, Rock logs, or other
methods approved by the Engineer.
CONSTRUCTION ACTIVITY NOTES:
DEWATERING AND BASIN DRAINING:
Dewater sediment-laden water to sedimentation basins if possible, or use other BMP's to
prevent erosion and remove sediment when discharging to surface waters. Use
appropriate energy dissipation measures on all discharges.
Dewatering practices cannot cause nuisance conditions, erosion or in receiving channels or
inundation of wetlands resulting in adverse impacts.
POLLUTION PREVENTION:
All solid waste collected from the construction site must be disposed in accordance with all
applicable regulations.
All hazardous materials (oil, gasoline, fuel, paint, etc) must be properly stored to prevent
spills, leaks or other discharge, storage areas shall provide secondary containment and a
hazardous materials spill kit. Storage and disposal of hazardous waste must be in
compliance with all applicable regulations.
Equipment maintenance areas must be limited to a defined area of the site. All runoff
containing any hazardous material must be properly collected and disposed. No engine
degreasing shall be allowed on site.
The contractor is responsible for monitoring air pollution and ensuring it does not exceed
levels set by local, state, or federal regulations. This includes dust created by work being
performed on the site. Air pollution and dust control correction is considered incidental to
the unit bid prices for which work is being performed. Additional dust control measures
may be required by the Engineer.
Concrete washout onsite: All liquid waste generated by concrete washout operations
must be contained in a leak-proof containment facility or impermeable liner. The liquid
waste must not contact the ground, and there must not be runoff from the concrete
washout operations or areas. A sign must be installed adjacent to each washout facility to
inform concrete equipment operators to utilize the proper facilities.
INSPECTION AND MAINTENANCE:
The Permittees must routinely inspect the construction site once every seven (7) days
during active construction.
All inspections performed during construction must be recorded and records retained with
the SWPPP.
Contractor is responsible for keeping a record of all rainfall information & erosion control
maintenance until final establishment of turf.
All silt fences must be repaired, replaced, or supplemented when they become
nonfunctional or the sediment reaches 12 of the height of the fence.
Erosion control, and other BMP's must be replaced, repaired, or supplemented when they
reach 50% design load.
FINAL STABILIZATION:
The Permittees must ensure final stabilization of the site. The Permittees must submit a
notice of termination within 30 days after final stabilization is complete or control has been
passed to another owner.
All temporary erosion control measures and BMP's must be removed as part of the final
site stabilization.
The storm water permit further defines final stabilization and its requirements.
MAINTENANCE SCHEDULE
The following Maintenance Schedule has been provided. The INSPECTOR must perform
the inspections. The OPERATOR/CONTRACTOR must perform all needed maintenance.
Furthermore, all erosion control feature requiring maintenance may not be listed below. The
OPERATOR/CONTRACTOR and INSPECTOR must perform their respective duties on all
BMP's that are not listed below as well.
1.Construction Entrance - The entrance shall be maintained in a condition which
will prevent tracking or flow of sediment onto public rights-of-way. This may
require periodic top dressing with additional stone or the washing and
reworking of existing stone as conditions demand and repair and/or cleanout of
any structures used to trap sediment. All materials spilled, dropped, washed, or
materials dropped, washed or tracked onto roadways will not be permitted
under any circumstances.
2.Wattles - The maintenance measures are as follows: (2.1) wattles shall be
inspected weekly; (2.2) close attention shall be paid to the repair of damaged
bales, end runs and undercutting beneath bales; (2.3) necessary repairs to
barriers or replacement of wattles shall be accomplished promptly; (2.4)
sediment deposits shall be removed after each rainfall, they must be removed
when the level of deposition reaches approximately one-half the height of the
wattle; and (2.5) any sediment deposits remaining in place after the wattle is no
longer required shall be dressed to conform to the existing grade, prepared and
seeded.
3.Silt Fence - The maintenance measures are as follows; (3.1) silt fences shall
be inspected weekly, any required repairs shall be made immediately; (3.2)
close attention shall be paid to the repair of damaged silt fence resulting from
end runs and undercutting; (3.3) should the fabric on a silt fence decompose or
become ineffective prior to the end of the expected usable life and the barrier is
still necessary, the fabric shall be replaced promptly; (3.4) sediment deposits
must be removed when the level of deposition reaches approximately one-half
the height of the barrier; and (3.5) any sediment deposits remaining in place
after the silt fence is no longer required shall be dressed to conform to the
existing grade, prepared and seeded.
4.Storm Drain Inlet Protection - The maintenance measures are as follows: (4.1)
structures shall be inspected weekly and repairs made as necessary and (4.2)
structures shall be removed and the area stabilized when the remaining
drainage area has been properly stabilized.
5.Temporary Seeding - Areas which fail to establish vegetative cover adequate
to prevent rill erosion will be re-seeded as soon as such areas are identified.
6.Permanent Seeding - The maintenance measures are as follows: (10.1) in
general, a stand of vegetation cannot be determined to be fully established until
it has been maintained for one full year after planning; (10.2) new seedlings
shall be supplied with adequate moisture, supply water as needed, especially
late in the season, in abnormally hot or dry conditions, or on adverse sites,
water applications shall be controlled to prevent excessive runoff; (10.3)
inspect all seeded areas for failures and make necessary repairs,
replacements, and reseedings within the planting season, if possible; [10.3.a] if
stand is inadequate for erosion control, over seed and fertilize using half of the
rates originally specified; [10.3.b] if stand is 60% damaged, re-establish
following seedbed and seeding recommendations; [10.3.c] if stand has less
than 40% cover, re-evaluate choice of plant materials and quantities of lime
and fertilizer, the soil must be tested to determine if acidity or nutrient
imbalances are responsible, re-establish the stand following seedbed and
seeding recommendations.
7.Street Cleaning / Sweeping - The maintenance measures are as follows: (13.1)
evaluate access points daily for sediment tracking; (13.2) when tracked or
spilled sediment is found on paved surfaces, it will be removed daily, during
times of heavy track-out, such as during rains, cleaning may be done several
times throughout the day; (13.3) all streets shall be swept at the end of each
working day and prior to a rain event; (13.4) unknown spills or objects will not
be mixed with the sediment; and (13.5) if sediment is mixed with other
pollutants, it will be disposed of properly at an authorized landfill.
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
Stabilization of disturbed areas must be initiated
immediately whenever any clearing, grading,
excavating, or other earth disturbing activities have
permanently ceased on any portion of the site or
temporarily ceased on any portion of the site and
will not resume for a period exceeding 14 calendar
days.
Stabilization of disturbed areas must be initiated
immediately whenever any clearing, grading,
excavating, or other earth disturbing activities
have permanently ceased on any portion of the
site or temporarily ceased on any portion of the
site and will not resume for a period exceeding 14
calendar days.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C1-SWPPP
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SWPPP DETAILS
C1-40
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C1-40 SWPPP DETAILS
---- 18-22051 C1-40
CONCRETE WASHOUT LOCATION WILL BE APPROVED BY ENGINEER
CONTRACTOR SHALL INSTALL A SIGN INDICATING THE CONCRETE WASHOUT AREA.
CONTRACTOR SHALL MAINTAIN WASHOUT AREA TO REMOVE MATERIALS BEYOND 75% CAPACITY.
WASHOUT AREA SHALL NOT BE PLACED WITHIN 50' OF STORM DRAINS, OPEN DITCHES OR BODIES OF WATER.
CONTRACTOR SHALL INSPECT WASHOUT AREA AS NECESSARY TO PREVENT LEAKS AND OVER TOPPING.
WASHOUT AREA SHALL BE REMOVED AFTER CONSTRUCTION IS COMPLETE.
NOTES:
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
102510301
0
3
5 1026102710281
0
2
9
10311032103310341
0
3
4
1
0
3
6
103710
3
7
1
0
2
3
10241
0
2
5
1
0
3
0
1
0
3
5
1
0
2
3
1
0
2
4
1
0
2
6
1
0
2
7
1
0
2
8
1
0
2
9
1031103210331
0
3
4
1
0
3
610371037 SE T
A
L
L
G
R
A
S
S
L
A
N
E
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C2-EXIST
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
--
WAUKEE IOWA
EXISTING SITE PLAN
C2-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C2-10 EXISTING SITE PLAN
---- 18-22051 C2-10
EXISTING SITE LEGEND
STORM DRAIN
SANITARY SEWER
WATER MAIN
GAS
UNDERGROUND ELECTRIC
OVERHEAD ELECTRIC
FIBER OPTIC
FENCE LINE
PROPERTY / LOT LINE
EASEMENT LINE
CONTOURS (MAJOR)
CONTOURS (MINOR)
CONTRACTOR SHALL FIELD VERIFY THE LOCATIONS OF ALL
EXISTING UTILITIES.
100
101
0
SCALE IN FEET
20 40
LOT 1
ZONING DISTRICT K-PUD:
KETTLEVIEW PLAN UNIT DEVELOPMENT
31,068 SQ FT, 0.71 AC
PROPERTY LINE (TYP)
BOUNDARY LINE (TYP)
LIGHT POLE
(TO BE PROTECTED)
SANITARY SEWER MANHOLE
(TO BE PROTECTED)
SANITARY SEWER MANHOLE
(TO BE PROTECTED)
STORM SEWER MANHOLE
(TO BE PROTECTED)
STORM SEWER CATCHBASIN
(TO BE PROTECTED)
LIGHT POLE
(REMOVE & RELOCATE)
EXISTING TEMPORARY
SEDIMENT BASIN
CITY OWNED
GREENSPACE
EXISTING CONTOUR, TYP.
DOWNING
CONSTRUCTION
15' SANITARY SEWER EASEMENT
BK 2017 PG 3264
EXISTING TEMPORARY EASEMENT
BK 2013 PG 190
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
EXG REGIONAL
STORMWATER
DETENTION BASIN61'
R
IGHT
OF
WAY1616TEMPORARY EASEMENT
PER BK 2013 PG 10390
EXISTING FIRE HYDRANT
11 SPACES
5 SPA
C
E
S
9 SPACES
DW
ELEC.#1 ELEC.#2PROPOSED BUILDING6,710 SF.FFE = 1031.00SE T
A
L
L
G
R
A
S
S
L
A
N
E
ENCOMPASS
DR
IVE
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C3-SITE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PROPOSED SITE
PLAN
C3-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C3-10 PROPOSED SITE PLAN
---- 18-22051 C3-10
0
SCALE IN FEET
20 40
SITE SUMMARY
ZONING:K-OF (KETTLESTONE OFFICE DISTRICT) / PD-1
(PLANNED DEVELOPMENT OVERLAY DISTRICT)
SITE/LOT AREA:31,068 SQ. FT. / .71 AC.
IMPERVIOUS AREA:19,841 SQ. FT. / .46 AC.
GREENSPACE PROVIDED:11,227 SQ. FT. / .25 AC.
PARKING REQUIREMENTS (PER CITY CODE)
BUSINESS AREA 4,840 SF 1 PER 250 SF
RESIDENTIAL AREA 4,840 SF 2 PER UNIT
TOTAL 7,202 SF 22 STALLS REQ/ 25
PROVIDED
9'9'9'
(TYP
)
19' (TY
P)
PROPERTY LINE (TYP)
EXISTING LIGHT POLE (TYP)
ACCESSIBLE PARKING
SIGN & POST (SEE DETAILS)
4" WIDE PARKING
STRIPE (TYP)
PROPOSED 4" MIN PCC SIDEWALK
SCREEN STRUCTURE,
REFER TO C6-10
FOR COMPLETE DETAIL
FUTURE AREAS SHOWN FOR PLANNING
AND COORDINATION PURPOSES ONLY
AND ARE NOT PART OF THIS
SITE PLAN SUBMITTAL
TEMPORARY GRAVEL TURNAROUND
CITY STANDARD 40' MIN RADIUS W/
GRANULAR SURFACE 8" THICK WITH
4" THICK, 3" THICK GRADATION ROCK
BASE W/ 4" THICK 1" ROAD STONE TOP
DOWNING
CONSTRUCTION
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
RELOCATED LIGHT POLE, COORDINATE WITH
CITY OF WAUKEE FOR FINAL APPROVAL
SUDAS TYPE A DRIVEWAY
SEE DETAIL, SHEET C0-34
SUDAS TYPE A DRIVEWAY
SEE DETAIL, SHEET C0-34
24'
19'24'
14'
55'117'49'35'
11'24'10'18'
6'24'19'21'
10'9'28'26'
BULK REGULATIONS
FRONT YARD SETBACK (REQUIRED FORM
ALL PUBLIC/ PRIVATE STREET FRONTAGE)0 FT
SIDE YARD SETBACK 0 FT
REAR YARD SETBACK 0 FT
PRINCIPLE BUILDING PERIMETER SETBACK
FROM ADJOINING SFR 50 FT
MINIMUM PRINCIPLE BUILDING
SEPARATION 25 FT
MINIMUM PRINCIPLE AND ACCESSORY
BUILDING SEPARATION n / a
DETACHED ACCESSORY STRUCTURE
SETBACKS n / a
PRINCIPLE STRUCTURE MAXIMUM HEIGHT MIN 2 STORIES
MAX 8 STORIES
MINIMUM % OPEN SPACE 15 - 25%
MAXIMUM FAR 0.35
MAXIMUM DU / AC n / a
MINIMUM LOT SIZE n / a
MINIMUM LOT WIDTH n / a
BUILDING TYPE n / a
0 SIDE
Y
A
R
D
S
E
T
B
A
C
K0 FRONT
YARD
SETBACK
0 SIDE Y
A
R
D
S
E
T
B
A
C
K
0 REAR YARD SETBACK(3)BIKE RACK
LANDSCAPE FORMS
STYLE = EMERSON
COLOR = MERCURY
CONTRACTOR SHALL COORDINATE WITH
THE CITY ON LOCATION AND COORDINATE
WITH PLANS FOR PUBLIC GREENWAY
PROPOSED ELECTRICAL
TRANSFORMER LOCATION
(BY MID AMERICAN)
PROPOSED
UNDERGROUND
ELECTRICAL
(BY MID AMERICAN)
EXISTING STORM SEWER INTAKE
EXISTING STORM
SEWER MANHOLE
R = 1028.71
I (W) = 1022.53
I (E) = 1022.37
EXISTING 24"
STORM SEWER
EXISTING SANITARY
SEWER MANHOLE
R = 1033.11
I (W) = 1018.35
I (E) = 1018.35
EXISTING 24"
STORM SEWER
EXISTING 24"
STORM SEWER
EXISTING SANITARY
SEWER MANHOLE
R = 1026.56
I (W) = 1009.70
I (N) = 1009.53
I (E) = 1009.44
41'
EX 8" SA
NI
T
A
R
Y
S
E
W
E
R
37'193'100'
TRASH ENCLOSURE
LOCTIONR25R11R4
R11 R9R4 R4R4
R4R4
R2
R4R40PROPOSED INGRESS/EGRESS
EASEMENT
PROPOSED PERMANENT 20'
STORM SEWER EASEMENT
PROPOSED 10' WATERMAIN EASEMENT
R25
R5
20'
62'
PROPOSE 10' SANITARY
SEWER EASEMENT
10'
10'
PAVEMENT LEGEND
SYMBOL DESCRIPTION
8" PCC PAVEMENT
6" PCC PARKING AND
DRIVEWAY
7" PCC PAVEMENT
4" PCC SIDEWALK
6" PCC SIDWALK
REVERSE PITCH CONCRETE
CURB & GUTTER
11 SPACES
5 SPA
C
E
S
9 SPACES
DW
ELEC.#1 ELEC.#2PROPOSED BUILDING6,710 SF.FFE = 1031.00SE T
A
L
L
G
R
A
S
S
L
A
N
E
5 SPACES5 SPACES10 SPACES7 SPACES2 SPACE
S
FUTURE
BUILDING
FUTUREBUILD
INGENCOMPASS
DR
IVE 01233FES-1
R=1020.26
I=1018.68
A-4
R=1029.45
I=1022.32
P-4 77'x
1
8"
R
C
P
@
1.
8
3
%
A-5
R=1025.67
I=1020.92
P-5 123'
x
1
8
"
@
1.
8
3
%
A-1
R=1031.70
I=1026.55
P-1 31'
x
1
2"
@
1.
0
0
%P-2
167
'x
12
"
@
1
.00%
A-2
R=1031.38
I=1026.24
A-3
R=1032.07
I=1024.57
P-3 (15")
STORM DRAIN APRON
SCHEDULE
APRON
NO.
FES-1
APRON
SIZE (in)
18
APRON
MATERIAL
RC
INVERT
ELEVATION
1018.68
PIPE
NO.
P-5
STORM DRAIN PIPE SCHEDULE
PIPE
NO.
P-1
P-2
P-3
P-4
P-5
DRAIN
FROM
A-4
A-5
INLET
ELEVATION
1026.24
1024.57
1022.32
1022.32
1020.92
DRAIN
TO
A-5
FES-1
OUTLET
ELEVATION
1026.55
1026.24
1024.57
1020.92
1018.68
PIPE
SIZE (IN)
12
12
15
18
18
MATERIAL
RCP
RCP
RCP
RCP
RCP
PIPE
CLASS
RCP
RCP
RCP
RCP
RCP
PIPE
GRADE
1.00%
1.00%
3.03%
1.83%
1.83%
PIPE
LENGTH (FT)
31
167
74
77
123
STORM DRAIN SCHEDULE
STRUCTURE
NO.
A-1
A-2
STRUCTURE
TYPE
SW-501
SW-401
STRUCTURE
SIZE (In)
36 x 24
48 Ø
STRUCTURE
MATERIAL
RC
RC
CASTING
FRAME GRATE COVER
FRAME GRATE COVER
PAY HEIGHT
LN FT
7.13
4.75
* TOP OF CASTING
ELEVATION
1029.45
1025.67
INVERT
ELEVATION
1022.32
1020.92
OUTLET
PIPE
P-1
P-2
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C3-SITE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PROPOSED UTILITY
PLAN
C3-20
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
DOWNING
CONSTRUCTION
LUSH DENTAL
DEVELOPMENT
18-22051
C3-20 PROPOSED UTILITY PLAN
---- 18-22051 C3-20
0
SCALE IN FEET
20 40
FUTURE AREAS SHOWN FOR PLANNING
AND COORDINATION PURPOSES ONLY
AND ARE NOT PART OF THIS
SITE PLAN SUBMITTAL
PROPOSED ELECTRICAL
TRANSFORMER LOCATION
(BY OTHERS)
EX STORM SEWER MANHOLE
R = 1028.71
I = 1022.53 24" (W)
I = 1022.37 24" (E)
EX SANITARY SEWER
R = 1026.56
I = 1009.70 (W)
I = 1009.53 (N)
I = 1009.44 (E)
EX SANITARY SEWER
R = 1033.11
I = 1018.35 (W)
I = 1018.35 (E)
PROPOSED GAS LINE
(BY OTHERS)PROPOSED UNDERGROUND
ELECTRICAL (BY OTHERS)
PROPOSED
SANITARY SEWER
LINE
INV=1026.5
PROPOSED STORM
SEWER LINE
ROOF DRAIN / DOWNSPOUT
COLLECTION TILE, REFER TO DETAIL
FIRE HYDRANT
ASSEMBLY
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
124 LF OF 8" PVC STORM @ 1.00%
(MINIMUM)
FIRE DEPT
CONNECTION
CONNECT TO EXISTING
SANITARY SEWER w/ WYE
CONNECTION
INV=1018.95
23 LF OF 6" PVC
SDR 23.5 @ 3.2%
SANITARY SEWER
SANITARY SEWER
CLEANOUT W/ HEAVY
DUTY CASTING
INV=1026.
1
PIPE CROSSING ELEVATIONS
I WATER ≈ 1023.70
I EX STR SEWER ≈ 1022.20
I WATER ≈ 1023.54
I EX SAN SEWER ≈ 1012.17
SEE NOTE 19-20
1
2
2
EX 8" W
A
T
E
R
M
AI
N
EX STORM
SEWER INTAKE
RELOCATED CITY LIGHT FIXTURE
COORDINATE STREET
LIGHT RELOCATION WITH
MIDAMERICAN ENERGY
EX 24"
S
T
O
R
M
S
E
W
E
R
EX 8" SANITARY SEWER
EX 24" ST
O
R
M
S
E
W
E
R
EX 8" SA
NI
T
A
R
Y
S
E
W
E
R
CONNECT TO EXISTING 8" WATER MAIN
WITH AN 8" TAPPING SLEEVE AND VALVE
BY BORING UNDERNEATH ROADWAY
8" WATER MAIN
6" HYDRANT, VALVE
& REDUCER
DOMESTIC WATER
CONNECTION
PROPOSED PERMANENT
INGRESS/EGRESS EASEMENT
15' SANITARY SEWER EASEMENT
BK 2017 PG 3264
FIRE RISER ROOM
PROPOSED PERMANENT
STORM SEWER EASEMENT
2" COPPER DOMESTIC
6" C900 PVC FIRE
6" C900 PVC WATERMAIN
34'10'
CLASS E REVETMENT
37 TONS
DW
ELEC.#1 ELEC.#2PROPOSED BUILDING6,710 SF.FFE = 1031.008" WAT
E
R
M
AI
N
SE T
A
L
L
G
R
A
S
S
L
A
N
E
1031103210301032
.
0
7
103
2
.
1
2
1031.
9
2
10
3
2
.
3
5
1030.99
1030.711030.771030.96103
1
.
1
91030.291030.80
1030.
9
2 1030.881030.961031.021031.021030.36
1029.
7
0
1029.9
0
1030
.
4
2
1030.311029.5
4
1
0
2
9
.
4
7
1030.7
71031.611031.271031.521031.771032.601032.281030.67ENCOMPASS
DR
IVE
103
2
.
1
0
1
0
3
2
.
2
7 1030.631030.2
7
1030.2
7
1030.751030.36
1030.82
1030.84
1030.8
3
1030.8
1
1030.951030.3
9 1030.471030.3
4
10
3
0
.
4
21031.021030.931031.
2
2
1031.
2
6
1031.
1
9
1030.5
4
1029.8
3
1029.7
6
1029.781029.
8
6 1030.061030.1810
3
0
.
2
6
1029.971030.691030.33
103
0
.
9
9
103
1
.
3
9
103
1
.
0
2 1031.021031.021031.0210
2
9
.
5
0
1030.101030.191030.011028.801029.461030.37
1030.59
1030.47
102
9
.
9
1
1029.7
6
1029.5
11031
10301030 10301026102710281029103110
2
6
10
2
7
1028
1029
102
9
.
5
8
1029.83
1028.93
103
0
1029
1031
1
0
2
3
1
0
2
4
1
0
2
5
1026102710281029103010311032103310341035
1034
1033
1032
10
3
1
1030
1
0
2
9 1028102
7 102610251030.27 1025102510241026.001026.001031.141025.67
102
5
.
3
1
1030.8
5
102
9
.
9
8
103
0
.
0
5
103
0
.
1
6
1030.77
1030.2
6
1030.2
8
1032.
2
3
1031.
9
6
1031.
8
1
1031.
7
51030.221030.231030.141030.311030.371030.20 1030.081030.901032.261030.04
1030.14
1031.4
1
1031.6
2
1029.4
4
1030.0
7
103
1
.
5
5
103
1
.
4
7
1
0
3
1
.
3
2
1031.3
9
1031.37
1
0
3
1
.
2
7
1033
1030
1032
1031 1030.15??
?1029.111027.581025.281024.861030.751030.731030.501031.011031.421032.041032.341032.101031.801031.191031.951029.34103
0
.
8
3
1031.19
1032.111030.25
1030.0710
3
0
.
8
1
10
3
0
.
5
5
103
1
.
3
3
103
1
.
7
8
1031.42103
1
.
8
8
1032.911032.
7
6 1033.
0
2
1032.
8
7
-2
.3%
-2
.0%
-2
.0%-1.6%-2.0%-2.0%-2.0%-2.0%-1.5%-4.4%-3.7%1031.021031.021031.021031.021031.021031.01-2.0%-2.0%1030.831
0
3
0
.
1
7
1031.311030.22-1
.0%1030.80-2.1%
-3.1%
-2.2%
3.3%
5.0%
3.2%1030.711030.771030.961030.361030.671030.631030.2
7
1030.2
7
1030.751030.36
1030.82
1030.84
1030.8
3
1030.8
1 1030.95102
9
.
9
1
1030.8
5
102
9
.
9
8
103
0
.
0
5
103
0
.
1
6
-0
.7%
-0
.7%
-0
.8%-1.1%
-6
.1%-1.5%-1.5%-1.5%-1.5%
-0
.1%
-6
.2%
-0
.1%-1.0%-1.7%-1.7%
-6
.0%
1030.77
1030.2
6
1030.2
8
-6
.1%1030.751030.73-1.5%-1.5%0.4%0.4%1031.021031.021031.021031.01-2.1%
1032
10
3
1
1030
1031.
9
6
1
0
3
0
.
2
2 1030.231030.141030.311030.37103
1
.
5
5
103
1
.
4
7
1
0
3
1
.
3
2
1031.3
9
1031.37
1
0
3
1
.
2
71.4%1.3%-0.1%-1.5%-1.6%1.3%
-1
.2%-1.5%-1.5%1030.501031.011031.951029.34103
0
.
8
3
-1
.5%
103
1
.
3
3
103
1
.
7
8
-6
.7%
-6
.6%1031.42103
1
.
8
8
-6
.6%
-1
.5%
-1
.5%1030.171031.311030.22-1.5%-1.5%
-0
.2%
-1
.0%
-0
.8%1030103
1
.
1
9 1031.021029.
7
0
1029.9
0
1029.8
3
1029.7
6
1029.781029.
8
6 1030.061030.1810
3
0
.
2
6
1029.971030.691030.33
103
0
.
9
9
103
1
.
3
9
103
1
.
0
2 1031.021030
1030.25
1030.0710
3
0
.
8
1
10
3
0
.
5
5
-0
.0%
-0
.0%-3.4%-1.4%-1.2%
-1
.1%
-1
.1%
1032
.
0
7
103
2
.
1
2
1031.
9
2
10
3
2
.
3
5
1032.601032.28ENCOMPASS
DR
IVE
103
2
.
1
0
1
0
3
2
.
2
7
1032.
2
3
1031.
9
6
1031.
8
1
1031.
7
5 -1.5%
-1
.3%
-1
.2%-0.7%
-5
.5%
-6
.4%-1.2%
-1
.5%
1
0
3
1
.
2
7 1031.011031.421
0
3
2
.
0
4
1032.341031.801031.19103
0
.
8
3
1031.19
1032.11103
1
.
3
3
103
1
.
7
8
-6
.7%
-6
.6%1031.42103
1
.
8
8
1032.911032.
7
6
1033.
0
2
1032.
8
7 -1.5%
-1
.8%
-1
.8%
-6
.6%
-6
.6%
-1
.5%
-1
.5%-1.5%1030.831031.31-1.5%-1.5%
-1
.5%
-1
.0%
-0
.8%
22051 C4-GRADING
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PROPOSED
GRADING SITE PLAN
C4-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
DOWNING
CONSTRUCTION
LUSH DENTAL
DEVELOPMENT
18-22051
C4-10 PROPOSED GRADING SITE PLAN
---- 18-22051 C4-10
EXISTING CONTOURS, TYP.
PROPOSED CONTOURS, TYP.
GRADING LEGEND
EXISTING CONTOUR (MINOR INTERVAL)
EXISTING CONTOUR (MAJOR INTERVAL)
PROPOSED CONTOUR (MINOR INTERVAL)
PROPOSED CONTOUR (MAJOR INTERVAL)
PROPOSED SPOT ELEVATION
PROPOSED TOP BACK OF CURB SPOT ELEVATION
SURFACE GRADE / DIRECTION
GENERAL GRADING NOTES
EXCAVATED MATERIAL SHALL BE COMPACTED TO 100% PROCTOR DENSITY FOR THE UPPER 3', AND
95% PROCTOR DENSITY BELOW 3' IN ALL BUILDING PADS. REFER TO THE QUALITY COMPACTION
METHOD IN ALL OTHER AREAS.
PROPOSED CONTOURS SHOW FINISHED GRADE ELEVATIONS. BUILDING PAD AND PAVEMENT HOLD
DOWNS ARE NOT INCLUDED.
101
100
101
100
XXX.XXXXX.XX-X.X%0
SCALE IN FEET
20 40
PROPOSED PROPERTY
L
INE
,
TYP
.
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
ADA PARKING/RAMP/SIDEWALK DETAIL
1" = 10'-0"
ENTRANCE CROSSWALK DETAIL
1" = 10'-0"
SE TALLGRASS LANE DETAIL
1" = 10'-0"
DETENTION BASIN FLOOD DESIGN
INITIAL BUILD:
100-YR ELEV. = 1015.50
500-YR ELEV. = 1017.50
FULL BUILD:
100-YR ELEV. = 1013.69
500-YR ELEV. = 1017.17
NOTE:
THE PROPOSED BUILDING HAS NO BASEMENT AND
THEREFORE NO SUMP PUMP. THE PROPERTY IS OUTSIDE OF
THE 100 YEAR FLOODPLAIN AND HENCE, THERE IS NO MPE.
SOUTH PEDESTRIAN RAMP DETAIL
1" = 10'-0"
ENCOMPASS
DR
IVE
DW
ELEC.#1 ELEC.#2PROPOSED BUILDING6,710 SF.FFE = 1031.00SE T
A
L
L
G
R
A
S
S
L
A
N
E
1030 1030102610271028102910311031103010311032SKYLINE HONEYLOCUST (4)
URBAN PINNACLE OAK (7)
RED SWITCH GRASS (10)
(70) RED SWITCH GRASS
LITTLE BLUESTEM GRASS (15)
FIRECRACKER SEDUM (15)
GRO-LOW FRAGRANT SUMAC (3)
(13) REGENT SERVICEBERRY
(14) AFTERGLOW WINTERBERRY
(2) JIM DANDY WINTERBERRY
(7) BLOOMSTRUCK HYDRANGEA
JIM DANDY WINTERBERRY (1)
AFTERGLOW WINTERBERRY (1)
GRO-LOW FRAGRANT SUMAC (3)
FIRECRACKER SEDUM (16)
REGENT SERVICEBERRY (1)
FUTURE TREE
LOCATIONS (TYP.)
4' x 4' SQ. TREE RING
STEEL EDGING (TYP.)
4' x 10' PLANTING BED, STEEL EDGING
SHREDDED WOOD MULCH (TYP.)
5' WIDE PLANTING BED
STEEL EDGING,
SHREDDED WOOD MULCH
JAPANESE TREE LILAC (2)
(1) JAPANESE TREE LILAC
JAPANESE TREE LILAC (1)
(14) LITTLE BLUESTEM GRASS
(1) GRO-LOW FRAGRANT SUMAC
(7) PRAIRIE DROPSEED
REGENT SERVICEBERRY (5)
(3) EASTERN REDCEDAR
BLOOMSTRUCK HYDRANGEA (8)
SUBSTITUTED GRASSES
FOR FRONTAGE SHRUB REQ.
EDGER
ROCK MULCH
(UNDER CANOPY)
LITTLE BLUESTEM GRASS (47)
PRAIRIE DROPSEED (17)
PRAIRIE DROPSEED (12)
(8) BLOOMSTRUCK HYDRANGEA
(1) EASTERN REDCEDAR
(1) EASTERN REDCEDAR
BLOOMSTRUCK HYDRANGEA (6)
LITTLE BLUESTEM GRASS (22)
PRAIRIE DROPSEED (21)
CON.TREES QTY COMMON NAME SIZE ROOT
5 Eastern Redcedar
Juniperus virginiana
6` Ht B & B
OVERSTORY QTY COMMON NAME SIZE ROOT
4 Skyline Honeylocust
Gleditsia triacanthos `Skyline`
8` Ht B & B
7 Urban Pinnacle Oak
Quercus macrocarpa `Urban Pinnacle`
8` Ht B & B
UNDERSTORY QTY COMMON NAME SIZE ROOT
4 Japanese Tree Lilac
Syringa reticulata
6` Ht B & B
SHRUBS QTY COMMON NAME SIZE ROOT
19 Regent Serviceberry
Amelanchier alnifolia `Regent`
24" Ht.#5 Cont.
29 Bloomstruck Hydrangea
Hydrangea macrophylla `Bloomstruck`
24" Ht.#5 Cont.
15 Afterglow Winterberry
Ilex verticillata `Afterglow`
24" Ht.#5 Cont.
3 Jim Dandy Winterberry
Ilex verticillata `Jim Dandy`
24" Ht.#5 Cont.
7 Gro-Low Fragrant Sumac
Rhus aromatica `Gro-Low`
12" Ht #5 Cont.
GRASSES QTY COMMON NAME SIZE ROOT
80 Red Switch Grass
Panicum virgatum `Shenandoah`
6" HT.#1 Cont.
98 Little Bluestem Grass
Schizachyrium scoparium
12" Ht #1 Cont.
57 Prairie Dropseed
Sporobolus heterolepis
6" HT.#1 Cont.
PERENNIALS QTY COMMON NAME SIZE ROOT
31 Firecracker Sedum
Sedum x `Firecracker`
6" HT.#1 Cont.
PLANT SCHEDULE
09/11/2018 2ND CITY STIE PLAN SUBMITTAL DNA/BLF
22051 C5-LANDSCAPE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PLANTING PLAN
C5-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C5-10 PLANTING PLAN
---- 18-22051 C5-10
0
SCALE IN FEET
20 40
AS REQUIRED IN THE CITY OF WAUKEE, IOWA ZONING CODE.
LOT DATA:
31,045 SF = TOTAL LOT AREA
K-PUD = LOT'S ZONING DISTRICT
76 LF = LENGTH OF SETBACK BETWEEN R.O.W. AND PARKING
7761 SF = REQUIRED OPEN SPACE
(CODE: 25% OF TOTAL LOT AREA, 31,045 x 25% = 7761)
11,164 SF = OPEN SPACE SHOWN (36% OF LOT AREA)
15 OVERSTORY TREES REQUIRED
12 OVERSTORY TREES = NUMBER OF OVERSTORY TREES FOR LOT REQUIREMENT
(CODE: REQ. OPEN SPACE / 1000 x 1.5, 7761 / 1000 x 1.5 = 11.64 OR 12 TREES)
3 OVERSTORY TREES = NUMBER OF OVERSTORY TREES FOR PARKING SETBACK REQ.
(CODE: LENGTH OF SETBACK / 50 x 2, 76 / 50 x 2 = 3.04 OR 3 TREES)
4 UNDERSTORY TREES REQUIRED
4 UNDERSTORY TREES = NUMBER OF UNDERSTORY TREES FOR LOT REQUIREMENT
(CODE: REQ. OPEN SPACE / 1000 X 0.5, 7761 / 1000 X 0.5 = 3.88 OR 4 TREES)
28 SHRUBS REQUIRED
16 SHRUBS = NUMBER OF SHRUBS REQUIRED FOR LOT REQUIREMENT
(CODE: REQ. OPEN SPACE / 1000 x 2, 7761 / 1000 x 2 = 15.52 OR 16 SHRUBS)
12 SHRUBS = NUMBER OF SHRUBS FOR PARKING SETBACK REQ.
(CODE: LENGTH OF SETBACK / 50 x 8, 76 / 50 x 8 = 12.16 OR 12 SHRUBS)
OTHER REQUIREMENTS:
* 10 OF REQ. TREES MUST BE OVERSTORY
(CODE: 50% OF REQ. TREES SHALL BE OVERSTORY, 19 x 50% = 9.5 OR 10)
* 5 OF REQ. TREES MUST BE EVERGREEN
(CODE: 25% OF REQ. TREES SHALL BE EVERGREEN, 19 x 25% = 4.75 OR 5)
TOTAL PLANTS SHOWN ON PLAN
20 TREES
73 SHRUBS,
266 PERENNIALS & GRASSES
CITY LANDSCAPE REQUIREMENTS
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/25/2018 3RD CITY SITE PLAN SUBMITTAL CWT
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C5-LANDSCAPE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PLANTING NOTES &
DETAILS
C5-11
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
LUSH DENTAL
DEVELOPMENT
18-22051
C5-11 PLANTING NOTES & DETAILS
---- 18-22051 C5-11
REMOVE AT MINIMUM THE TOP HALF OF WIRE
BASKETS, BURLAP, TWINE - REMOVE THESE AND ALL
NON-BIODEGRADIBLE MATURIALS FROM THE
PLANTING PIT. AVOID CUTTING OR SCARING ROOTS.
ANY ROOTS THAT ARE SCARED OR BROKEN DURING
PLANTING SHOULD BE CUT CLEAN AT 90 DEGREES
BACKFILL PLANTING PIT PER TREE PLANTING
SPECIFICATIONS WHEN PROVIDED, OR WITH NATIVE
SOIL-EXCEPT WHEN IN HEAVY CLAY, MIX AMENDED
TOPSOIL FROM A LOCAL SOURCE WITH NATIVE SOIL.
DO NOT TAMP SOIL, BUT SATURATE WITH WATER
THROUGHOUT BACKFILL PROCESS.
EXCAVATE PLANTING PIT TO A DEPTH EQUAL TO
THE DEPTH OF THE ROOTBALL MINUS 3" AND A
MINIMUM TWICE THE DIAMETER OF THE ROOTBALL
3" LAYER OF SHREDDED HARDWOOD MULCH
MOUNDED AT EDGE TO FORM A SHALLOW SAUCER -
DO NOT PLACE MULCH WITHIN 3" OF TRUCK. WHEN IN
PLANT BED, SUBSTITUTE WITH PLANT BED MULCH.
ROOTBALL DIA
2X ROOTBALL DIA
DEPTH OF
ROOTBALL
NEVER CUT PRIMARY LEADER
PRUNE ALL BROKEN, DAMAGED, OR RUBBING LIMBS
AND BRANCHES IMMEDIATELY AFTER PLANTING -
ALL PRUNING CUTS CLEAN AT 90 DEGREES
TREES 8'+TREES 6'-8'
SET ROOT FLAIR ABOVE GRADE 3"
WHEN STAKED, ATTACH 1/2" WIDE NYLON
STRAPPING SNUGLY AROUND TRUCK AND, WITH
SOME LOOSENESS, TO STAKES AS SHOWN
NOTE:
* AVOID STAKING
UNLESS
NECESSARY.
* NO STAKING
TREES
UNDER 6'.
STAKING
DIAGRAM
MUST MAINTAIN TRUNK IN VERTICAL ORIENTATION
MULCH - PER PLANS & NOTES
PLANTING BED - SOIL PREPARATION PER PLANS
& NOTES
LAWN OR GROUND COVER
FINISH GRADE
LANDSCAPE EDGING AND STAKING - PER PLANS
& NOTES
SUBGRADE - PER PLANS & NOTES
MULCH, PER PLANS & NOTES
BACKFILL PLANTING PIT PER SHRUB PLANTING
SPECIFICATIONS WHEN PROVIDED, OR WITH NATIVE
SOIL-EXCEPT WHEN IN HEAVY CLAY, MIX AMENDED
TOPSOIL FROM A LOCAL SOURCE WITH NATIVE SOIL
EXCAVATE PLANTING PIT TO A DEPTH EQUAL TO THE
DEPTH OF THE ROOTBALL / CONTAINER MINUS 3" AND
A MINIMUM TWICE THE DIAMETER OF THE ROOTBALL
/ CONTAINER - TILL ALL PLANTING BEDS TO A
MINIMUM DEPTH OF 6" THROUGHT
PLACE ROOTBALL ON UNDISTURBED SOIL AND
ENSURE PLANT IS PLUMB
ALL PLANTS TO BE INSTALLED SO THAT THE TOP OF
THE CROWN OF THE PLANT IS SLIGHTLY ABOVE
FINISH GRADE 3"
ROOTBALL DIA
2 TIMES ROOTBALL DIA
DEPTH OF
ROOTBALL
CUT AND REMOVE AT MINIMUM THE TOP HALF OF
WIRE BASKETS, BURLAP AND/OR TWINE, OR ENTIRE
CONTAINER, AND REMOVE FROM THE PLANTING PIT,
SCARIFY ROOTS FOR ALL CONTAINERIZED PLANTS 5
GALLONS OR SMALLER
CONTAINER DIA
2 TIMES CONTAINER DIA
SHRUB PLANTING DETAIL
NO SCALE
LANDSCAPE EDGING DETAIL
NO SCALE
TREE PLANTING DETAIL
NO SCALE
UNDISTURBED SOIL
EDGE OF PLANTING BED - PER PLANS &
NOTES
PLANT UNDER DRIP LINE OF LIMBED UP
SHRUBS AND TREES
STAGGER SPACING WHERE POSSIBLE
EDGE OF STRUCTURE OR PAVING
PLANT PERIMETER AT SPECIFIED SPACING
UNLESS OTHERWISE NOTED, PLANT UP TO
EXISTING DRIP LINE OF ADJACENT SHRUBS
LAYER OF MULCH AS INDICATED ON PLAN
TILL ALL PLANT BEDS TO A MINIMUM DEPTH OF 6" AND
BACKFILL PER SPECIFICATIONS, WHEN PROVIDED - IN
AREAS WITH HEAVY CLAY OR ROCKY SOILS AMEND
WITH PLANTING SOIL FROM A LOCAL SOURCE
ALL PLANTS TO BE INSTALLED SO THAT THE TOP OF
THE CROWN OF THE PLANT IS SLIGHTLY ABOVE
FINISH GRADE 3"
CUT AND REMOVE THE ENTIRE CONTAINER AND
SCARIFY, AS NECESSARY, ROOTS FOR ALL
CONTAINERIZED PLANTS 5 GALLONS OR SMALLER
PLACE ROOTBALL ON UNDISTURBED SOIL AND
ENSURE PLANT IS PLUMB
PERENNIAL PLANTING DETAIL
NO SCALE
PLAN
SECTION
1.COORDINATE LOCATION OF ALL UTILITIES (LINES, DUCTS, CONDUITS,
SLEEVES, FOOTINGS, ETC.) WITH LOCATIONS OF PROPOSED
LANDSCAPE ELEMENTS (FENCE, FOOTINGS, TREE ROOTBALLS, ETC.).
CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO OWNER'S
REPRESENTATIVE PRIOR TO CONTINUING WORK.
2.SAVE AND PROTECT ALL EXISTING TREES NOT NOTED TO BE
REMOVED.
3.REMOVE ALL CONSTRUCTION DEBRIS AND MATERIALS INJURIOUS TO
PLANT GROWTH FROM PLANTING PITS AND BEDS PRIOR TO
BACKFILLING WITH PLANTING MIX.
4.LAWN AREAS SHALL HAVE 8" MINIMUM DEPTH OF TOPSOIL. TOPSOIL
SHALL BE COMPACTED TO 85% MAXIMUM DENSITY AT OPTIMUM
MOISTURE CONTENT.
5.REFER TO PLANTING DETAILS PLAN FOR AMENDED SOIL DEPTH IN
PLANTING BEDS AND SURROUNDING TREES. REFER TO
SPECIFICATIONS FOR MIX TYPE.
6.FIELD STAKE PLANTINGS ACCORDING TO PLAN. OWNER'S
REPRESENTATIVE SHALL APPROVE ALL PLANT LOCATIONS PRIOR TO
INSTALLATION. OWNER RESERVES THE RIGHT TO REVISE PLANTING
LAYOUT AT TIME OF INSTALLATION.
7.ALL PLANT MATERIALS SHALL BE TRUE TO THEIR SCIENTIFIC NAME
AND SIZE AS INDICATED IN THE PLANT SCHEDULE.
8.IF DISCREPANCIES EXIST BETWEEN THE NUMBER OF PLANTS DRAWN
ON THE PLANTING PLAN AND THE NUMBER OF PLANTS IN THE
SCHEDULE, THE PLANTING PLAN SHALL GOVERN.
9.OWNER RESERVES THE RIGHT TO REVISE QUANTITIES TO SUIT
BUDGET LIMITATIONS. CONTRACTOR'S UNIT BID PRICES SHALL
PREVAIL FOR ANY CHANGES IN QUANTITIES.
10.ANY PROPOSED SUBSTITUTIONS OF PLANT SPECIES SHALL BE MADE
WITH PLANTS OF EQUIVALENT OVERALL FORM, HEIGHT, BRANCHING
HABIT, FLOWER, LEAF, COLOR, FRUIT AND CULTURE, AND ONLY
AFTER WRITTEN APPROVAL OF THE OWNER'S REPRESENTATIVE AND
OWNER.
11.ALL PLANT MATERIALS MUST CONFORM TO AMERICAN STANDARDS
FOR NURSERY STOCK (A.N.S.I.), LATEST EDITION PUBLISHED BY THE
AMERICAN ASSOCIATION OF NURSERYMEN, WASHINGTON D.C.
LARGER SIZED PLANT MATERIALS OF THE SPECIES LISTED MAY BE
USED IF THE STOCK CONFORMS TO A.N.S.I.
12.ALL PLANT MATERIAL SHALL BE GUARANTEED TO BE IN A LIVE AND
HEALTHY GROWING CONDITION FOR ONE FULL GROWING SEASON
(ONE YEAR) AFTER FINAL PROJECT ACCEPTANCE OR SHALL BE
REPLACED FREE OF CHARGE WITH THE SAME GRADE AND SPECIES.
ALL TREES SHALL HAVE A STRONG CENTRAL LEADER.
13.CONTRACTOR IS RESPONSIBLE FOR ALL DAMAGE DUE TO
OPERATIONS. ANY AREAS THAT ARE DISTURBED SHALL BE
RESTORED TO ITS ORIGINAL CONDITION AT NO ADDITIONAL COST TO
THE OWNER.
14.PLANTING BED EDGING - USE 1/8" x 4" METAL EDGING IN ALL AREAS
WHERE PLANTING BED MEETS LAWN AREAS OR WHERE INDICATED.
USE 12" METAL SPIKES AS INSTRUCTED BY MANUFACTURER.
15.PROVIDE SHREDDED HARDWOOD MULCH, NATURAL COLOR,
SURROUNDING ALL PROPOSED TREES TO A 3-INCH MINIMUM DEPTH
AS SHOWN IN TREE PLANTING DETAIL. DO NOT USE AN
UNDERLAYMENT SUCH AS PLASTIC SHEET OR LANDSCAPE FABRIC. IF
LOCATED WITHIN A PLANT BED, SUBSTITUTE THIS MULCH WITH THE
MULCH CALLED FOR WITHIN THAT PLANT BED. APPLY PRE-EMERGENT
TO ALL PLANTING BEDS PRIOR TO MULCHING.
16.PROVIDE SHREDDED HARDWOOD MULCH, NATURAL COLOR, IN ALL
PLANTING BEDS 3-INCH MINIMUM DEPTH. DO NOT USE AN
UNDERLAYMENT SUCH AS PLASTIC SHEET OR LANDSCAPE FABRIC.
APPLY PRE-EMERGENT TO ALL PLANTING BEDS PRIOR TO MULCHING.
17.PROVIDE ROCK MULCH UNDER CANOPY AS INDICATED ON PLAN. GET
PRIOR APPROVAL BY OWNER AND ARCHITECT REGARDING ROCK
TYPE BEFORE INSTALLATION.
18.ALL TURF AREAS DISTURBED BY CONSTRUCTION SHALL BE SODDED.
SOD SECTIONS SHALL BE NO SMALLER THAN 24" X 36" STAKED IN
PLACE WITH BIODEGRADABLE SOD STAKES WHEN SLOPE IS STEEPER
THAN 5:1 OR WHEN CONDITIONS REQUIRE.
19.FOR SOD, FOLLOW IOWA SUDAS (STATEWIDE URBAN DESIGN AND
SPECIFICATIONS) FOR SODDING SPECIFICATIONS. (WWW.
IOWASUDAS.ORG)
20.IRRIGATION REQUIRED - IRRIGATION SYSTEM SHALL BE
CONSTRUCTED AS A 'DESIGN BUILD' PROJECT AND SERVICE ALL
GREEN SPACE INCLUDING LAWN AND PLANTING BEDS. CONTRACTOR
TO SUBMIT DRAWING FOR APPROVAL BY ENGINEER AND LANDSCAPE
ARCHITECT.
21.FOR PLANT, SHRUB, AND TREE LOCATIONS: CONTRACTOR IS
PERMITTED TO USE DISCRETION AS NECESSARY TO AVOID
DRIVEWAYS, UTILITIES, OR OTHER CONFLICTS. THE TOTAL NUMBER
OF PLANTS, INCLUDING SHRUBS AND TREES SHALL MEET CITY CODE.
ANY PROPOSED SUBSTITUTIONS TO THE PLANTING PLAN SHALL BE
APPROVED IN WRITING BY THE WAUKEE DEVELOPMENT SERVICES
DEPARTMENT.
22.INDICATED QUANTITIES ARE ESTIMATES AND SHOULD BE CONFIRMED
BY THE CONTRACTOR/BIDDER.
23.MINIMUM PLANTING HEIGHTS ARE AS FOLLOWS: DECIDUOUS
OVERSTORY TREE 8' MIN., EVERGREEN OVERSTORY 6' MIN.,
DECIDUOUS UNDERSTORY 6' MIN., SHRUBS 2' HT.
GENERAL PLANTING NOTES
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
09/25/2018 3RD CITY SITE PLAN SUBMITTAL CWT
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C6-TRASH ENCLOSURE
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
PROPOSED TRASH
ENCLOSURE
C6-10
22051
BLF/DNA
NSG/DNA
DAJ
08/21/18
DOWNING
CONSTRUCTION
LUSH DENTAL
DEVELOPMENT
18-22051
C6-10 PROPOSED TRASH ENCLOSURE
---- 18-22051 C6-10
NOTE:
THE CLARITY OF THESE PLANS DEPENDS UPON COLOR
COPIES. IF THIS TEXT DOES NOT APPEAR IN COLOR, THIS IS
NOT AN ORIGINAL PLAN SET AND MAY RESULT IN
MISINTERPRETATION.
NOTE:
DRAWINGS SHOWN ON THIS
SHEET ARE NOT TO SCALE.
09/11/2018 2ND CITY SITE PLAN SUBMITTAL DNA/BLF
22051 C7-SITE LIGHING PLAN
THIS DOCUMENT IS THE PROPERTY OF I & S GROUP, INC.
AND MAY NOT BE USED, COPIED OR DUPLICATED
WITHOUT PRIOR WRITTEN CONSENT.
DATE
REVISION SCHEDULE
DESCRIPTION BY
PROJECT NO.
CAD FILE NAME
DRAWN BY
DESIGNED BY
ORIGINAL ISSUE DATE
CLIENT PROJECT NO.
REVIEWED BY
PROJECT
SHEET
TITLE
WAUKEE IOWA
SITE LIGHTING &
PHOTOMETRIC PLAN
C7-10
22051
--
--
--
08/21/18
DOWNING
CONSTRUCTION
LUSH DENTAL
DEVELOPMENT
18-22051
C7-10 SITE LIGHTING & PHOTOMETRIC PLAN
---- 18-22051 C7-10
T.O. MAIN FLOORSLAB0"T.O. SECONDFLOOR PLY.13'-8 3/4"T.O. FOUNDATION-8"T.O. MAIN PLATE12'-0"PARAPET-117'-2 3/4"2nd S.F. HEAD22'-4 3/4"SECOND PLATE23'-8 3/4"S.F. SILL HT.1'-6"B.O. CANOPY10'-8"S.F. HEAD HT9'-0"PARAPET-219'-3"T.O. RIDGE30'-6"STEEL CANOPYSTEEL CANOPYDARK GRAY NICHIHA (HORZ.)HORIZONTAL CEMENT BOARD SIDING PANELS(PRE-FINISHED WOOD GRAINED)4" PRE-FINISHED METAL CAPPRE-FINISHED METAL WRAPPED FASCIASSR METAL ROOFINGBLACK NICHIHA (VERT.)STEEL CANOPYCULTURED STONE VENEERHSS STEEL COLUMNS PER STRUCTURALKNOX BOXADDRESS SIGNAGE LOCATIONPER LOCAL CODE REQUIREMENTSTYP.2'-1"TYP.5'-5"TYP.1'-8"CUSTOM DOUBLE TIE RODSCUSTOM SINGLE TIE RODS0"10'-8 3/4"1'-0"1'-8"2'-1"5'-5"1'-6"4" PRE-FINISHED METAL CAPSIGNAGE LOCATION VERIFY W/ OWNERSILL HT1'-6"STOOPSTOOPCONCRETE PIER FOOTING PER STRUCT.STOOPBEYONDPREFINISHED COMMERCIAL SIZED DOWNSPOUTSPREFINISHED COMMERCIAL SIZED DOWNSPOUTST.O. THICKENEDGARAGE SLAB7"f: 515.961.0468THIS PLAN IS THE PROPERTY OF DOWNING CONSTRUCTION INC.ANY USE WITHOUT WRITTEN PERMISSION IS STRICTLY PROHIBITED!PLAN NO. =DWG. LISTREVISIONSORIGINAL CONSTRUCTION DOCUMENTDRAWN BY: www.downingconstruct.comwww.downingplanroom.com509 E Scenic Valley AveIndianola, IA 50125p: 515.961.5386CONSTRUCTION DOCUMENT SET - PLANS FOR CONSTRUCTIONCGL A-202Lush Family DentalKettlestone DevelopmentWaukee, Iowa 5026315-14702/28/2018 - By OthersCOLOREXTERIORELEVATIONS05/29/2018 - SD Concept05/31/2018 - DD Elevs.06/05/2018 - DD Set07/02/2018 - Bid SetEXTERIOR MATERIAL SELECTIONSROOFING: GUTTER & DOWNSPOUTSROLEX-BLACKROOFING: FASCIA & SOFFIT PANELSROLEX- STANDING SEAM BLACKINCLUDES: VISIBLE FLASHINGSCULTURED STONE VENEERCENTURION | CUTFACE CUT- KENTUCKYSTOREFRONT WINDOW & DOORSKAWNEER-BLACKINCLUDES: OHD. PAINTED TO MATCHSCALE:3/16" = 1'-0"1COLOR - FRONT ELEVATIONSCALE:1/8" = 1'-0"2COLOR - REAR ELEVATIONSCALE:1/8" = 1'-0"3COLOR - LEFT ELEVATIONSCALE:1/8" = 1'-0"4COLOR - RIGHT ELEVATIONFIBER CEMENT PANELINGNICHIHA- CEDAR/TABACCO RIFT SAWNNICHIHA- BLACK VERTICAL PANELS(SW 6258 TRICORN BLACK)NICHIHA- GREY HORIZONTAL PANELS(SW 7674 PEPPERCORN)EXTERIOR AWNINGSSTEEL- POWDER COATED BLACK09/20/2018 - Permit Set
WALL HT.6' -1"GRADE0"T1T21st COURSE HT.1"WALL HT.6' -1"GRADE0"T1T21st COURSE HT.1"WALL HT.6' -1"GRADE0"TaTb1st COURSE HT.1"WALL HT.6' -1"GRADE0"TaTb1st COURSE HT.1"f: 515.961.0468THIS PLAN IS THE PROPERTY OF DOWNING CONSTRUCTION INC.ANY USE WITHOUT WRITTEN PERMISSION IS STRICTLY PROHIBITED!PLAN NO. =DWG. LISTREVISIONSORIGINAL CONSTRUCTION DOCUMENTDRAWN BY: www.downingconstruct.comwww.downingplanroom.com2500 West 2nd Ave.Indianola, Iowa 50125p: 515.961.5386CONSTRUCTION DOCUMENT SET - PLANS FOR CONSTRUCTIONCGL T-101Lush Family Dental2505 SE Encompass DriveWaukee, IA15-14708/31/2018TRASHENCLOSURECOLOREDELEVATIONS10/03/2018--/--/------/--/------/--/------/--/------/--/----SCALE:1/2" = 1'-0"1COLORED FRONT ELEVATIONSCALE:1/2" = 1'-0"2COLORED REAR ELEVATIONSCALE:1/2" = 1'-0"3COLORED RIGHT ELEVATIONSCALE:1/2" = 1'-0"4COLORED SIDE ELEVATIONEXTERIOR MATERIAL SELECTIONSMETAL FLASHINGSROLEX- BLACKCULTURED STONE VENEERCENTURION | CUTFACE CUT- KENTUCKYVERTICAL WD. SIDINGSHERWIN WILLIAMS PEPPERCORN SW7674